Plan Review Details - Permit 23021392
Plan Review Stops For Permit 23021392
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 08:08 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 07:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-03-10 Cont ID  
Sent By ccole Date 2023-03-10 Time 08:07 Rev Time 0.00
Received By ccole Date 2023-03-10 Time 07:08 Sent To  
Notes
2023-03-10 08:08:252ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23021392
 3/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISO #2: INCREASE THE SIZE OF ??-INCH GALVANIZED
 PIPE SUPPLYING THE RANGE TO ??-INCH- TABLE G2413.4(1)
 FBC RES.
  
 2) THE RESUBMITTED RISER DRAWING IS MISSING THE PIPING
 TO THE DRYER. A COMPLETE RISER DRAWING IS REQUIRED-
 SEC. 107.3.5.3 WPB.
  
 3) COMBUSTION AIR CALCULATIONS FOR THE GAS RANGE AND
 DRYER NOT PROVIDED- SEC. G2407.1 FBC RES. PLEASE NOTE
 THAT IF USING THE STANDARD METHOD OF INDOOR AIR FOR THE
 RANGE IN ACCORDANCE WITH SEC. G2407.5.1, A TOTAL VOLUME
 OF 6250 CU. FT. IS REQUIRED. PLEASE PROVIDE A BASIC,
 DIMENSIONED FLOOR PLAN DRAWING SHOWING THE LOCATIONS OF
 BOTH THE RANGE AND THE DRYER AND PROVIDE THE
 CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 10:16 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 08:58 Sent To  
Notes
2023-03-03 10:19:561ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23021392
 3/3/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISO #1 & #2: PLEASE PROVIDE THE TOTAL LOW
 PRESSURE PIPING RUN LENGTH FROM THE REGULATOR TO THE
 RANGE- SEC. G2413.14.1 FBC RES. IT APPEARS THE RUN IS
 GREATER THAN 20 FT. SO THE 1/2-INCH GALVANIZED AND
 3/4-IINCH CSST (25-EHD) ARE UNDERSIZED PER TABLES
 G24134(1) [402.4(2)], AND G2413.4(5) [402.4(15) ].
  
 2) SURVEY: PLEASE PROVIDE A CLEARER APPLIANCE AND
 PIPING LOCATION PLAN THAT CLEARLY SHOWS THE ACTUAL
 PHYSICAL LOCATIONS OF THE NEW POOL HEATER, THE BBQ, THE
 TANKLESS WATER HEATER AND THE DRYER- SEC. 107.2.1 WPB.
 THE PLAN SHALL PROVIDE DETAILS AND NOTES IN COMPLIANCE
 WITH THE FBC RES ITEMS A, B, C, ,& E LISTED BELOW.
 A) PE PIPING SHALL NOT BE INSTALLED UNDER ANY PORTION
 OF THE EXISTING BUILDINGS- SEC. G2415.17.1.
 B) THE GAS BBQ SHALL BE INSTALLED WITH CLEARANCES TO
 COMBUSTIBLES PER THE MANUFACTURER???S INSTALLATION
 INSTRUCTIONS AND MAY REQUIRE AN EXHAUST HOOD AND DUCT
 IF INSTALLED UNDER OVERHEAD COMBUSTIBLE CONSTRUCTION-
 SEC. G2447.1.
 C) THE TANKLESS WATER HEATER SHALL BE INSTALLED WITH
 CLEARANCES PER THE MANUFACTURER AND THE EXHAUST SHALL
 BE MINIMUM 4 FT. AWAY FROM OPENINGS INTO THE BUILDING
 INCLUDING OPERABLE WINDOWS AND DOORS, AND SOFFIT VENTS-
 SECS. G2447.2.2, G2427.8 & G2448.1. PLEASE NOTE THE
 MOST STRINGENT CLEARANCES SHALL APPLY.
 D) SHOW THE ROOM THE DRYER WILL BE LOCATED IN AND THE
 ROOM DIMENSIONS. PROVIDE COMBUSTION AIR AND EXHAUST
 VENTILATION FOR THE DRYER- SEE SECS. G2407.1, G2438.1 &
 G2439.1.
 E) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 POOL HEATER HOWEVER THE CURRENT PLAN SHALL SHOW THE
 UNIT WILL BE INSTALLED WITH CLEARANCES PER THE
 MANUFACTURER AND THE EXHAUST SHALL BE MINIMUM 4 FT.
 AWAY FROM OPENINGS INTO THE BUILDING INCLUDING OPERABLE
 WINDOWS AND DOORS, AND SOFFIT VENTS- SECS. G2447.2.2,
 G2427.8 & G2441.1. PLEASE NOTE THE MOST STRINGENT
 CLEARANCES SHALL APPLY.
  
 3) SURVEY: IT APPEARS THE TANKLESS WATER HEATER IS
 BEING INSTALLED AT THE GARAGE. PLEASE CLARIFY IF THE
 GARAGE IS BEING CONVERTED INTO LIVING SPACE AND INCLUDE
 INSTALLATION OF NEW PLUMBING FIXTURES AND PIPING- SEC.
 107.2.1 WPB.
  
 4) THE GAS RISER DRAWINGS AND LOCATION PLAN SHALL BEAR
 THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR WHO
 PREPARED THE DRAWING- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-03-17 Time   Rev Time 0.00
Received By aoliver Date 2023-03-16 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-03-10 Time   Rev Time 0.00
Received By aoliver Date 2023-03-09 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-03-03 Time   Rev Time 0.00
Received By amcgrego Date 2023-03-02 Time 08:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 08:08 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 07:55 Sent To  
Notes
2023-03-17 08:09:54PLUMBING SUB-PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-03-10 Cont ID  
Sent By ccole Date 2023-03-10 Time 08:11 Rev Time 0.00
Received By ccole Date 2023-03-10 Time 07:08 Sent To  
Notes
2023-03-10 08:16:282ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021392
 3/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I WAS UNABLE TO LOCATE A PERMIT FOR THE TANKLESS
 WATER HEATER INSTALLED AT THE OUTBUILDING LABELED AS
 "LIVING SPACE" ON THE DRAWINGS. PLEASE PROVIODE A
 PLUMBING SUB-PERMIT APPLICATION FOR INSTALLATION OF THE
 HEATER, AND A WATER RISER DRAWING- SECS.105.1,107.2.1,
 & 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 10:23 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 08:59 Sent To  
Notes
2023-03-03 10:23:531ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021392
 3/3/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SURVEY: IT APPEARS THE TANKLESS WATER HEATER IS
 BEING INSTALLED AT THE GARAGE. PLEASE CLARIFY IF THE
 GARAGE IS BEING CONVERTED INTO LIVING SPACE AND INCLUDE
 INSTALLATION OF NEW PLUMBING FIXTURES AND PIPING- SEC.
 107.2.1 WPB. PROVIDE RISER DRAWINGS IF APPLICABLE AND A
 PLUMBING SUB-PERMIT- SECS. 105.1 & 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 08:08 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-10 Cont ID  
Sent By ccole Date 2023-03-10 Time 08:09 Rev Time 0.00
Received By ccole Date 2023-03-10 Time 07:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 10:26 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 08:59 Sent To  
Notes
2023-03-03 10:26:22SIGNATURE REVIEW
 PERMIT- 23021392
 3/3/23
  
 RESULTS- DENIED.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 SHALL BE ON THE DRAWINGS- SEC. 107.2.1 WPB.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  