Plan Review Details - Permit 23021112
Plan Review Stops For Permit 23021112
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By cpuell Date 2023-04-20 Time 08:33 Rev Time 0.00
Received By cpuell Date 2023-04-20 Time 08:33 Sent To  
Notes
2023-04-20 08:34:07WORK TO BE DONE ON DUPLEX 742 53RD ST AND 744 53RD ST
 UPDATED PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-26 Cont ID  
Sent By lbond Date 2023-05-26 Time 09:44 Rev Time 0.00
Received By lbond Date 2023-05-26 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 11:41 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 11:41 Sent To  
Notes
2023-04-17 11:44:39PROVIDE FPC PRODUCT APPROVAL FOR NEW EXTERIOR WINDOWS
 AND DOORS.
 PROVIDE MORE ACCURATE KITCHEN LAYOUTS WITH DIMENSIONS
 INCLUDING ACCURATE APPLIANCES LOCATION, PLUMBING AND
 ELECTRICAL
 SAME FOR BATHROOMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By lbond Date 2023-03-10 Time 10:32 Rev Time 0.00
Received By lbond Date 2023-03-10 Time 10:32 Sent To  
Notes
2023-03-10 10:45:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 2302112
  
 REVIEWED: MARCH 10, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 AS PER SECTION 107.2.1
  
 1) CLEARLY DEFINE SCOPE OF WORK FOR DUPLEX UNITS AND
 SHOW FULL KITCHEN AND BATHROOM LAYOUTS OF THE EXISITING
 FOR BOTH UNITS.
  
 2) PROVIDE PLANS AND DETAILS OF THE PROPOSED SCOPE OF
 WORK. DEFINED IN YOUR APPLICATION AS "REMODEL" "ETC."
  
 3) PLANS SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE REMODEL.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-14 Cont ID  
Sent By cmontell Date 2023-07-14 Time 13:05 Rev Time 0.00
Received By cmontell Date 2023-07-14 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 08:53 Rev Time 0.00
Received By vbroglia Date 2023-05-25 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-24 Cont ID  
Sent By vbroglia Date 2023-04-24 Time 15:19 Rev Time 0.00
Received By vbroglia Date 2023-04-14 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-03-16 Time   Rev Time 0.00
Received By amcgrego Date 2023-03-09 Time 10:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2023-07-14 Cont ID  
Sent By cmontell Date 2023-07-14 Time 13:05 Rev Time 0.00
Received By cmontell Date 2023-07-14 Time 13:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-06-08 Cont ID  
Sent By cmontell Date 2023-06-08 Time 13:47 Rev Time 0.00
Received By cmontell Date 2023-06-08 Time 13:47 Sent To  
Notes
2023-06-08 13:50:10PER FBC SEC 107
 NEED DISCRIPTION OF MECHANICAL WORK BEING DONE IF ANY.
 CHRIS MONTELLO
 561-805-6673

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By medwards Date 2023-04-19 Time 07:56 Rev Time 0.00
Received By medwards Date 2023-04-19 Time 07:56 Sent To  
Notes
2023-04-19 08:01:38THE APPLICATION STATES IT IS FOR REMODEL INCLUDING HOT
 WATER HEATER REPLACEMENT, CENTRAL AIR, PLUMBING,
 DOORS,ECT.
 PROVIDE A COMPLETE MECHANICAL DESIGN FOR THESE PROJECTS
 INCLUDING MECHANICAL EQUIPMENT SIZING CALCULATIONS AND
 A MECHANICAL DRAWING. FBC 107.3.5
 THE DRAWING SUBMITTED HAS 742 53RD ST AND 744 53RD ST.
 IS THIS A CHANGE FROM A SINGLE FAMILY RESIDENCE TO A
 DUPLEX?
 ADDITONAL COMMENT: 4/25/2023- WHAT IS THE USE OF THIS
 STRUCTURE? ARE THESE 2 SPACES TO BE RENTAL UNITS?
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By medwards Date 2023-03-10 Time 07:51 Rev Time 0.00
Received By medwards Date 2023-03-10 Time 07:51 Sent To  
Notes
2023-03-10 07:51:421ST REVIEW FMC
 PERMIT: 23021112
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRAWING SUBMITTED INDICATES THIS TO BE A DUPLEX.
 WE HAVE NO RECORDS OF A PERMITTED MECHANICAL SYSTEM
 BEING INSTALLED IN THIS DUPLEX. PROVIDE A COMPLETE
 MECHANICAL DESIGN FOR THE INSTALLATION OF THE
 MECHANICAL SYSTEMS FOR THIS DUPLEX. INCLUDE THE ENERGY
 CALCULATIONS, MECHANICAL EQUIPMENT SIZING CALCULATIONS,
 MECHANICAL EQUIPMENT SCHEDULE AND A MECHANICAL DRAWING.
 FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2023-06-30 Cont ID  
Sent By ccole Date 2023-06-30 Time 11:22 Rev Time 0.00
Received By ccole Date 2023-06-30 Time 11:17 Sent To  
Notes
2023-06-30 11:37:582ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021112
 6/30/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE A WRITTEN
 SCOPE OF WORK FOR PLUMBING ON THE PLAN WITH
 CORRESPONDING DETAILS. THE APPLICANT HAS RESPONDED TO
 THE COMMENT WITH A LETTER RESPONSE WHICH HAS CLARIFIED
 THE SCOPE OF WORK BUT THAT INFORMATION WAS ASKED TO BE
 PLACED ON THE PLAN- SEC. 107.2.1 WPB.
 PLEASE SHOW ON THE PLAN THE NEW LOCATIONS OF THE
 ELECTRIC WATER HEATERS AND IDENTIFY ALL FIXTURES TO BE
 REPLACED. IF NECESSARY PLEASE PROVIDE A SEPARATE
 PLUMBING AND ELECTRICAL PLAN. THE ELECTRICAL DRAWING
 SHALL SHOW THE NEW WIRING AND CIRCUITRY FOR THE
 RELOCATED WATER HEATERS. PLEASE INCLUDE THE MAKES AND
 MODELS OF THE WATER HEATERS AND NOTE DRAIN PANS AND
 DRAIN LINES SHALL BE PROVIDED IN ACCORDANCE WITH
 SEC.P2801.6- P2801.6.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-05-26 Cont ID  
Sent By ccole Date 2023-05-26 Time 08:49 Rev Time 0.00
Received By ccole Date 2023-05-26 Time 08:27 Sent To  
Notes
2023-05-26 08:49:551ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021112
 5/25/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE TWO NEW FLOOR PLANS 001 & 002 DO NOT MATCH. ONE
 DRAWING SHOWS THE KITCHENS AND BATHS AT THE FRONT SIDE
 OF THE AND THE OTHER SHOWS THE KITCHENS AND BATHS AT
 THE REAR. PLEASE CHOOSE ONE PLAN OR THE OTHER AND
 PROVIDE A WRITTEN SCOPE OF WORK FOR PLUMBING ON THE
 PLAN WITH CORRESPONDING DETAILS. PROVIDE A SEPARATE
 PLUMBING PLAN IF NECESSARY. THE PREVIOUS RESPONSE TO
 COMMENTS INDICATED WATER HEATER REPLACEMENTS ONLY. IF
 THAT IS THE ENTIRE SCOPE THEN INDICATE THAT ON THE
 PLANS AND PROVIDE EQUIPMENT SCHEDULES FOR EACH WATER
 HEATER INDICATING THE MAKES AND MODELS AND GALLON
 CAPACITIES- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By ccole Date 2023-04-17 Time 08:15 Rev Time 0.00
Received By ccole Date 2023-04-17 Time 07:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By ccole Date 2023-03-10 Time 09:39 Rev Time 0.00
Received By ccole Date 2023-03-10 Time 09:14 Sent To  
Notes
2023-03-10 09:40:291ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23021112
 3/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVISE THE PROPOSED PLAN TO SHOW THE SCOPE OF
 WORK FOR PLUMBING WITH NOTES AND DETAILS- SEC. 107.2.1
 WPB. PLEASE NOTE A SANITARY RISER IS REQUIRED FOR NEW
 DRAIN AND VENT PIPING INSTALLATION- SEC. 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-26 Cont ID  
Sent By lbond Date 2023-05-26 Time 09:43 Rev Time 0.00
Received By lbond Date 2023-05-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 11:53 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-16 Cont ID  
Sent By ccole Date 2023-03-16 Time 09:06 Rev Time 0.00
Received By ccole Date 2023-03-16 Time 09:06 Sent To  
Notes
2023-03-16 09:42:361ST SIGNATURE REVIEW
 PERMIT- 23021112
 3/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN SHALL BE ON THE PLANS- SEC.
 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 08:53 Rev Time 0.00
Received By vbroglia Date 2023-06-14 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-24 Cont ID  
Sent By vbroglia Date 2023-04-24 Time 15:19 Rev Time 0.00
Received By vbroglia Date 2023-04-24 Time 15:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By vbroglia Date 2023-03-14 Time 12:01 Rev Time 0.00
Received By vbroglia Date 2023-03-14 Time 12:01 Sent To  
Notes
2023-03-14 12:17:243/14/2023 FAILED
  
 PER STAFF'S FINDINGS THERE ARE NO PERMITS OR PROPERTY
 RECORDS OF THIS BEING CONVERTED INTO TWO LEGAL UNITS,
  
 CURRENT ZONING ONLY PERMITS ONE SINGLE FAMILY HOME,
 PLEASE CONVERT BACK OR SHOW PROOF OF PERMITS THAT
 ALLOWED TWO UNITS ON THE PROPERTY.
  
 PLEASE SHOW AN EXSISTING AND PROPOSED FLOOR PLAN
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  