| 2023-03-07 08:24:25 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23021303 |
| | 3/7/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A REVISION APPLICATION HAS BEEN SUBMITTED WITH A |
| | PRODUCT DATA SHEET FOR AN AO SMITH GAS WATER, AND |
| | APPROVESD PLAN SHEET P201. PLEASE NOTE THE SELECTED |
| | MODEL IS THE SAME MODEL SPECIFIED ON SHEET P201 OF THE |
| | APPROVED PLANS UNDER MASTER PERMIT 21070167. IT IS NOT |
| | CLEAR WHAT THIS REVISION IS FOR. PLEASE NOTE THAT THE |
| | GAS REVIEW UNDER 21070167 WAS REMOVED PER THE |
| | ARCHITECT'S REQUEST AND GAS WAS TO BE UNDER A SEPARATE |
| | PERMIT. CURRENTLY THERE HAS BEEN NO SEPARATE PERMIT |
| | APPLICATION AND GAS PLANS SUBMITTED FOR REVIEW. COPIED |
| | BELOW ARE THE REMAINING SECOND REVIEW COMMENTS UNDER |
| | 21070167 WHICH WERE RECEIVED BY THE ARCHITECT PRIOR TO |
| | THE REQUEST FOR THE SEPARATE PERMIT. PLEASE PROVIDE A |
| | NARRATIVE RESPONSE TO THESE COMMENTS AND THE SEPARATE |
| | GAS PERMIT APPLICATION AND PLANS. |
| | |
| | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21070167 |
| | 8/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 2) FAILED. P106: PROVIDE A GAS PIPING PLAN AND RISER |
| | DRAWING SHOWING COMPLIANCE WITH THE FBC FG AND SECTION |
| | 107.3.5.1.5 WPB. |
| | |
| | B) FAILED. TYPE OF GAS- NATURAL OR LP AND SYSTEM |
| | PRESSURE. TYPE OF GAS NOT PROVIDED. |
| | |
| | C) FAILED. TOTAL BTU LOAD AND WATER HEATER BTU LOADS. |
| | LOADS NOT PROVIDED. |
| | |
| | D) FAILED. TYPES AND SIZES OF GAS PIPING. TYPE OF |
| | PIPING NOT PROVIDED. |
| | |
| | G) FAILED. LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | PLEASE INDICATE THE SELECTED MAKE AND MODEL NUMBER OF |
| | THE REGULATORS, AND SUBMIT MARKED UP OR HIGHLIGHTED |
| | SPECS SHOWING THE SELECTED MODEL, THE INPUT AND OUTPUT |
| | PIPE SIZES AND PRESSURES- SECTION 410.2 FBC FG. PROVIDE |
| | A REGULATOR AND RELIEF VALVE VENTING PLAN AND DIAGRAM |
| | IN ACCORDANCE WITH SECTION 5.3- 5.3.2.1 NFPA 37, UNLESS |
| | THE SPECS SHOW COMPLIANCE WITH SECTION 5.3.1.2 (ITEMS |
| | 1-4). |
| | |
| | I) FAILED. PIPE SIZING TABLES FOR ALL NEW PIPING |
| | INSTALLATIONS. NOT PROVIDED. |
| | |
| | 3) FAILED. INDICATE HOW COMBUSTION AIR IS BEING |
| | PROVIDED TO THE WATER HEATERS AND PROVIDE CALCULATIONS- |
| | SECTION 304.1 FBC FG. NOT PROVIDED ON PLAN. THE |
| | NARRATIVE FROM THE ENGINEER PROVIDES INFORMATION THAT |
| | MUST BE PLACED ON THE PLAN. REFERENCE IS ALSO MADE TO |
| | THE WH MANUAL WHICH HAS NOT BEEN PROVIDED. AS |
| | PREVIOUSLY NOTE THE SPECS AND MANUAL MAY BE DEFERRED. |
| | PLEASE REFER TO SECTION 304.6.2 FBC FG FOR COMBUSTION |
| | AIR OPENING REQUIRMENTS AND PROVIDE INFORMATION AND/OR |
| | DETAILS ON THE PLAN. |
| | |
| | 4) FAILED. PROVIDE A VENTING DIAGRAM IN COMPLIANCE WITH |
| | SECTION 624.1 AND 503.3.2 FBC FG. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VENT. THE ENGINEER'S NARRATIVE |
| | REFRENCES THE MANUAL WHICH HAS NOT BEEN SUBMITTED. |
| | PLEASE REFER TO SECTION 502.1 FBC FG AND INDICATE THE |
| | TYPE OF VENTING SYSTEM TO BE INSTALLED BASED ON THE |
| | CATEGORY OF THE WATER HEATERS- I, II, II, OR IV. |
| | PROVIDE A COMPLETE VENTING PLAN INDICATING THE TYPE OF |
| | MATERIAL, VENT RUN LENGTHS AND TERMINATION LOCATIONS-, |
| | 502, AND 503 FBC FG. PLEASE INCLUDE VENTING HANGING AND |
| | SUPPORT DETAILS- SECTION 503.6.11. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | 3RD REVIEW |
| | 10/14/2021 |
| | |
| | THE ARCHITECT OF RECORD HAS REQUESTED GAS TO BE UNDER A |
| | SEPARATE PERMIT. COMPLETE PLANS AND SPECIFICATIONS |
| | SHALL BE SUBMITTED FOR REVIEW AND APPROVAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |