| 2023-07-12 16:50:33 | RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23021253 | | | 216 32ND ST | | | | | | 1- NEW GENERATOR CONCRETE PAD ENGINEERING: | | | A)THE EQUIVALENT WIND SHOWN ON TABLE 2.2 DOESN'T MEET | | | THE WIND SPEED REQUIRED FOR THIS LOCATION. THIS | | | GENERATOR IS LOCATED IN EXPOSURE D. REVISE AS REQUIRED. | | | SEC. R301.2.1.4 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | B) THE ENGINEER IS LIMITING THE USE OF THIS CONCRETE | | | PAD ENGINEERING TO A SPECIFIC LOCATION (ZIP CODE AND | | | COMPANY). ACCORDING TO THIS, THE CONCRETE PAD | | | ENGINEERING IS VOID BECAUSE THE LOCATION OF THIS | | | PROJECT DOESN'T MATCH THAT LIMITATION. PROVIDE | | | ENGINEERING FOR THIS SITE SPECIFIC LOCATION. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 2- DIGITAL SIGNATURE ON NEW GENERATOR CONCRETE PAD | | | ENGINEERING: | | | A)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | B)BOX LANGUAGE MUST BE IDENTICAL TO THE SAMPLES | | | PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALI | | | NG-ENGINEERING-DOCUMENTS/ AND REVISE AS REQUIRED. | | | | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | SEC. 61G15-23.004 F.A.C. PROCEDURES FOR DIGITALLY | | | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-30 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-30 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2023-06-30 10:24:46 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23021253 | | | 216 32ND ST | | | | | | 1- NEW GENERATOR CONCRETE PAD ENGINEERING: | | | A)THE EQUIVALENT WIND SHOWN ON TABLE 2.2 DOESN'T MEET | | | THE WIND SPEED REQUIRED FOR THIS LOCATION. THIS | | | GENERATOR IS LOCATED IN EXPOSURE D. REVISE AS REQUIRED. | | | SEC. R301.2.1.4 FBC-RESIDENTIAL. | | | | | | B) THE ENGINEER IS LIMITING THE USE OF THIS CONCRETE | | | PAD ENGINEERING TO A SPECIFIC LOCATION (ZIP CODE AND | | | COMPANY). ACCORDING TO THIS, THE CONCRETE PAD | | | ENGINEERING IS VOID BECAUSE THE LOCATION OF THIS | | | PROJECT DOESN'T MATCH THAT LIMITATION. PROVIDE | | | ENGINEERING FOR THIS SITE SPECIFIC LOCATION. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 2- DIGITAL SIGNATURE ON NEW GENERATOR CONCRETE PAD | | | ENGINEERING: | | | A)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | B)BOX LANGUAGE MUST BE IDENTICAL TO THE SAMPLES | | | PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALI | | | NG-ENGINEERING-DOCUMENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | SEC. 61G15-23.004 F.A.C. PROCEDURES FOR DIGITALLY | | | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-22 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-22 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-03-22 17:27:28 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23021253 | | | 216 32ND ST | | | | | | 1- GENERATOR CONCRETE PAD ENGINEERING: | | | A)THE WEIGHT AND DIMENSIONS OF THE GENERATOR SPECIFIED | | | ON THE DESIGN CALCULATIONS DON'T MATCH THE WEIGHT AND | | | DIMENSIONS OF THE GENERATOR SPECS SUBMITTED. ENGINEER | | | OF RECORD TO REVISE DESIGN SPECIFICATIONS AND | | | CALCULATIONS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS | | | AND SEC. R301.1 FBC-RESIDENTIAL. | | | | | | B)DRAWING SUBMITTED DOESN'T HAVE THE SEAL/SIGNATURE OF | | | THE ENGINEER OF RECORD. PLANS/DOCUMENTS NEED TO HAVE | | | THE ORIGINAL SEAL/SIGNATURE OF THE ENGINEER OF RECORD | | | AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471 | | | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | | RECORDS. | | | NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT | | | PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-03-10 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-03-10 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-07-18 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-07-18 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-06-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-12 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-12 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2023-06-12 11:20:54 | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 23021253 | | | 6/12/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. THE CORRECTED RISER | | | DRAWING WAS NOT UPLOADED FOR REVEW. THE 1ST REVIEW | | | COMMENTS BELOW STILL EXIST. | | | | | | 1) GAS RISER: PROVIDE A COMPLETE RISER DRAWING THAT | | | INCLUDES THE NEW GAS PIPING TO THE GENERATOR AND | | | EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE- | | | SECTION G2412.3 & G2412.4 FBC RES. WPB BUILDING DEPT. | | | RECORDS INDICATE PREVIOUS GAS PIPING PERMIT FOR WATER | | | HEATER AND DRYER- 07020505. PLEASE REVISE THE RISER | | | DRAWING PER ITEMS A- C BELOW. | | | | | | A) SHOW THE TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL | | | APPLIANCE BTU LOADS. | | | | | | B) SHOW THE SIZE OF THE MAIN SUPPLY PIPE AT THE METER | | | AND THE SIZE OF THE SUPPLY PIPE AT THE GENERATOR. | | | | | | C) AT THE MAIN SUPPLY PIPE PLEASE SHOW BOTH THE NEW | | | BRANCH PIPING POINT OF CONNECTION AND THE EXISTING | | | BRANCH PIPING POINT OF CONNECTION. IDENTIFY THE TYPE | | | AND SIZE OF THE EXISTING BRANCH PIPING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2023-03-16 16:01:19 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23021253 | | | 3/16/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: PROVIDE A COMPLETE RISER DRAWING THAT | | | INCLUDES THE NEW GAS PIPING TO THE GENERATOR AND | | | EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE- | | | SECTION G2412.3 & G2412.4 FBC RES. WPB BUILDING DEPT. | | | RECORDS INDICATE PREVIOUS GAS PIPING PERMIT FOR WATER | | | HEATER AND DRYER- 07020505. PLEASE REVISE THE RISER | | | DRAWING PER ITEMS A- C BELOW. | | | | | | A) SHOW THE TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL | | | APPLIANCE BTU LOADS. | | | | | | B) SHOW THE SIZE OF THE MAIN SUPPLY PIPE AT THE METER | | | AND THE SIZE OF THE SUPPLY PIPE AT THE GENERATOR. | | | | | | C) AT THE MAIN SUPPLY PIPE PLEASE SHOW BOTH THE NEW | | | BRANCH PIPING POINT OF CONNECTION AND THE EXISTING | | | BRANCH PIPING POINT OF CONNECTION. IDENTIFY THE TYPE | | | AND SIZE OF THE EXISTING BRANCH PIPING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-11 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-30 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-07 |
Time |
09:19 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-22 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-02-24 |
Time |
09:55 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-07-18 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-07-18 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2023-06-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-14 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-12 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-07-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-07-12 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-07-12 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2023-07-12 16:51:04 | SIGNATURE REVIEW: | | | | | | 1- DIGITAL SIGNATURE ON NEW GENERATOR CONCRETE PAD | | | ENGINEERING: | | | A)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | B)BOX LANGUAGE MUST BE IDENTICAL TO THE SAMPLES | | | PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALI | | | NG-ENGINEERING-DOCUMENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | SEC. 61G15-23.004 F.A.C. PROCEDURES FOR DIGITALLY | | | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-30 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-30 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2023-06-30 10:26:28 | SIGNATURE REVIEW: | | | | | | 1- DIGITAL SIGNATURE ON NEW GENERATOR CONCRETE PAD | | | ENGINEERING: | | | A)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | B)BOX LANGUAGE MUST BE IDENTICAL TO THE SAMPLES | | | PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALI | | | NG-ENGINEERING-DOCUMENTS/ AND REVISE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | SEC. 61G15-23.004 F.A.C. PROCEDURES FOR DIGITALLY | | | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-22 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-22 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2023-03-22 17:30:01 | SIGNATURE REVIEW: | | | | | | 1-GENERATOR CONCRETE PAD ENGINEERING: DRAWING SUBMITTED | | | DOESN'T HAVE THE SEAL/SIGNATURE OF THE ENGINEER OF | | | RECORD. PLANS/DOCUMENTS NEED TO HAVE THE ORIGINAL | | | SEAL/SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY | | | SEC. 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN | | | SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT | | | PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-06-14 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-06-14 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-06-14 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-03-07 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-03-07 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|