Plan Review Details - Permit 23021107
Plan Review Stops For Permit 23021107
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 11:23 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 11:23 Sent To  
Notes
2023-06-14 11:26:29RECIEVED PRELIMINARY LETTER, PARCELS TO BE COMBINED
 UNDER 74434322170001203 WITH THE ADDRESS OF 400 N
 FLAGLER DR 1203 UNDER PERMIT 23021107

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2023-05-30 Cont ID  
Sent By cpuell Date 2023-05-30 Time 09:40 Rev Time 0.00
Received By cpuell Date 2023-05-30 Time 09:40 Sent To  
Notes
2023-05-30 09:40:21PRELIMINARY LETTER NOT RECIEVED, SPOKE TO CONTRACTOR
 ABOUT WHAT WAS REQUIRED, WILL SPEAK TO THE OWNER.
 PLEASE CONTACT [email protected] OR CALL
 561-805-6659 ONLY PRELIMINARY LETTER IS OBTAINED FROM
 THE PROPERTY APPRIAISER.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By cpuell Date 2023-05-02 Time 16:43 Rev Time 0.00
Received By cpuell Date 2023-05-02 Time 16:43 Sent To  
Notes
2023-05-02 16:44:02I SEE THAT THE UNITY OF DECLARARATION WAS UPLOADED,
 HOWEVER THIS IS NOT A UNITY OF TITLE, I ALSO SAW THE
 APPLICATION TO THE COUNTY TO COMBINE THE UNITS HOWEVER
 I DO NOT KNOW IF THEY HAS RECEIVED THOSE DOCUMENTS.
 PLEASE RECIEVED THE INSTRUCTIONS ON HOW TO COMBINE THE
 PARCELS AND FOLLOW EACH ONE WITH THE APPROPRIATE
 CONTACT.
  
 STEP ONE: CONTACT VINCE NOEL [email protected] OR CALL
 561-494-1040 TO START THE UNITY OF TITLE PROCEDURE.
  
 STEP TWO: FILL OUT PALM BEACH COUNTYS PARCEL
 COMBINATION REQUEST FORM WHICH CAN BE FOUND AT THIS
 LINK HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM,
 THEY WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL
 NUMBER (PCN).
  
 STEP THREE: WHEN YOU CONTACT THE PROPERTY APPRAISERS
 YOU NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED
 PCN.
  
 STEP FOUR: ONCE YOU HAVE RECEIVED THE PRELIMINARY
 LETTER PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO BE ISSUED AN ADDRESS.
  
 PLEASE ENSURE THAT YOU ARE DOING THOSE STEPS IN THAT
 ORDER.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By cpuell Date 2023-04-18 Time 15:17 Rev Time 0.00
Received By cpuell Date 2023-04-18 Time 15:17 Sent To  
Notes
2023-04-18 15:20:42PLANS APPEAR TO SHOW THAT UNIT 1203 AND UNIT 1204 ARE
 BEING MERGED, THE HALLWAY PARTITION IS BEING REMOVED TO
 CREATE ONE UNIT. A UNITY OF TITLE WILL BE NEEDED,
 PLEASE CONTACT CONTACT VINCE NOEL [email protected] OR CALL
 561-494-1040 TO START THE UNITY OF TITLE PROCEDURE.
 CURRENTLY THERE ARE TWO SEPARATE PROPERTY CONTROL
 NUMBER (PCN) FOR THE TWO UNITS, YOU WILL NEED TO GO
 FILL OUT PALM BEACH COUNTYS PARCEL COMBINATION REQUEST
 FORM WHICH CAN BE FOUND AT THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL NUMBER
 (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU
 NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED PCN.
 ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE
 CONTACT [email protected] OR CALL 561-805-6659 TO BE
 ISSUED A SINGULAR ADDRESS.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By lbond Date 2023-05-03 Time 08:48 Rev Time 0.00
Received By lbond Date 2023-05-03 Time 08:48 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 15:24 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 15:24 Sent To  
Notes
2023-04-10 15:25:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23020604
  
 REVIEWED: 04.10. 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENT:
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By lbond Date 2023-05-03 Time 08:52 Rev Time 0.00
Received By lbond Date 2023-05-03 Time 08:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 15:56 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 15:56 Sent To  
Notes
2023-04-10 16:00:11PLEASE CLEARLY IDENTIFY THE SCOPE OF WORK FOR UNIT 1204
 ONLY.
 PLEASE PROVIDE ALL TRADE INFO RELEVANT TO THIS PERMIT
 FOR THIS UNIT.
 WE UNDERSTAND YOU ARE COMNBINING THE 2 UNITS, BUT EACH
 PERMIT IS SEPERATE. THE INFORMATION ON EACH UNIT SHOULD
 BE SEPERATED FROM THE OTHER AND CLEARLY IDENTIFIED.
 PLEASE COMPLY TO PLUMBING AND SIGNATURE COMMENTS, ALSO
 NEW HOME OFFICE CLOSET AND WALL PARTITION WILL ALTER
 THE EXTERIOR ELEVATION-PROVIDE FLOOR TO CEILING SECTION
 CONNECTING WALL TO GLAZING.
 PLEASE MAKE SURE THIS IS OK WITH THE CONDO ASSOCIATION.
 IF NOT PROVIDE AN ALTERNATIVE THAT WOULD BE.
 THANK YOU.
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-15 Cont ID  
Sent By rperdomo Date 2023-05-15 Time 15:16 Rev Time 0.00
Received By rperdomo Date 2023-05-15 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By rperdomo Date 2023-04-10 Time 14:42 Rev Time 0.00
Received By rperdomo Date 2023-04-10 Time 14:22 Sent To  
Notes
2023-04-10 14:41:41FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE PANEL SCHEDULE IN ACCORDANCE WITH NEC
 408.4(B).
  
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By pleduc Date 2023-05-03 Time   Rev Time 0.00
Received By pleduc Date 2023-05-03 Time 11:17 Sent To  
Notes
2023-05-03 11:18:20FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-04 Cont ID  
Sent By pleduc Date 2023-04-04 Time   Rev Time 0.00
Received By pleduc Date 2023-04-04 Time 10:59 Sent To  
Notes
2023-04-04 13:22:24FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 11:27 Rev Time 0.00
Received By cpuell Date 2023-06-12 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-07 Cont ID  
Sent By cmontell Date 2023-06-07 Time 13:09 Rev Time 0.00
Received By cmontell Date 2023-06-07 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-16 Cont ID  
Sent By aoliver Date 2023-05-16 Time 08:14 Rev Time 0.00
Received By aoliver Date 2023-05-02 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-18 Cont ID  
Sent By cpuell Date 2023-04-18 Time 15:20 Rev Time 0.00
Received By cpuell Date 2023-03-31 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-06-07 Cont ID  
Sent By cmontell Date 2023-06-07 Time 13:08 Rev Time 0.00
Received By cmontell Date 2023-06-07 Time 13:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 08:51 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 08:51 Sent To  
Notes
2023-05-09 08:52:27LIKE FOR LIKE CHANGE OUT FORM WAS NOT SUBMITTED AGAIN
 IN THIS REVIEW CYCLE. PROVIDE THE COMPLETED LIKE FOR
 LIKE CHANGE OUT FORM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-13 Cont ID  
Sent By medwards Date 2023-04-13 Time 11:34 Rev Time 0.00
Received By medwards Date 2023-04-13 Time 11:34 Sent To  
Notes
2023-04-13 11:35:031ST REVIEW FMC
 PERMIT: 23021107
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM FOR THE
 AHU THAT IS TO BE CHANGED OUT. THIS SHOULD SHOW THE
 INFORMATION FOR THE EXISTING UNIT AND THE INFORMATION
 FOR THE NEW UNIT, INCLUDING THE NEW SEER2 RATING OF THE
 REPLACEMENT UNIT.
  
 2) DOCUMENTS SUBMITTED WILL NEED THE DESIGNERS DIGITAL
 SIGNATURE. FS 471/481
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By ccole Date 2023-05-09 Time 10:37 Rev Time 0.00
Received By ccole Date 2023-05-09 Time 10:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By ccole Date 2023-04-10 Time 10:34 Rev Time 0.00
Received By ccole Date 2023-04-10 Time 10:19 Sent To  
Notes
2023-04-10 10:35:081ST REVIEW FBC-2020 PLUMBING
 PERMIT-23021107
 4/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE ARCHITECTURAL PLANS SHOW A NEW SHOWER
 IN THE MASTER BATHROOM 2, A RELOCATED LAV SINK IN THE
 GUEST BATHROOM, A RELOCATE WASHING MACHINE, AND A
 REMODELED KITCHEN 2. PROVIDE PLUMBING RISER DRAWINGS
 SHOWING ALL NEW DRAIN, VENT AND WATER SUPPLY PIPINGS-
 SEC. 107.3.5.1.3 WPB.
  
 2) SHEET P1: THE PLAN SHALL BEAR EITHER THE DIGITAL
 SIGNATURE AND SEAL OF THE FL. LICENSED DESIGN
 PROFESSIONAL, OR THE PRINTED NAME AND SIGNATURE OF THE
 CONTRACTOR OR QUALIFIER- SEC. 107.2.1, FL. STATUTES 471
 & 481.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By lbond Date 2023-05-03 Time 08:51 Rev Time 0.00
Received By lbond Date 2023-05-03 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 16:00 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 16:00 Sent To  
Notes
2023-04-10 15:52:06BUILDING: FAILED
  
 SHEET A-1
 THE PLAN SHALL BEAR EITHER THE DIGITAL SIGNATURE AND
 SEAL OF THE FL. LICENSED DESIGN PROFESSIONAL, OR THE
 PRINTED NAME AND SIGNATURE OF THE CONTRACTOR OR
 QUALIFIER- SEC. 107.2.1, FL. STATUTES 471 & 481.
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
2023-04-10 10:42:44SHEET P1 (PLUMBING) DOES NOT HAVE A SIGNATURE BY A
 DESIGN PROFESSIONAL OR THE CONTRACTOR.