| 2023-03-10 15:34:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | |
| | COURTESY REVIEW VIA EMAIL |
| | |
| | 1. FBC R 703.4, FBC B 1405.4, PRODUCT SHEET FOR DOWSILL |
| | CONTRACTOR'S PAINTABLE SEALANT WAS SUBMITTED VIA EMAIL. |
| | THIS PRODUCT APPEARS TO COMPLY WITH ASTM C-920 FOR |
| | CAULKING. IT IS NOT CLEAR WITH WHICH METHOD IN FBC R |
| | 703.4 THIS COMPLIES FOR FLASHING, SEE OPTIONS BELOW. |
| | SENT OPTIONS TO CONTRACTOR VIA EMAIL. |
| | |
| | R703.4FLASHING. |
| | APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED |
| | MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING |
| | SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH |
| | THE MANUFACTURER???S INSTRUCTIONS. METAL FLASHING SHALL |
| | BE CORROSION RESISTANT. FLUID-APPLIED MEMBRANES USED AS |
| | FLASHING SHALL BE APPLIED IN ACCORDANCE WITH THE |
| | MANUFACTURER'S INSTRUCTIONS. ALL FLASHING SHALL BE |
| | APPLIED IN A MANNER TO PREVENT THE ENTRY OF WATER INTO |
| | THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING |
| | STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED MEMBRANES |
| | USED AS FLASHING SHALL COMPLY WITH AAMA 711. ALL |
| | EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT THE |
| | JUNCTURE WITH THE BUILDING WALL WITH A SEALANT |
| | COMPLYING WITH AAMA 800 OR ASTM C920 CLASS 25 GRADE NS |
| | OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, |
| | ASTM C1281, AAMA 812, OR OTHER APPROVED STANDARD AS |
| | APPROPRIATE FOR THE TYPE OF SEALANT. FLUID-APPLIED |
| | MEMBRANES USED AS FLASHING IN EXTERIOR WALLS SHALL |
| | COMPLY WITH AAMA 714. THE FLASHING SHALL EXTEND TO THE |
| | SURFACE OF THE EXTERIOR WALL FINISH. APPROVED FLASHINGS |
| | SHALL BE INSTALLED AT THE FOLLOWING LOCATIONS: |
| | |
| | 1.EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT |
| | EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND TO THE |
| | SURFACE OF THE EXTERIOR WALL FINISH OR TO THE |
| | WATER-RESISTIVE BARRIER COMPLYING WITH SECTION 703.2 |
| | FOR SUBSEQUENT DRAINAGE. MECHANICALLY ATTACHED FLEXIBLE |
| | FLASHINGS SHALL COMPLY WITH AAMA 712. FLASHING AT |
| | EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING: |
| | |
| | 1.1.THE FENESTRATION MANUFACTURER???S INSTALLATION AND |
| | FLASHING INSTRUCTIONS, OR FOR APPLICATIONS NOT |
| | ADDRESSED IN THE FENESTRATION MANUFACTURER???S |
| | INSTRUCTIONS, IN ACCORDANCE WITH THE FLASHING |
| | MANUFACTURER???S INSTRUCTIONS. WHERE FLASHING |
| | INSTRUCTIONS OR DETAILS ARE NOT PROVIDED, PAN FLASHING |
| | SHALL BE INSTALLED AT THE SILL OF EXTERIOR WINDOW AND |
| | DOOR OPENINGS. PAN FLASHING SHALL BE SEALED OR SLOPED |
| | IN SUCH A MANNER AS TO DIRECT WATER TO THE SURFACE OF |
| | THE EXTERIOR WALL FINISH OR TO THE WATER-RESISTIVE |
| | BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN |
| | FLASHING SHALL INCORPORATE FLASHING OR PROTECTION AT |
| | THE HEAD AND SIDES. |
| | |
| | 1.2.IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF |
| | A REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 1.3.IN ACCORDANCE WITH OTHER APPROVED METHODS. |
| | |
| | 1.4IN ACCORDANCE WITH FMA/AAMA 100, FMA/AAMA 200, |
| | FMA/WDMA 250, FMA/AAMA/WDMA 300 OR FMA/AAMA/WDMA 400. |
| | |
| | 2. FS471, THE ENGINEERING IS NOT DIGITALLY SIGNED. |
| | EITHER UPLOAD DIGITALLY SIGNED ENGINEERING OR EMAIL |
| | [email protected] AND REQUEST THAT IT BE DELETED. |
| | |
| | |