| Plan Review Stops For Permit 23021085 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-26 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-26 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2023-05-26 12:02:30 | PROVISO | | | INCLUDE UPDATED SHEET INDEX ON PAGE A0 THAT IS SIGNED | | | AND SEALED WITH TITLE BLOCK, CLOUD IT. | | | REMOVE INDEX OF DRAWING THAT IS NOT SIGNED AND SEALED | | | IN PROJECTDOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-13 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-13 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2023-03-13 11:26:40 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 22121339 | | | | | | REVIEWED: MARCH 9, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | PROVIDE SUPPORTING DOCUMENT FOR NOA OR FPA APPROVED FOR | | | ALL NEW WINDOWS AND DOORS, | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-06-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-06-02 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-06-02 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-03-16 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-03-16 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2023-03-16 12:02:48 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) GENERATOR REQUIRES SEPARATE PLANS AND PERMIT. | | | | | | 2) ALL 120 VOLT 15 AND 20 AMP RECEPTACLE OUTLETS IN | | | LAUNDRY ROOM TO BE GFCI PROTECTED. 210.8(A)(10) | | | | | | 3) OUTLET SPACING ON WORK SURFACE COUNTER IN LAUNDRY | | | AREA MAY NEED ADDITIONAL OUTLETS. 210.52(C)(1) |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-05-26 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-05-26 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-06 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-06 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2023-03-06 14:49:18 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23021085 | | | 3/6/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-0.1: A COMPLETE GAS PIPING PLAN AND RISER | | | DRAWING IS REQUIRED WHICH INCLUDES THE EXISTING | | | INTERIOR GAS PIPING AND APPLIANCE LOADS- SEC. G2412.3 & | | | G2412.4 FBC RES. REVISE THE DRAWINGS TO SHOW THE | | | FOLLOWING ITEMS: | | | A) TYPE AND SIZE OF THE MAIN SUPPLY PIPE AT THE METER | | | AND THE INTERIOR PIPING POINT OF CONNECTION TO THE | | | MAIN. | | | B) TYPE AND SIZE OF RISER PIPE FROM THE PE TO THE MAIN. | | | C) REVISE THE GAS SCHEDULE TO INCLUDE THE EXISTING | | | APPLIANCE LOADS AND THE TOTAL LOAD. | | | | | | 2) P-0.1: PLEASE SHOW THE CLEARANCE DISTANCE FROM THE | | | GENERATOR EXHAUST TO MECHANICAL AND GRAVITY AIR INTAKES | | | INTO THE BUILDING INCLUDING OPERABLE WINDOWS AND DOORS. | | | PLEASE NOTE A MINIMUM 10 FT. CLEARANCE IS REQUIRED. | | | | | | 3) P-0.1: PLEASE PLACE A NOTE ON THE PLAN INDICATING A | | | SEPARATE PERMIT IS REQUIRED FOR THE NEW GENERATOR- SEC. | | | 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-07-10 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-07-10 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-29 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-29 |
Time |
12:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-07-17 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-05-25 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-03 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-31 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2023-03-31 08:04:22 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-06-15 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-15 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-15 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-09 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-09 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2023-03-09 07:26:13 | 1ST REVIEW FMC | | | PERMIT: 23021085 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. | | | FEC R101.5.1.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC R403.7.1 | | | | | | 3) THE RETURN FOR AHU-3 CANNOT BE FROM THE CLOSET. FRC | | | M1602.2 ITEM 4. | | | | | | 4) PROVIDE THE RETURN AIR PATH FOR THE NEW BEDROOM. FRC | | | M1602.3 | | | | | | 5) SHEET M-1 INDICATES AN EF-2 100 CFM, SHOW THIS FAN | | | IN THE EXHAUST FAN SCHEDULE ON SHEET M-2. FBC 107.3.5 | | | | | | 6) THE DESIGNER OF THE MECHANICAL DRAWINGS MUST | | | DIGITALLY SIGN EACH SHEET. FS 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-05-26 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-05-26 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-06 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-06 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2023-03-06 14:17:01 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23021085 | | | 3/6/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-2: IT APPEARS THAT THE AIR HANDLER IN THE | | | CLOSET WILL BE OBSTRUCTING THE REQUIRED 30X30 INCH | | | ACCESS SPACE ON THE CONTROL SIDE OF THE NEW TANKLESS | | | WATER HEATER (WH2)- SECS. P2801.4 & M1305.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-17 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-17 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-13 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-13 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2023-03-13 11:30:36 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23021085 | | | | | | REVIEWED: MARCH 13, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | ROOF COMMENTS: FAILED | | | | | | AS PER SECTION 107.2.1 | | | PLEASES PROVIDE NOA APPROVED FOR ALL COMPONENTS OF THE | | | UPDATED NEW ROOF | | | ROOF CALCULATIONS AND SYSTEM USED DIGITALLY SIGNED AND | | | SEALED BY ENGINEER | | | | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-26 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-26 |
Time |
12:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-31 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2023-03-13 10:47:32 | ARCHITECTURE SHEETS ARE DIGITALLY SIGNED OTHER | | | DISCIPLINE NOT- PLEASE UPDATE | | 2023-03-09 07:27:13 | THE DESIGNER OF THE MECHANICAL DRAWINGS MUST DIGITALLY | | | SIGN EACH SHEET. ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-07-10 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-07-10 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-29 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-29 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2023-03-29 12:55:56 | VALUE OF WORK REQUIRES FILING OF SEPERATE LANDSCAPE | | | PERMIT |
|
|