| 2023-03-01 09:22:16 | 1ST REVIEW FMC |
| | PERMIT: 23021468 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1: THIS REVISION ELIMINATES THE AHU-2. |
| | PROVIDE THE EQUIPMENT SIZING CALCULATIONS SHOWING THIS |
| | DESIGN WILL BE SUFFICIENT FOR THIS BUILDING. |
| | |
| | 2) SHEET M6.1: THE OUTDOOR AIR CALCULATIONS NOW SHOW |
| | THE AHU-1 IS SUPPLING ALL REQUIRED OUTDOOR AIR FOR THIS |
| | BUILDING. IT ALSO SHOWS A LOBBY IN THIS NEW OUTDOOR AIR |
| | CALCULATION. THE TOTAL REQUIRED OUTDOOR AIR FOR THE |
| | BUILDING IS 1109 CFM. THE EQUIPMENT SCHEDULE SHOWS THE |
| | MAX. CFM???S FOR AHU-1 IS 450 CFM???S OF OUTDOOR AIR. |
| | THIS WILL NOT MEET THE REQUIRED OUTDOOR AIR REQUIRED |
| | BASED ON THE OCCUPANCIES PRESENTED IN THIS REVISED |
| | DESIGN FOR THIS BUILDING. CORRECT THE AIR BALANCE CHART |
| | ONCE THE CORRECTIONS ARE MADE IN THIS DESIGN. FBC |
| | 107.3.5 |
| | |
| | 3) SHEET M2.1: THIS SHEET IS NOT CONSISTENT WITH THE |
| | REVISED M6.1 SHEET. PROVIDE DRAWINGS THAT ARE |
| | CONSISTENT. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |