Plan Review Details - Permit 23021400
| Plan Review Stops For Permit 23021400 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-28 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-03-28 |
Time |
06:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-21 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-03-20 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2023-03-21 07:34:07 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 23021400 | | | ADD: 801 S OLIVE AVE # 1518 | | | CONT: CRITICAL PATH CONSTRUCTION | | | TEL: 561-863-2226 | | | E-MAIL: CRITICAL.PATH@ ATT.NET | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: TUES. MAR. 21ST /2023 | | | ACTION: DENIED | | | | | | 1) THIS REVIEW THE PERMIT APPLICATION DESCRIPTION OF | | | WORK STATES REPLACE WITH ENGINEERED GLUE DOWN FLOORING. | | | SUBMITTED SPEC SHEET FOR PROFLEX SUPER SIM-90 & FLAME | | | SPREAD TEST FOR PROFLEX SUPER SIM 90. | | | THIS REVIEW CYCLE THERE WERE NO TEST REPORTS SUMITTED | | | FOR ENGINEERED WOOD FLOORING. | | | | | | 1ST ROUND COMMENT. FLOOR INSULATION/ UNDERLAYMENT | | | (FBC-B 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP), | | | LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE | | | HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO | | | THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS | | | LISTED UNDER EACH OF THE STANDARDS FOR A 6-INCH | | | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 1A) 3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE | | | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS | | | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 1B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 1C) 3RD REQUEST. FBC-B 804.4.4.1 SOFT FLOOR FINISHES | | | (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING) | | | WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 | | | -PILL TEST (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. | | | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH | | | CLASSIFICATION AS REQUIRED IN SECTION 804.2 | | | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF | | | THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253 | | | | | | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT | | | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-14 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-03-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-03-14 08:26:17 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 23021400 | | | ADD: 801 S OLIVE AVE # 1518 | | | CONT: CRITICAL PATH CONSTRUCTION | | | TEL: 561-863-2226 | | | E-MAIL: CRITICAL.PATH@ ATT.NET | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. MAR. 14TH/2023 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST. THE DESCRIPTION OF WORK IS INSTALL | | | ENGINEERED GLUE DOWN FLOOR. DOES ENGINEERED GLUE DOWN | | | MEAN WOOD LAMINATE OR LUXURY VINYL TILE/ PLANK. | | | SUBMITTED THIS REVIEW IS A FLAME SPREAD REPORT FOR | | | PROFLEX SUPER SIM 90, PROFLEX SUPER SIM 90 WAS ONLY | | | TESTED FOR TILE AND MARBLE. PROFLEX DOES HAVE LV-200 | | | TESTED FOR WOOD LAMINATE AS WELL AS TESTED FOR LVT-LVP | | | FLOORING ALL 3 REQUIRED TEST REPORTS. | | | | | | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, | | | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND | | | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND | | | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING | | | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH | | | OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ | | | NO DROPPED CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE | | | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS | | | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1. | | | EXCEPTION 2. (TILE & MARBLE) INSULATION INSTALLED | | | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT | | | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME | | | SPREAD INDEX OF NOT MORE THAN 200. | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT | | | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-02 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-03-02 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2023-03-02 13:21:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 23021400 | | | ADD: 801 S OLIVE AVE # 1518 | | | CONT: CRITICAL PATH CONSTRUCTION | | | TEL: 561-863-2226 | | | E-MAIL: CRITICAL.PATH@ ATT.NET | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. MAR. 02/2023 | | | ACTION: DENIED | | | | | | 1) THERE IS NO DESCRIPTION OF WORK IN THE PERMIT | | | APPLICATION DESCRIPTION OF WORK. OTHER FLOORING | | | ENGINEERED WOOD. SUBMITTED IS A SALES BROCHURE FOR | | | PROFLEX MSC SOUND CONTROL. THE CITY DOES NOT HAVE TEST | | | REPORTS FOR PROFLEX MSC 90 FOR USE IN ANY APPLICATION, | | | TESTED ON A 6 INCH CONCRETE SLAB, NO DROPPED CEILING. | | | THE CITY DOES HAVE PROFLEX PRODUCT LV 200 TESTED FOR | | | LAMINATE WOOD, LVT & LVP IIC, STC & FLAME SPREAD. | | | | | | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, | | | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND | | | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND | | | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING | | | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH | | | OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ | | | NO DROPPED CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | | | | 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE | | | & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR | | | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE | | | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN | | | 200. | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT | | | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-20 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-06 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2023-03-06 10:05:48 | ******THE PREVIOUS FIRE COMMENTS HAVE NOT BEEN | | | ADDRESSED**** | | | | | | PLEASE PROVIDE THE FINISHED FLOORING PRODUCT NAME AND | | | SPEC SHEETS. | | | | | | THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED BELOW: | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT | | | NAME FOR THE ACTUAL PROPOSED ENGINEERED WOOD FLOORING. | | | | | | ENGINEERED WOOD FLOORING IS MANUFACTURED AROUND THE | | | WORLD BUT NOT ALL ARE TESTED AND MEETING LISTED AND | | | NFPA STANDARDS. | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ENGINEERED | | | WOOD FLOORING NAME AND THE PRODUCT SPEC SHEETS | | | INDICATING THE FIRE BEHAVIOR RATING. | | | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | | WOULD NOT BE REQUIRED. | | | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | | FLOORING, WOOD/VINYL LAMINATES, ENGINEERED WOOD, ETC. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-01 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2023-03-01 13:29:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT | | | NAME FOR THE ACTUAL PROPOSED ENGINEERED WOOD FLOORING. | | | | | | ENGINEERED WOOD FLOORING IS MANUFACTURED AROUND THE | | | WORLD BUT NOT ALL ARE TESTED AND MEETING LISTED AND | | | NFPA STANDARDS. | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ENGINEERED | | | WOOD FLOORING NAME AND THE PRODUCT SPEC SHEETS | | | INDICATING THE FIRE BEHAVIOR RATING. | | | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | | WOULD NOT BE REQUIRED. | | | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | | FLOORING, WOOD/VINYL LAMINATES, ENGINEERED WOOD, ETC. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-28 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-03-22 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-17 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-03 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-02 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-02-28 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-03-02 |
Time |
13:20 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2023-03-02 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|