Plan Review Details - Permit 23021382
Plan Review Stops For Permit 23021382
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-04-06 Cont ID  
Sent By jgomez Date 2023-04-06 Time 15:19 Rev Time 0.00
Received By jgomez Date 2023-04-06 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-31 Cont ID  
Sent By jgomez Date 2023-03-31 Time 09:37 Rev Time 0.00
Received By jgomez Date 2023-03-31 Time 09:29 Sent To  
Notes
2023-03-31 09:37:42RESIDENTIAL (R3)THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23021382
 10241 HERONWOOD LN
  
 PREVIOUS COMMENT:
 1- REVISE NOTE ON SURVEY. THE GENERATOR SHALL BE
 LOCATED A MINIMUM OF 10 FT. FROM AIR INTAKES INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. PLEASE CORRECT THE
 NOTE INDICATING 5 FT.
  
 RESPONSE:
 REPEAT COMMENT THREE TIMES. NOT ADDRESSED.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-29 Cont ID  
Sent By jgomez Date 2023-03-29 Time 09:31 Rev Time 0.00
Received By jgomez Date 2023-03-29 Time 09:31 Sent To  
Notes
2023-03-29 09:31:49RESIDENTIAL (R3)SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23021382
 10241 HERONWOOD LN
  
 PREVIOUS COMMENT:
 1- REVISE NOTE ON SURVEY. THE GENERATOR SHALL BE
 LOCATED A MINIMUM OF 10 FT. FROM AIR INTAKES INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. PLEASE CORRECT THE
 NOTE INDICATING 5 FT.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 PREVIOUS COMMENT:
 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 RESPONSE:
 REPEAT COMMENT. PAD ENGINEERING UPLOADED ON 03/24/23 IS
 A COPY. NEED DOCUMENT WITH VERIFIABLE DIGITAL
 SIGNATURE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-23 Cont ID  
Sent By jgomez Date 2023-03-23 Time 18:54 Rev Time 0.00
Received By jgomez Date 2023-03-23 Time 18:36 Sent To  
Notes
2023-03-23 18:54:16RESIDENTIAL (R3)BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23021382
 10241 HERONWOOD LN
  
 1- REVISE NOTE ON SURVEY. THE GENERATOR SHALL BE
 LOCATED A MINIMUM OF 10 FT. FROM AIR INTAKES INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. PLEASE CORRECT THE
 NOTE INDICATING 5 FT.
  
 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By jleahy Date 2023-03-10 Time 09:59 Rev Time 0.00
Received By jleahy Date 2023-03-10 Time 09:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-03-27 Cont ID  
Sent By ccole Date 2023-03-27 Time 12:10 Rev Time 0.00
Received By ccole Date 2023-03-27 Time 12:03 Sent To  
Notes
2023-03-27 12:12:26GAS UNDER PERMIT 23020704.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 07:03 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 06:50 Sent To  
Notes
2023-03-24 07:05:561ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 23021382
 3/24/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE THAT GAS FOR THE GENERATOR CAN BE UNDER A
 SEPARATE PERMIT BY REQUEST.
  
 1) A GAS RISER DRAWING IS REQUIRED PER SEC. 107.3.5.3
 WPB. PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 THE NEW PIPING TO THE GENERATOR AND THE EXISTING THE
 GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION
 G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24
 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS AND OUTLET PRESSURES.
 H) LOCATIONS OF SHUT OFF VALVES.
 I) PIPE SIZING TABLES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-06 Cont ID  
Sent By jgomez Date 2023-04-06 Time 15:19 Rev Time 0.00
Received By jgomez Date 2023-04-03 Time 11:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-31 Cont ID  
Sent By jgomez Date 2023-03-31 Time 09:37 Rev Time 0.00
Received By jgomez Date 2023-03-30 Time 10:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-29 Cont ID  
Sent By jgomez Date 2023-03-29 Time 09:31 Rev Time 0.00
Received By jgomez Date 2023-03-26 Time 07:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-03-24 Time   Rev Time 0.00
Received By amcgrego Date 2023-02-28 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-03-27 Cont ID  
Sent By ccole Date 2023-03-27 Time 12:10 Rev Time 0.00
Received By ccole Date 2023-03-27 Time 12:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 07:03 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 06:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-31 Cont ID  
Sent By jgomez Date 2023-03-31 Time 09:37 Rev Time 0.00
Received By jgomez Date 2023-03-31 Time 09:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-29 Cont ID  
Sent By jgomez Date 2023-03-29 Time 09:32 Rev Time 0.00
Received By jgomez Date 2023-03-29 Time 09:31 Sent To  
Notes
2023-03-29 09:32:14SIGNATURE REVIEW:
  
 PREVIOUS COMMENT:
 1- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 RESPONSE:
 REPEAT COMMENT. PAD ENGINEERING UPLOADED ON 03/24/23 IS
 A COPY. NEED DOCUMENT WITH VERIFIABLE DIGITAL
 SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-23 Cont ID  
Sent By jgomez Date 2023-03-23 Time 18:54 Rev Time 0.00
Received By jgomez Date 2023-03-23 Time 18:43 Sent To  
Notes
2023-03-23 18:55:32SIGNATURE REVIEW:
  
 1- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
2023-03-10 11:41:05ELECTRICAL PAGE SIGNATURE IS APPROVED JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-06 Cont ID  
Sent By vbroglia Date 2023-04-06 Time 15:04 Rev Time 0.00
Received By vbroglia Date 2023-04-06 Time 15:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-07 Cont ID  
Sent By VBroglia Date 2023-03-07 Time 10:13 Rev Time 0.00
Received By vbroglia Date 2023-03-07 Time 10:13 Sent To  
Notes
***NONE***