| 2023-03-02 11:06:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF A PROPOSED NEW STORAGE |
| | ROOM WITH 2-HOUR RATED WALLS; HOWEVER, THERE IS NO |
| | INDICATION OF A FIRE RATED DOOR ASSEMBLY TO THIS ROOM. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE A RATED DOOR ASSEMBLY EQUAL TO PROPOSED |
| | RATED WALLS. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF WHAT IS BEING PROPOSED TO |
| | STORE WITHIN THIS STORAGE ROOM |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE DETAILS ON THE PROPOSED STORAGE |
| | MATERIALS/COMMODITY/HAZARD CLASSIFICATIONS. |
| | |
| | |
| | 3) THERE IS NO INDICATION OF THE RACKS/SHELVING TYPE, |
| | LOCATION AND HEIGHT BEING USED IF ANY. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE DETAILS OF THE RACKS/SHELVING TYPE, |
| | LOCATION AND HEIGHT. |
| | |
| | |
| | 4) THERE IS NO INDICATIONS OF EXISTING FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS |
| | EXISTING FIRE SPRINKLER PROTECTION. |
| | |
| | |
| | 5) THERE IS NO INDICATIONS OF EXISTING FIRE ALARM |
| | PROTECTION. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS |
| | EXISTING FIRE ALARM PROTECTION AND THE LOCATION OF ANY |
| | DEVICES WITHIN THIS ROOM. |
| | |
| | |
| | 6) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AS TO WHAT |
| | SYSTEM MAYBE EXISTING. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |