Plan Review Details - Permit 23021260
Plan Review Stops For Permit 23021260
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-03-20 Cont ID  
Sent By cpuell Date 2023-03-20 Time 10:21 Rev Time 0.00
Received By cpuell Date 2023-03-20 Time 10:20 Sent To  
Notes
2023-03-20 10:21:22ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-08 Cont ID  
Sent By cthroop Date 2023-04-08 Time 08:05 Rev Time 0.00
Received By cthroop Date 2023-04-08 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-18 Cont ID  
Sent By cthroop Date 2023-03-18 Time 09:43 Rev Time 0.00
Received By cthroop Date 2023-03-18 Time 08:17 Sent To  
Notes
2023-03-18 09:52:351ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: VALUE HAS BEEN ADJUSTED TO $410,138 PER THE ICC
 BUILDING VALUATION DATA.
  
 1. CEILING INSULATION TYPE AND R VALUE ARE MISSING FROM
 THE ENERGY SUBMITTAL. PROVIDE A COMPLETE RESIDENTIAL
 ENERGY SUBMITTAL (RE)
 R401.2 COMPLIANCE.
 SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 2. WINDO0W SCHEDULE INDICATES SINGLE HUNG WINDOWS SHALL
 BE INSTALLED.
 PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVALS
 FOR THE PROPOSED SINGLE HUNG WINDOWS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. CEILING INSULATION ON PLAN SHEET 3 INDICATES R-20
 SPRAY FOAM INSULATION SHALL BE INSTALLED.
 PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-20 Cont ID  
Sent By jleahy Date 2023-03-20 Time 12:15 Rev Time 0.00
Received By jleahy Date 2023-03-20 Time 12:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 16:37 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 16:37 Sent To  
Notes
2023-04-05 16:38:50THE CONTRACTOR EMAILED A REQUEST FOR GAS TO BE UNDER A
 SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 09:25 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 09:12 Sent To  
Notes
2023-04-05 09:28:551ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23021260
 4/5/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS COPIED BELOW FROM
 THE 1ST REVIEW STILL EXIST. PLEASE COMPLY THE COMMENTS.
 THE CONTRACTOR HAS THE OPTION OF HAVING GAS UNDER A
 SEPARATE PERMIT. IF THIS OPTION IS CHOSEN PLEASE EMAIL
 AND I WILL CHANGE THE FAILED REVIEW TO N (NO REVIEW)
 WITH A NOTE REQUIRING A SEPARATE GS PERMIT. DEFERRING
 GAS TO A SEPARATE
  
 1) SHEET 3: THE PLAN SHOWS A GAS COOKTOP AND A GAS
 FIRED TANKLESS WATER HEATER. PLEASE PROVIDE A COMPLETE
 GAS RISER DRAWING IN COMPLIANCE WITH SEC. 107.3.5.3
 WPB. THE RISER SHALL SHOW PROVIDE THE FOLLOWING
 INFORMATION-
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 J) PIPE SIZING TABLES.
  
 2) SHEET 3: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW COOK TOP- SEC. G2407.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 07:40 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 07:29 Sent To  
Notes
2023-03-20 07:41:321ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23021260
 3/20/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: THE PLAN SHOWS A GAS COOKTOP AND A GAS
 FIRED TANKLESS WATER HEATER. PLEASE PROVIDE A COMPLETE
 GAS RISER DRAWING IN COMPLIANCE WITH SEC. 107.3.5.3
 WPB. THE RISER SHALL SHOW PROVIDE THE FOLLOWING
 INFORMATION-
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 J) PIPE SIZING TABLES.
  
 2) SHEET 3: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW COOK TOP- SEC. G2407.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 13:22 Rev Time 0.00
Received By medwards Date 2023-04-27 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-10 Cont ID  
Sent By aoliver Date 2023-04-10 Time 07:43 Rev Time 0.00
Received By aoliver Date 2023-04-04 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-27 Cont ID  
Sent By vbroglia Date 2023-03-27 Time 15:24 Rev Time 0.00
Received By vbroglia Date 2023-03-17 Time 10:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-05-12 Cont ID  
Sent By lmarchan Date 2023-05-12 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2023-04-10 Time 07:43 Sent To  
Notes
2023-05-04 08:29:49RECEIPT MU-2023-015975-0000 PAID - $2,280.84
2023-04-10 07:43:30EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-18 Cont ID  
Sent By cthroop Date 2023-03-18 Time 08:28 Rev Time 0.00
Received By cthroop Date 2023-03-18 Time 08:17 Sent To  
Notes
2023-03-18 08:29:09IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 13:20 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 13:20 Sent To  
Notes
2023-05-02 13:21:20PRIVISO: ADD ANOTHER BATH EXHAUST FAN IN THE MASTER
 SHOWER AREA. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By hmoser Date 2023-04-05 Time 12:46 Rev Time 0.00
Received By hmoser Date 2023-04-05 Time 12:26 Sent To  
Notes
2023-04-05 12:46:02PLAN DENIED
 REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 WEST PALM BEACH AMENDMENTS.
 ALL INFORMATION DRAWINGS SPECIFICATIONS AND
 ACCOMPANYING DATA
 SHALL BEAR THE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE
 FOR THE DESIGN.
  
 PROVIDE CFM ON ALL SUPPLY GRILS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-03-20 Cont ID  
Sent By medwards Date 2023-03-20 Time 17:25 Rev Time 0.00
Received By medwards Date 2023-03-20 Time 17:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 09:24 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-03-20 Cont ID  
Sent By ccole Date 2023-03-20 Time 07:28 Rev Time 0.00
Received By ccole Date 2023-03-20 Time 06:59 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-04-28 Cont ID  
Sent By dbattles Date 2023-04-28 Time 11:09 Rev Time 0.00
Received By dbattles Date 2023-04-28 Time 11:09 Sent To  
Notes
2023-04-28 11:09:53NTBO FOR INSPECTIONS.
 DOCUMENTS SENT TO FILENET.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-03-18 Cont ID  
Sent By cthroop Date 2023-03-18 Time 09:32 Rev Time 0.00
Received By cthroop Date 2023-03-18 Time 08:17 Sent To  
Notes
2023-03-18 09:33:15PROVISO ON PLAN SHEET 4: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 13:22 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-18 Cont ID  
Sent By cthroop Date 2023-03-18 Time 09:10 Rev Time 0.00
Received By cthroop Date 2023-03-18 Time 08:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-27 Cont ID  
Sent By VBroglia Date 2023-03-27 Time 15:22 Rev Time 0.00
Received By vbroglia Date 2023-03-27 Time 15:22 Sent To  
Notes
***NONE***