Plan Review Details - Permit 23021063
Plan Review Stops For Permit 23021063
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-27 Cont ID  
Sent By jwitmer Date 2023-06-27 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2023-06-27 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 14:42 Sent To  
Notes
2023-05-09 14:55:532020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 09TH, 2023
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET T1 COVERSHEET, PLEASE UPDATE TO
 THE 2020 FBC-BUILDING CODE, NOT THE 2018 IBC. PLEASE
 UPDATE PLANS.
  
 2) 2ND REQUEST. SHEET C-3 DOES NOT PROVIDE A WIND
 DESIGN AS TO THE CHARGING STATIONS WERE DESIGNED. 2020
 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
  
 3) SEMI-COMPLIED. SHEET C-3 INDICATES A HANDICAPPED
 STRIPING DETAIL.
 2ND REQUEST. 502.4 ACCESS AISLE & PARKING SPACE SAME
 LEVEL/ 502.4, FLOOR AND GROUND SURFACES. PARKING SPACES
 AND THE ACCESS AISLES SERVING THEM SHALL COMPLY WITH
 302. ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE
 PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By jwitmer Date 2023-03-21 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2023-03-21 Time 09:34 Sent To  
Notes
2023-03-21 10:19:03 
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23021063
 ADD: 2370 45TH STREET
 CONT: NEELZ CONTRACTING
 TEL: 561-275-5671
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 21, 2023
 ACTION: DENIED
  
 1) SHEET T1 COVERSHEET, PLEASE UPDATE THE 2020
 FBC-BUILDING CODE AND FAMILY OF CODES IS BASED ON THE
 2018 IBC. PLEASE UPDATE PLANS.
  
 2) SHEET C-3 DOES NOT PROVIDE A WIND DESIGN AS TO THE
 CHARGING STATIONS WERE DESIGNED. 2020 FBC-B 1603.1.4
 WIND DESIGN CRITERIA.
  
 3) SHEET C-3 INDICATES A HANDICAPPED STRIPING DETAIL.
 ACCESSIBLE PARKING SPACE / STALL PAINTING.
 2020 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 502.4 ACCESS AISLE & PARKING SPACE SAME LEVEL/ 502.4,
 FLOOR AND GROUND SURFACES. PARKING SPACES AND THE
 ACCESS AISLES SERVING THEM SHALL COMPLY WITH 302.
 ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING
 SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-06-26 Cont ID  
Sent By mpeterso Date 2023-06-26 Time 14:57 Rev Time 0.00
Received By mpeterso Date 2023-06-26 Time 14:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-05-22 Cont ID  
Sent By mpeterso Date 2023-05-22 Time 09:52 Rev Time 0.00
Received By mpeterso Date 2023-05-22 Time 09:46 Sent To  
Notes
2023-05-22 09:53:342ND ELECTRICAL REVIEW FAILED
  
 1) PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 14:25 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 14:25 Sent To  
Notes
2023-03-10 14:46:29ELECTRIC REVIEW FAILED
  
 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
 FBC 109.3 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN
 ESTIMATED PERMIT VALUE AT TIME OF APPLICATION. PERMIT
 VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING
 MATERIALS AND LABOR, FOR WHICH THE PERMIT IS BEING
 ISSUED, SUCH AS ELECTRICAL, GAS, MECHANICAL, PLUMBING
 EQUIPMENT AND PERMANENT SYSTEMS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE VALUATION IS UNDERESTIMATED
 ON THE APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS
 THE APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL
  
 2) NO SECIFICATIONS WERE PROVIDED FOR THE TESLA SUPER
 CHARGER CABINETS. PLEASE PROVIDE SPECIFICATIONS FOR
 THESE SUPER CHARGER CABINETS. PLEASE ENSURE THEY
 PROVIDE DISCONNECTION AND OVER CURRENT PROTECTION FOR
 EACH CHARGING POST CIRCUIT. NEC 240.4 AND NEC 625.43
  
 240.4 PROTECTION OF CONDUCTORS.
 CONDUCTORS, OTHER THAN FLEXIBLE CORDS, FLEXIBLE CABLES,
 AND FIXTURE WIRES, SHALL BE PROTECTED AGAINST
 OVERCURRENT IN ACCORDANCE WITH THEIR AMPACITIES
  
 625.43 DISCONNECTING MEANS.
 FOR EQUIPMENT RATED MORE THAN 60 AMPERES OR MORE THAN
 150 VOLTS TO GROUND, THE DISCONNECTING MEANS SHALL BE
 PROVIDED AND INSTALLED IN A READILY ACCESSIBLE
 LOCATION. THE DISCONNECTING MEANS SHALL BE LOCKABLE
 OPEN IN ACCORDANCE WITH 110.25.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-05-09 Cont ID  
Sent By lquinone Date 2023-05-09 Time 11:19 Rev Time 0.00
Received By lquinone Date 2023-05-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-06-30 Cont ID  
Sent By clfranci Date 2023-06-30 Time   Rev Time 0.00
Received By clfranci Date 2023-06-30 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-11 Cont ID  
Sent By pleduc Date 2023-05-11 Time   Rev Time 0.00
Received By pleduc Date 2023-05-11 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By pleduc Date 2023-05-03 Time   Rev Time 0.00
Received By pleduc Date 2023-05-03 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By pleduc Date 2023-02-23 Time   Rev Time 0.00
Received By pleduc Date 2023-02-23 Time 12:38 Sent To  
Notes
2023-02-23 12:53:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION NO CLEAR INDICATION OF AN
 EMEGENCY DISCONNECT REMOTELY LOCATED.
  
 FOR THE OFFICIAL RECORD, AND PER NFPA 70, PLEASE
 PROVIDE THE LOCATION OF AN EMERGECNY DISCONNECT WITH
 PROPER SIGNAGE FOR 1ST RESPONDERS IN THE EVENT OF
 EMERGECNY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-03 Cont ID  
Sent By aoliver Date 2023-07-03 Time 13:05 Rev Time 0.00
Received By aoliver Date 2023-06-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2023-05-10 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-09 Cont ID  
Sent By lmarchan Date 2023-05-09 Time 12:58 Rev Time 0.00
Received By lmarchan Date 2023-05-02 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-21 Cont ID  
Sent By jwitmer Date 2023-03-21 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2023-02-22 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-27 Cont ID  
Sent By jwitmer Date 2023-06-27 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2023-06-27 Time 13:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 12:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 14:47 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-03 Cont ID  
Sent By llouie Date 2023-07-03 Time   Rev Time 0.00
Received By llouie Date 2023-07-03 Time   Sent To  
Notes
2023-07-03 11:48:18* REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE
 CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS).
  
 * REFERENCE: LANDSCAPE PERMIT #23050492
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By llouie Date 2023-05-19 Time   Rev Time 0.00
Received By llouie Date 2023-05-19 Time   Sent To  
Notes
2023-05-19 10:39:31* REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE
 CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS).
  
 * REFERENCE: LANDSCAPE PERMIT #23050492
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By LLouie Date 2023-03-03 Time   Rev Time  
Received By llouie Date 2023-03-03 Time   Sent To  
Notes
2023-03-03 13:59:08** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) DETAIL OF THE PARKING STALL STRIPING, CONSISTENT
 WITH THE CITY'S MINIMUM STRIPING STANDARDS SHALL BE
 INCLUDED IN THE PERMIT PLANS. [ZLDR S.94-485]
  
 2.) SEPARATE LANDSCAPE PERMIT FOR THE LANDSCAPE
 IMPROVEMENTS SHALL BE SUBMITTED PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT.
  
 3.) PLEASE ATTACH/UPLOAD A COPY OF THE CONDITIONAL
 APPROVAL LETTER FOR PB CASE NO. 1837F TO THIS FILE FOR
 THE BUILDING PERMIT RECORD.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE
 CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS).
  
 * SPOKE TO SHERYL BLASI, AGENT, ON 3/3/2023 TO GO OVER
 REQUIRED DOCUMENTS, ILLUSTRATIONS AND PROCESSES.
  