| 2023-03-10 10:35:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF AN AUTO SERVICE, PARTS AND |
| | EV STORAGE AREAS THAT DOES NOT APPEAR TO HAVE FIRE |
| | RATED SEPARATION. |
| | |
| | THE LIFE SAFETY DESIGN OF THIS OCCUPANCY APPEARS TO BE |
| | MIXED NON-SEPARATED; HOWEVER, IT IS NOT THE OCCUPANCY |
| | CLASSIFICATION THAT AT ISSUE, IT'S THE HAZARD OF |
| | CONTENTS. |
| | |
| | ADDITIONALLY, THESE AREAS ARE NOT ACCESSORY NOR |
| | INCIDENTAL |
| | |
| | PER NFPA 101, CH 6 |
| | |
| | 6.2 HAZARD OF CONTENTS |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL BE |
| | THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF SMOKE |
| | OR GASES GENERATED, AND THE DANGER OF EXPLOSION OR |
| | OTHER OCCURRENCE |
| | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE |
| | OCCUPANTS OF THE |
| | BUILDING OR STRUCTURE. |
| | |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED DESIGN |
| | PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING |
| | JURISDICTION FOR REVIEW AND APPROVAL ON THE BASIS OF |
| | THE CHARACTER OF THE |
| | CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED IN |
| | THE BUILDING OR |
| | STRUCTURE. |
| | |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF HAZARD |
| | OF CONTENTS EXIST IN DIFFERENT PARTS OF A BUILDING OR |
| | STRUCTURE, THE MOST |
| | HAZARDOUS SHALL GOVERN THE CLASSIFICATION, UNLESS |
| | HAZARDOUS AREAS ARE |
| | SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND |
| | THE APPLICABLE |
| | SECTIONS OF CHAPTERS 11 THROUGH 43 |
| | |
| | VEHICLES UNDER REPAIR, EVEN ELECTRICAL, POSE A RELATIVE |
| | DANGER OF THE START |
| | AND SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES |
| | GENERATED, AND THE |
| | DANGER OF EXPLOSION OR OTHER OCCURRENCE POTENTIALLY |
| | ENDANGERING THE LIVES |
| | AND SAFETY OF THE OCCUPANTS OF THE BUILDING. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR THE REQUIRED FIRE RATED |
| | SEPARATION OF THESE AREAS OR |
| | JUSTIFY WITH SPECIFIC DETAILS AND CODE REFERENCES TO |
| | NOT SEPARATE. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |