| Plan Review Stops For Permit 23021237 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-28 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-28 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2023-02-28 11:24:58 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-07 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-07 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-16 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-16 |
Time |
05:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-22 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-21 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2023-03-22 13:31:02 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: STRUCTURES ARE LOCATED SPECIAL FLOOD HAZARD | | | AREA'S (SFHA). SEE COMMENTS UNDER NFIP REVIEW. FEMA | | | ELEVATION CERTIFICATE REQUIRED. | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDY LINE SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | | | | 2. SITE PLAN SUBMITTED FOR REVIEW IS FOR 5300 ESSEX CT. | | | PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY | | | LOCATION OF WORK. REMOVE ANY REFERENCE TO EXISTING | | | STRUCTURES. | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE | | | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | | ACCURATE AND INCLUDED BOUNDRY LINE SURVEY. | | | | | | 3. REMOVED | | | | | | 4. THE PRODUCT APPROVAL FOR THE OVERHEAD DOOR (OHD) HAS | | | EXPIRED. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVALS | | | FOR THE PROPOSED OHD. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 5.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE | | | SPECIFICATION SHEETS OF A LIQUID APPLIED MEMBRANE. | | | FBC R 703.4, FBC B 1405.4 | | | | | | 6. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM | | | INSULATION. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. PROVIDE THE FINISHED FLOOR ELEVATION FOR EACH ROOM | | | ON THE FLOOR PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 8. PROVIDE THE STAIR HANDRAIL DETAIL FOR THE GARGAE | | | STAIRS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 9. PROVIDE A ROOF TO WALL CONNECTOR SCHEDULE. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 10. PROVIDE A LINTEL SCHEDULE. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 11.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVALS FOR THE PROPOSED LINTELS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 12.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. | | | R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | | CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO | | | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES | | | (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 | | | SQUARE FEET (2.8 M2). | | | | | | 13.PROVIDE THE DESIGN PRESSURES FOR NEW ROOFING PER | | | FIGURE R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES | | | R301.2.1.1WIND DESIGN REQUIRED. | | | | | | 14.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE | | | ENHANCED CALCULATED DESIGN PRESSURES OF ZONES 2 AND 3. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-05-02 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-05-02 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2023-05-02 14:39:28 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW | | | | | | 1. GENERATOR AND SWIMMING POOL, EACH REQUIRES A | | | SEPARATE PERMIT APPLICATION. | | | | | | END OF COMMENTS | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-03-15 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-03-15 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2023-03-15 11:30:00 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE IN ACCORDANCE | | | WITH NE 220. | | | | | | 2. PROVIDE AN ONE-LINE DIAGRAM SHOWING INFORMATION OF | | | SERVICE EQUIPMENT (SERVICE CONDUCTORS, SERVICE | | | OVERCURRENT PROTECTION, GROUNDED CONDUCTOR, EQUIPMENT | | | GROUNDING CONDUCTORS (EGC), MAIN PANEL AND SUBPANELS). | | | NEC 230, 250 | | | | | | 3. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | 4. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT | | | SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN | | | ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC | | | POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER | | | NEC 210.11(C)(4) | | | | | | 5. SWIMMING POOL REQUIRES A SEPARATE PERMI NUMBER. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
| Sent By |
parking |
Date |
2023-05-19 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-05-19 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-08 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-08 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2023-06-08 10:06:44 | 3RD GAS REVIEW - AMENDED 6-20-23 CHANGED COMMENT #1 TO | | | DONE | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-24 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-24 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2023-04-24 12:22:52 | 2ND GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.3.5.1.5 - A DETAIL FOR THE WATER | | | HEATER VENTING IS NOT SHOWN. | | | | | | 2. 2017 WPB AMENDS 107.3.5.1.5 - A DETAIL FOR THE DRYER | | | MAKEUP AIR IS NOT SHOWN | | | | | | 3. 2017 WPB AMENDS 107.3.5.1.5 - DETAIL FOR THE | | | FIREPLACE VENTING NOT SHOWN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-28 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-28 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2023-03-15 11:27:46 | | | | | | 2023-02-28 14:18:36 | 1ST GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS | | | RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING | | | APPLICABLE ITEMS. | | | A) AN ISOMETRIC THAT INCLUDES - PIPE MATERIAL, LOCATION | | | OF SHUT OFFS, PIPING LENGTHS, PIPE PRESSURES, LOCATION | | | OF REGULATORS, BTU LOADS FROM EACH APPLIANCE, | | | INDIVIDUAL SYSTEM SIZING WITH REFERENCES TO SIZING | | | TABLES FROM THE CODE. | | | B) A FLOOR PLAN THAT INCLUDES APPLIANCE LOCATIONS AND | | | COMBUSTION AIR/MAKE UP AIR SIZING FOR EACH APPLIANCE | | | WITHIN THE ROOM THAT CONTAINS IT. | | | C) VENTING DETAILS FOR APPLIANCES THAT VENT TO THE | | | OUTDOORS, INCLUDE DISTANCES FOR SEPARATION FROM THE | | | VENT TERMINATIONS TO OPERABLE WINDOWS, AIR INTAKES, | | | ETC. | | | D) CHIMNEY DETAILS FOR THE FIREPLACES | | | E) SPECS FOR THE APPLIANCES | | | F) SPECIAL ATTENTION TO THE GENERATOR ROOM AND THE | | | COMBUSTION AIR INTAKES, EXHUASTS, SEPARATION EXHAUST | | | AND INTAKES WITH OTHER SYSTEMS. | | | I) SPECIAL NOTE FOR THE GENERATOR EXHAUST - 2020 FRC | | | R303.5.1 - RESIDENTIAL GAS GENERATOR EXHAUST | | | TERMINATION MUST BE 10 FEET FROM ANY OPENING INTO THE | | | STRUCTURE AND FROM ANY LOT LINE/POSSIBLE OPENING INTO | | | ANY OTHER STRUCTURE. | | | G) DETAILS FOR ANY SLEEVING REQUIRED FOR PENETRATIONS | | | INTO THE STRUCTURE OR UNDER THE STRUCTURE. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-07 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-06-07 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-19 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-05-19 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-04-21 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-22 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-27 |
Time |
12:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-07-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-07-20 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-07-10 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2023-07-19 13:39:25 | RECEIPT MU-2023-031269 - $12,378.21 PAID | | 2023-07-10 08:55:34 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-22 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-21 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2023-03-22 07:29:13 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-06-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-22 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-22 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-02 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-02 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2023-05-02 11:14:32 | 2ND REVIEW FMC | | | PERMIT: 23021237 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE | | | NOT SUBMITTED IN THIS REVIEW CYCLE. PROVIDE THE | | | CORRECTED MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | | | | 2) PROVIDE THE CALCULATIONS FOR THE INTAKE LOUVERS | | | SIZING AND THE EXHAUST FOR THE GENERATOR ROOM. | | | FBC107.3.5 | | | | | | 3) THE ENGINEER OF RECORD WILL NEED TO DIGITALLY SIGN | | | THE SUBMITTED MECHANICAL DRAWINGS. FS 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-28 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-28 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2023-02-28 11:27:22 | 1ST REVIEW FMC | | | PERMIT: 23021237 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS DESIGNED FOR 4 SYSTEMS, EACH BEING A | | | NATURAL GAS FURNACE, DOES NOT MATCH THE MECHANICAL | | | DRAWINGS THAT ARE DESIGNED WITH 22 AHU???S AND 12 | | | HP???S. THE MECHANICAL SIZING CALCULATIONS FBC 107.3.5 | | | | | | 2) SHEET M201-A: THE DRYERS APPEAR TO SHARE ONE SINGLE | | | DRYER DUCT. PROVIDE A DETAIL OF THIS DESIGN SHOWING THE | | | DUCT SIZES FOR THE SINGLE DRYERS AND ALSO THE DUCT | | | AFTER THE 2 ARE JOINED. FRC M1502 | | | | | | 3) SHEET M201B: PROVIDE THE VENTILATION DETAILS FOR THE | | | GENERATOR ROOM. WHERE IS THE INTAKE FOR THIS GENERATOR? | | | FBC 107.3.5 | | | | | | 4) SHEET M202: EXPLAIN THE DAMPERS IN THE EXHAUST DUCT | | | SYSTEM. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-07 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-07 |
Time |
06:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2023-05-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-16 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-16 |
Time |
05:38 |
Sent To |
|
|
| Notes |
| 2023-05-16 16:23:49 | PEER REVIEW COMPLETED RMCP | | 2023-05-16 14:36:40 | 2ND NFIP REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | FEMA DESK REFERENCE P 758 | | | FBC R322 FLOOD-RESISTANT CONSTRUCTION | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR THIS SITE | | | ARE AE 6 AND AE 7 WITH A BASE FLOOD ELEVATIONS (BFE) OF | | | 6'0" AND 7'0" NAVD. | | | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. | | | 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. | | | THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE | | | 9'0" NAVD. | | | | | | NOTICE: 1ST REVIEW OF THE CONSTRUCTION DRAWING EC: | | | | | | 1. LINES A8B) & C) SHALL BE N/A. (PER EC INSTRUCTIONS) | | | | | | 2. LINES 9AB) & C) SHALL BE N/A. (PER EC INSTRUCTIONS) | | | | | | 3. LINE C2E) STATES MACHINERY SERVICING BUILDING | | | (GENERATOR PER COMMENTS) WILL BE AT 10.5'. PLAN PAGE | | | A201B SHOWS MECH. ROOM (GENERATOR) IS AT 10.0'. PLEASE | | | CLARIFY? | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | | | | | | 2023-05-16 10:20:16 | PEER REVIEW REQUESTED 5/16/23. CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-22 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-21 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2023-03-22 12:14:01 | 1ST NFIP REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | FEMA DESK REFERENCE P 758 | | | FBC R322 FLOOD-RESISTANT CONSTRUCTION | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR THIS SITE | | | ARE AE 6 AND AE 7 WITH A BASE FLOOD ELEVATIONS (BFE) OF | | | 6'0" AND 7'0" NAVD. | | | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. | | | 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. | | | THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE | | | 9'0" NAVD. | | | | | | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 | | | SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT | | | CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE | | | II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL | | | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH | | | SHALL READ AS FOLLOWS: | | | | | | SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE, RESIDENTIAL. | | | R322.2.1 ELEVATION REQUIREMENTS. | | | 1. | | | 1.BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT | | | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST | | | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION | | | PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER | | | IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17). | | | | | | 2. PROVIDE THE FOLLOWING (3) ELEVATION CERTIFICATES AS | | | REQUIRED. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-08 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-08 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-24 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-24 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2023-04-24 11:19:53 | 2ND PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | | | | 1. IF THERE ARE TWO METERS, ONE FOR IRRIGATION AND ONE | | | FOR DOMESTIC WATER, EACH WILL NEED ITS OWN BACKFLOW AND | | | ASSOCIATED PERMIT. ONLY ONE BACKFLOW PERMIT HAS BEEN | | | APPLIED FOR. | | | | | | 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES TWO | | | SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND ONE | | | FOR THE POTABLE WATER. EACH WILL REQUIRE ITS OWN | | | BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT | | | AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT | | | HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED | | | PERMIT APPLICATION TO [email protected]. AFTER | | | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL | | | OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS | | | COMMENT. | | | | | | 2. NOT ADDRESSED -- | | | | | | 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL REQUIRE | | | A SEPARATE PERMIT | | | | | | 3. DONE - RISER SHOWN - SEE BELOW FOR INDIVIDUAL | | | COMMENTS NOT ADDRESSED -- | | | | | | A) DONE | | | | | | B) DONE | | | | | | C) DONE | | | | | | D) DONE | | | | | | E) DONE | | | | | | F) PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3 | | | (12) - THE FLOOR PLAN SHOWS A 2" SAN UP TO SECOND FLOOR | | | WHICH GOES TO THE WATER CLOSET. THE ISOMETRIC SHOWS A | | | 3". FIX THE FLOOR PLAN TO SHOW THE REQUIRED 3" TO THE | | | WATER CLOSET. | | | | | | G) WYE IS STILL FACING BACKWARDS -- | | | PAGE 201A PRIMARY BATH - 2017 WPB AMEND 107.3.5.3 (12) | | | - IN THE SAME AREA IT APPEARS ONE OF THE WYES IS FACING | | | BACKWARDS. | | | | | | H) PAGE 201A PRIMARY BATH - THE BATHTUB IS MISSING FROM | | | THE ISOMETRIC AND THE FLOOR PLAN. | | | | | | I) NEW COMMENT - THE ISOMETRIC DOES NOT MATCH THE FLOOR | | | PLAN. THE TWO BATHROOMS NEAREST THE IT ROOM ARE NOT | | | SHOWN THE SAME ON THE FLOOR PLAN AS THEY ARE ON THE | | | ISOMETRIC. THE SHOWER AND WATER CLOSETS IN BOTH | | | BATHROOMS ARE SWITCHED AROUND. | | | | | | 4. IT IS TYPICAL AND MOST HELPFUL IF YOU SHOW A SECOND | | | FLOOR PLUMBING PLAN WITH THE SANITARY TO THE SECOND | | | FLOOR PLUMBING FIXTURES IMPOSED UNDER THE 2ND FLOOR UP | | | TO THE CORRESPONDING 2ND FLOOR FIXTURES, MUCH LIKE THE | | | 1ST FLOOR IS SHOWN. | | | 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND-FLOOR | | | PLUMBING PLAN APPEARS TO BE MISSING. | | | | | | 5. DONE | | | | | | 6. 2017 WPB AMENDS 107.2.1 - THE REFERENCED PAGES IN | | | THE KEY NOTES WITHIN THE PLAN ARE MISSING - A727, A718, | | | A731, A734, ETC..? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-28 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-28 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2023-02-28 14:03:14 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | NOTE: PAGE SP100-SITE PLAN - THIS LAYOUT DOES NOT MATCH | | | THE REST OF THE PAGES. | | | | | | 1. 2017 WPB AMEND - 105.1/107.3 -- PAGE C4.0 INDICATES | | | TWO SEPARATE METER CONNECTIONS. ONE FOR IRRIGATION AND | | | ONE FOR THE POTABLE WATER. EACH WILL REQUIRED ITS OWN | | | BACKFLOW PERMIT. THESE ARE REQUIRED TO BE APPLIED FOR | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT | | | AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT | | | HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED | | | PERMIT APPLICATION TO [email protected]. AFTER | | | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL | | | OR NOTE IN THE RESPONSE LETTER AND I WILL COMPLY THIS | | | COMMENT. | | | | | | 2. 2017 WPB AMEND - 105.1/107.3 -- IRRIGATION WILL | | | REQUIRE A SEPARATE PERMIT | | | | | | 3. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE ADD A RISER | | | IN ISOMETRIC FORM FOR PLUMBING REVIEW. A RISER IS | | | ALWAYS REQUIRED. A PRELIMINARY REVIEW OF THE SANITARY | | | FOLLOWS BUT WILL NEED TO HAVE THE ISOMETRIC FOR FULL | | | REVIEW: | | | A) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.1 - THE | | | KITCHENETTE CANNOT CONNECT INTO THE SHOWER FIXTURE | | | DRAIN. IF A WET VENT SYSTEM IS BEING USED IN THE | | | BATHROOM AREA, ANY OTHER FIXTURES WOULD NEED TO | | | DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. | | | B) PAGE P200B - POOL BATH AREA - 2020 FRC P3108.2.1 - | | | IT APPEARS, BUT IS UNCLEAR THAT THE WATER CLOSET AND | | | SHOWER ARE BOTH UPSTREAM OF THE VENTED FIXTURE'S | | | (LAVATORY) CONNECTION. ONLY ONE FIXTURE WOULD BE | | | ALLOWED UPSTREAM OF THE VENTED FIXTURE THAT CREATES THE | | | WET VENT FOR THAT BATHROOM GROUP. | | | C) PAGE P200B - POOL BATH AREA - 2020 FPC P3104.4 - THE | | | PRIVATE WATER CLOSET HAS A DRYVENT THAT IS HORIZONTAL | | | BELOW THE FLOOD RIM OF THE FIXTURE. A VENT SHALL RISE | | | VERTICALLY TO 6" ABOVE THE FLOOD RIM OF THE FIXURE(S) | | | SERVED. | | | D) PAGE P200A - STAFF LOUNGE AREA - THE WATER CLOSET IS | | | NOT VENTED TO CODE. | | | E) PAGE P200A - KITCHEN AREA - 2020 FRC P3101.2.1 - IT | | | IS UNCLEAR IF THE KITCHEN TRAPS ARE VENTED/STUDOR | | | VENTED? | | | THIS IS ALL I CAN SEE FOR NOW. PLEASE SUBMIT THE SECOND | | | FLOOR PLAN AS WELL AS THE COMPLETE ISOMETRIC FOR THE | | | SANITARY FOR REVIEW. INCLUDE THE CONTINUATION OF THE | | | VENTING IN THE SANITARY ISOMETRIC | | | F) PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IT | | | APPEARS THE UPSTAIRS WATER CLOSET AND BATHTUB ARE | | | MISSING FROM THE DRAWING. | | | G)PAGE 201A - 2017 WPB AMEND 107.3.5.3 (12) - IN THE | | | SAME AREA IT APPEARS ONE OF THE WYES IS FACING | | | BACKWARDS. | | | | | | 4. 2017 WPB AMEND 107.3.5.3 (12) - THE SECOND FLOOR | | | PLUMBING PLAN APPEARS TO BE MISSING. | | | | | | 5. PAGE 701 - 2017 WPB AMEND 107.3.5.3 (12) - THERE IS | | | A NOTE ON THE WATER RISR-EAST THAT STATES "REFER TO | | | P702" AND THERE IS NO PAGE 702. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2023-03-22 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2023-03-22 |
Time |
16:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-02-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2023-02-28 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-02-28 07:55:18 | FS553.791, APPLICATION INDICATES THAT THIS PROJECT WILL | | | UTILIZE A PRIVATE PROVIDER FOR INSPECTIONS. UPLOAD | | | NOTICE TO BUILDING OFFICIAL, LICENSES, RESUMES, | | | CERTIFICATE OF INSURANCE. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2023-03-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-22 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-21 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2023-03-22 12:12:09 | PROVISO ON PLAN PAGE A203A: A SEPERATE ROOFING PERMIT | | | IS REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-07 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-07 |
Time |
06:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-05-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-16 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-16 |
Time |
05:39 |
Sent To |
|
|
| Notes |
| 2023-05-02 11:15:51 | THE EOR FOR THE MECHANICAL DRAWINGS SUBMITTED THIS | | | CYCLE WILL NEED TO DIGITALLY SIGN EACH DRAWING. ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-28 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-28 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2023-02-28 11:27:54 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-07-05 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-07-05 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2023-06-27 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-06-27 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-06-27 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2023-06-27 10:30:00 | LANDSCAPE PERMIT STILL REQUIRED TO MOVE THIS PERMIT | | | FORWARD |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-09 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-09 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2023-05-09 13:30:49 | FAILED FOR THE FOLLOWING REASONS: | | | | | | | | | 1. LANDSCAPE PERMIT IS REQUIRED, YOU WILL NEED TO APPLY | | | FOR A PERMIT TO MOVE THE BUILDING PERMIT FORWARD | | | | | | 2. SEPERATE PERMIT IS REQUIRED FOR POOLS, FENCE/WALLS, | | | DRIVEWAY, AND MECHANICAL EQUIPMENT. | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | PLANNER | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
AJVann |
Date |
2023-03-17 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2023-03-17 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2023-03-17 14:23:07 | 3/17/23- FAILED | | | PLEASE ADDRESS THE FOLLOWING COMMENTS IN YOUR | | | RESUBMITAL: | | | | | | 1.SECTION 94-72 A.3. STATES THAT THE MAXIMUM BUILDING | | | HEIGHT:30 FEET. PLEASE REVISED THE PLANS ACCORDINGLY | | | 2. DOES THE POOL HOUSE HAVE A FULL KITCHEN | | | 3. THE WALL ALONG FLAGLER DRIVE CAN GO TO A MAXIMUM | | | HEIGHT OF 6 FEET | | | 4. SEPERATE PERMIT REQUIRED FOR LANDSCAING, SITE WALLS | | | AND FENCES, DRIVEWAYS, SWIMMING POOLS AND OTHER | | | HARDSCAPE. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] | | | |
|
|