Plan Review Details - Permit 23021403
Plan Review Stops For Permit 23021403
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By lbond Date 2023-04-06 Time 09:48 Rev Time 0.00
Received By lbond Date 2023-04-06 Time 09:48 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By lbond Date 2023-03-21 Time 10:58 Rev Time 0.00
Received By lbond Date 2023-03-21 Time 10:58 Sent To  
Notes
2023-03-21 10:59:22BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23021403
  
 REVIEWED: MARCH 21, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENT:
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By lbond Date 2023-04-07 Time 07:59 Rev Time 0.00
Received By lbond Date 2023-04-07 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 08:06 Rev Time 0.00
Received By lbond Date 2023-03-28 Time 08:06 Sent To  
Notes
2023-03-28 08:21:07ALL COMMENTS MUST BE ADDRESSED FIRST.
 PLEASE RESPOND ACCORDINGLY TO EACH COMMENT. THANK YOU!
  
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-13 Cont ID  
Sent By jleahy Date 2023-04-13 Time 09:08 Rev Time 0.00
Received By jleahy Date 2023-04-13 Time 08:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By jleahy Date 2023-03-14 Time 14:07 Rev Time 0.00
Received By jleahy Date 2023-03-14 Time 13:52 Sent To  
Notes
2023-03-14 14:11:58FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) DRINKING FOUNTAIN TO BE GFCI PROTECTED 422.5
  
 2) CIRCUIT FOR DRINKING FOUNTAIN AND GARAGE DOOR OPENER
 ARE THE SAME CIRCUIT. 210.23(A)(1,2)
  
 3) TWO OF THE AC UNITS ARE ON THE SAME CIRCUIT. 210.23

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-01 Cont ID  
Sent By cwalker Date 2023-03-01 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-03-01 10:08:49FIRE PROVISO COMMENTS:
  
 (1) AN EVALUATION OF THE FIRE SPRINKLER SYSTEM SHALL BE
 CONDUCTED BY A PROPERLY LICENSED FIRE SPRINKLER
 CONTRACTOR TO ENSURE THE EXISTING FIRE SPRINKLER SYSTEM
 IS ADEQUATE FOR THE PROPOSED OCCUPANCY AND COMMODITY
 CLASSIFICATION.
  
 (2) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (3) THE EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (5) THE PLAN SUBMITTAL DID NOT INDICATE THE LOCATION OF
 THE NEAREST WATER SOURCE TO THE FIRE DEPARTMENT
 CONNECTION OF THE EXISTING FIRE SPRINKLER SYSTEM. THE
 LOCATION MUST MEET THE REQUIREMENTS OF NFPA 13.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 09:05 Rev Time 0.00
Received By medwards Date 2023-04-05 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 08:18 Rev Time 0.00
Received By lbond Date 2023-02-28 Time 09:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 08:07 Rev Time 0.00
Received By lbond Date 2023-03-28 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 09:05 Rev Time 0.00
Received By medwards Date 2023-04-14 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By medwards Date 2023-03-07 Time 10:57 Rev Time 0.00
Received By medwards Date 2023-03-07 Time 10:57 Sent To  
Notes
2023-03-07 10:58:041ST REVIEW FMC
 PERMIT: 23021403
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS DO NOT SHOW THE NEW OVER
 HEAD DOOR IN THE CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS INCLUDING THE OVERHEAD DOOR. FEC C402.5.4
 AND C402.5.6
  
 2) PROVIDE THE SMOKE DETECTORS IN THE SUPPLY DUCT FOR
 EACH OF THESE RTU???S. THEY SHARE THE SUPPLY SO ARE
 REQUIRED FMC 606.2.2
  
 3) PROVIDE A ROOF DRAWING INDICATING THE LOCATIONS OF
 THE RTU???S AND GUARD PROTECTION IF REQUIRED BY FMC
 304.11
  
 4) INDICATE THE LOCATION OF THE ACCESS FOR THE RTU???S
 ON THE ROOF DRAWING. FMC 306.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By ccole Date 2023-04-10 Time 16:16 Rev Time 0.00
Received By ccole Date 2023-04-10 Time 16:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By ccole Date 2023-03-07 Time 09:50 Rev Time 0.00
Received By ccole Date 2023-03-07 Time 08:52 Sent To  
Notes
2023-03-07 09:56:101ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23021403
 3/7/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: BASED ON THE PLANS IT APPEARS THE SCOPE
 OF PLUMBING WORK IS TO REPLACE THE WATER HEATER, THE
 RESTROOM FIXTURES, AND INSTALL A NEW HOSE BIB. PLEASE
 CONFIRM AND PROVIDE NOTES OR DETAILS ON THE PLAN
 SPECIFYING ACCESSIBLE WATER CLOSETS AND LAVATORIES WILL
 BE INSTALLED- SECS. (213.1- 213.3.4), (604.1- 604.4), &
 (606.1- 606.5) FBC ACC.
  
 2) P-1: THE SANITARY RISER SHOWS EXISTING DRAIN AND
 VENT PIPING HOWEVER PLEASE NOTE THE FIXTURE DRAIN FOR
 THE DRINKING FOUNTAINS SHOULD NOT BE CONNECTING TO THE
 WET VENT FOR THE BATHROOM FIXTURES, AND SHOULD BE
 MAKING CONNECTION DOWNSTREAM OF THE VENT- SEC. 912.1
 FBC P.
  
 3) P-1: THE WATER HEATER DETAIL SHOWS A MOP SINK BELOW
 THE UNIT HOWEVER NO PIPING FOR THE FIXTURE IS SHOWN IN
 THE RISER DRAWINGS. PLEASE NOTE THE MOP SINK IS A
 REQUIRED FIXTURE FOR STORAGE OCCUPANCIES- TABLE 403.1
 FBC P.
  
 4) P-1: A MEANS OF LIMITING THE HOT WATER TEMPERATURE
 DELIVERY OTHER THAN THE WATER HEATER THERMOSTAT IS
 REQUIRED. PLEASE PROVIDE A MASTER THERMOSTATIC MIXING
 VALVE AND REVISE THE WATER HEATER DETAIL TO SHOW THE
 LOCATION OF THE DEVICE AND PIPING CONNECTIONS- SEC.
 607.1.1 FBC P.
  
 5) P-1: TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORIES THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SECS. 419.5 & 607.1.2 FBC
 P.
  
 6) P-1: THE 1/2-INCH HW SUPPLY PIPES TO THE PUBLIC
 LAVATORIES SHALL NOT EXCEED 2FT. TO TERMINATION FROM
 THE HW SOURCE PER TABLE C404.5.1 FBC ENERGY. IN ORDER
 TO MEET COMPLIANCE, PROVIDE EITHER A RECIRCULATION PUMP
 AND LINE, OR POINT OF USE WATER HEATERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-18 Cont ID  
Sent By lbond Date 2023-04-07 Time 07:59 Rev Time 0.00
Received By lbond Date 2023-04-07 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-14 Cont ID  
Sent By jleahy Date 2023-03-14 Time 14:15 Rev Time 0.00
Received By jleahy Date 2023-03-14 Time 14:15 Sent To  
Notes
2023-03-21 11:03:41SURVEY DIGITAL SIGNATURE AND SEAL FAILED
2023-03-07 10:58:58MECHANICAL DIGITAL SIGNATURE APPROVED ME
2023-03-07 09:06:32PLUMBING PLAN PASSED.

Review Stop Z ZONING
Rev No 1 Status N Date 2023-03-21 Cont ID  
Sent By ASangele Date 2023-03-21 Time 14:36 Rev Time 0.00
Received By asangele Date 2023-03-21 Time 14:36 Sent To  
Notes
***NONE***