Plan Review Stops For Permit 23021063 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2023-06-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-06-27 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-06-27 |
Time |
13:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-06-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-06-06 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-06-06 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-05-09 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-05-09 |
Time |
14:42 |
Sent To |
|
|
Notes |
2023-05-09 14:55:53 | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: TUES. MAY 09TH, 2023 | | ACTION: DENIED | | | | 1) 2ND REQUEST. SHEET T1 COVERSHEET, PLEASE UPDATE TO | | THE 2020 FBC-BUILDING CODE, NOT THE 2018 IBC. PLEASE | | UPDATE PLANS. | | | | 2) 2ND REQUEST. SHEET C-3 DOES NOT PROVIDE A WIND | | DESIGN AS TO THE CHARGING STATIONS WERE DESIGNED. 2020 | | FBC-B 1603.1.4 WIND DESIGN CRITERIA. | | | | 3) SEMI-COMPLIED. SHEET C-3 INDICATES A HANDICAPPED | | STRIPING DETAIL. | | 2ND REQUEST. 502.4 ACCESS AISLE & PARKING SPACE SAME | | LEVEL/ 502.4, FLOOR AND GROUND SURFACES. PARKING SPACES | | AND THE ACCESS AISLES SERVING THEM SHALL COMPLY WITH | | 302. ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE | | PARKING SPACES THEY SERVE. | | CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES | | NOT GREATER THAN 1:48 SHALL BE PERMITTED. | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT | | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ SEMI-RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-03-21 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-03-21 |
Time |
09:34 |
Sent To |
|
|
Notes |
2023-03-21 10:19:03 | | | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 23021063 | | ADD: 2370 45TH STREET | | CONT: NEELZ CONTRACTING | | TEL: 561-275-5671 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: TUES. MARCH 21, 2023 | | ACTION: DENIED | | | | 1) SHEET T1 COVERSHEET, PLEASE UPDATE THE 2020 | | FBC-BUILDING CODE AND FAMILY OF CODES IS BASED ON THE | | 2018 IBC. PLEASE UPDATE PLANS. | | | | 2) SHEET C-3 DOES NOT PROVIDE A WIND DESIGN AS TO THE | | CHARGING STATIONS WERE DESIGNED. 2020 FBC-B 1603.1.4 | | WIND DESIGN CRITERIA. | | | | 3) SHEET C-3 INDICATES A HANDICAPPED STRIPING DETAIL. | | ACCESSIBLE PARKING SPACE / STALL PAINTING. | | 2020 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES. | | EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL | | BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN | | ADJACENT ACCESS AISLE COMPLYING WITH 502.3. | | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR | | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT | | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. | | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 | | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL | | PAINTING. | | | | 502.4 ACCESS AISLE & PARKING SPACE SAME LEVEL/ 502.4, | | FLOOR AND GROUND SURFACES. PARKING SPACES AND THE | | ACCESS AISLES SERVING THEM SHALL COMPLY WITH 302. | | ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING | | SPACES THEY SERVE. | | CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES | | NOT GREATER THAN 1:48 SHALL BE PERMITTED. | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT | | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | PART-TIME/ SEMI-RETIRED. | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | BACK INTO THE OFFICE CALL | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | THANK YOU. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-06-26 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-06-26 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-06-26 |
Time |
14:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-05-22 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-05-22 |
Time |
09:46 |
Sent To |
|
|
Notes |
2023-05-22 09:53:34 | 2ND ELECTRICAL REVIEW FAILED | | | | 1) PREVIOUS COMMENTS NOT ADDRESSED |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-10 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-03-10 |
Time |
14:25 |
Sent To |
|
|
Notes |
2023-03-10 14:46:29 | ELECTRIC REVIEW FAILED | | | | 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, | | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR | | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 | | | | FBC 109.3 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN | | ESTIMATED PERMIT VALUE AT TIME OF APPLICATION. PERMIT | | VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING | | MATERIALS AND LABOR, FOR WHICH THE PERMIT IS BEING | | ISSUED, SUCH AS ELECTRICAL, GAS, MECHANICAL, PLUMBING | | EQUIPMENT AND PERMANENT SYSTEMS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE VALUATION IS UNDERESTIMATED | | ON THE APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS | | THE APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING | | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL | | | | 2) NO SECIFICATIONS WERE PROVIDED FOR THE TESLA SUPER | | CHARGER CABINETS. PLEASE PROVIDE SPECIFICATIONS FOR | | THESE SUPER CHARGER CABINETS. PLEASE ENSURE THEY | | PROVIDE DISCONNECTION AND OVER CURRENT PROTECTION FOR | | EACH CHARGING POST CIRCUIT. NEC 240.4 AND NEC 625.43 | | | | 240.4 PROTECTION OF CONDUCTORS. | | CONDUCTORS, OTHER THAN FLEXIBLE CORDS, FLEXIBLE CABLES, | | AND FIXTURE WIRES, SHALL BE PROTECTED AGAINST | | OVERCURRENT IN ACCORDANCE WITH THEIR AMPACITIES | | | | 625.43 DISCONNECTING MEANS. | | FOR EQUIPMENT RATED MORE THAN 60 AMPERES OR MORE THAN | | 150 VOLTS TO GROUND, THE DISCONNECTING MEANS SHALL BE | | PROVIDED AND INSTALLED IN A READILY ACCESSIBLE | | LOCATION. THE DISCONNECTING MEANS SHALL BE LOCKABLE | | OPEN IN ACCORDANCE WITH 110.25. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-05-09 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-05-09 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2023-06-30 |
|
|
Cont ID |
|
Sent By |
clfranci |
Date |
2023-06-30 |
Time |
|
Rev Time |
0.00 |
Received By |
clfranci |
Date |
2023-06-30 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2023-05-11 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-11 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-11 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-03 |
Time |
11:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-02-23 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-02-23 |
Time |
12:38 |
Sent To |
|
|
Notes |
2023-02-23 12:53:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION NO CLEAR INDICATION OF AN | | EMEGENCY DISCONNECT REMOTELY LOCATED. | | | | FOR THE OFFICIAL RECORD, AND PER NFPA 70, PLEASE | | PROVIDE THE LOCATION OF AN EMERGECNY DISCONNECT WITH | | PROPER SIGNAGE FOR 1ST RESPONDERS IN THE EVENT OF | | EMERGECNY. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-07-03 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-07-03 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-06-21 |
Time |
16:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-06-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-06-06 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-05-10 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-05-09 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-05-02 |
Time |
09:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-03-21 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-02-22 |
Time |
11:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-06-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-06-27 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-06-27 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-06-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-06-06 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-06-06 |
Time |
12:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-03-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-10 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-03-10 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2023-07-03 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2023-07-03 |
Time |
|
Sent To |
|
|
Notes |
2023-07-03 11:48:18 | * REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE | | CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS). | | | | * REFERENCE: LANDSCAPE PERMIT #23050492 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2023-05-19 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2023-05-19 |
Time |
|
Sent To |
|
|
Notes |
2023-05-19 10:39:31 | * REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE | | CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS). | | | | * REFERENCE: LANDSCAPE PERMIT #23050492 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-03-03 |
|
|
Cont ID |
|
Sent By |
LLouie |
Date |
2023-03-03 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2023-03-03 |
Time |
|
Sent To |
|
|
Notes |
2023-03-03 13:59:08 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) DETAIL OF THE PARKING STALL STRIPING, CONSISTENT | | WITH THE CITY'S MINIMUM STRIPING STANDARDS SHALL BE | | INCLUDED IN THE PERMIT PLANS. [ZLDR S.94-485] | | | | 2.) SEPARATE LANDSCAPE PERMIT FOR THE LANDSCAPE | | IMPROVEMENTS SHALL BE SUBMITTED PRIOR TO THE ZONING | | APPROVAL OF THIS PERMIT. | | | | 3.) PLEASE ATTACH/UPLOAD A COPY OF THE CONDITIONAL | | APPROVAL LETTER FOR PB CASE NO. 1837F TO THIS FILE FOR | | THE BUILDING PERMIT RECORD. | | | | | | NOTES: | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * REFERENCE: PB CASE NO. 1837F (PALM BEACH RIVERSTONE | | CPD - MINOR PD AMENDMENT, TESLA CHARGING STATIONS). | | | | * SPOKE TO SHERYL BLASI, AGENT, ON 3/3/2023 TO GO OVER | | REQUIRED DOCUMENTS, ILLUSTRATIONS AND PROCESSES. | | |
|
|