| 2023-02-28 08:41:13 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. PLEASE VERIFY & CORRECT; SUBMITTED |
| | ROOF SKETCH INDICATES MRH 21 FT. GOOGLE EARTH SHOWS |
| | BUILDING AS BEING 3 STORIES WITH A ROOF; THE MRH @ A |
| | MINIMUM WILL BE GREATER THAN 35 FT. |
| | 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| | 22-0614.01 IS NOT VALID FOR USE AS PER LIMITATIONS: #2; |
| | SHALL NOT BE INSTALLED ON ROOF MEAN HEIGHTS IN EXCESS |
| | OF 33 FT. PLEASE PROVIDE A COMPLETE SET OF 2020 CODE |
| | VERSION PRODUCT APPROVALS/NOA???S FOR THE PROPOSED |
| | ASPHALT SHINGLE ROOFING SYSTEM TO BE USED. INCLUDE |
| | COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5; |
| | EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT 20 < H |
| | < 30; ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE |
| | CORRECT ROOF HEIGHT IS 30 < H < 40. WIND SPEED 170. |
| | PRODUCT APPROVAL FL16709-R10 WILL NOT SATISFY EXPOSURE |
| | CATEGORY C ENCLOSED AREAS; ROOF HEIGHT 30 < H < 40 |
| | WITHOUT USING INSULATION OR PROVIDING ENGINEERED |
| | ENHANCED NAILING. |
| | 4. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |