| Plan Review Stops For Permit 23020859 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-24 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-24 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2023-02-24 14:49:24 | WORK IS BEING DONE ON BOUTH THE NORTH AND SOUTH | | | BUILDING, UPDATED PERMIT TO REFLECT THE TWO ADDRESSES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-17 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-17 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2023-07-17 17:19:31 | FBC 107.2.1. | | | | | | | | | 1. WHAT ARE THE PROPERTIES OF THIS EXISITING GARAGE | | | DOOR? IS IT INSULATED, IMPACT RESISTANT, OPERABLE? | | | FIXED? | | | | | | 2. HOW IS THIS DETACHED BUILDING INSULATED? | | | | | | 3.CLARIFY HOW THIS BEDROOM IN THE PROPOSED FLOOR PLAN | | | WILL HAVE A MIN 5 S.F. REQUIRED EGRESS WINDOW BY CODE | | | FBC 1030.2? | | | | | | 4.HOW DO YOU ACCESS THE BATHROOM FORM THE BEDROOM? I | | | SEE A SOLID WALL AND NO DOOR. | | | | | | PLEASE ANSWER EACH COMMENT WITH A NARRATIVE. | | | ANY QUESTIONS OR CONCERNS, | | | | | | PLEASE REACH OUT: | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-27 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-27 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-27 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2023-04-27 09:12:38 | PREVIOUS COMMENTS NOT ANSWERED. | | | | | | PROVIDE BUIILDING 2 FLOOR PLAN AND ELEVATIONS-EXISTING | | | DEMO AND PROPOSED. | | | FPC PRODUCT APPROVAL FOR ALL NEW WINDOWS AND DOORS. | | | PLEASE REPLY TO ALL COMMENTS WITH A NARRATIVE. | | | | | | THANK YOU | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-06 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-06 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2023-03-06 16:52:36 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 22120266 | | | | | | REVIEWED: MARCH 6, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | 1)PROVIDE SUPPORTING DOCUMENTS FOR NOA OR FPA APPROVED | | | FOR NEW WINDOW REPLACING GARAGE DOOR IN BUILDING 2 | | | 2)CLEARLY DEFINE SCOPE OF WORK FOR BUILDING 2; INCLUDE | | | GARAGE DOOR INFILL DETAILS. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-17 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-17 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2023-07-17 14:50:36 | ELECTRIC REVIEW FAILED | | | PROVIDED A WRITTEN NARRATIVE HOW THE BELOW COMMENTS | | | WILL BE ADDRESSED. | | | 1) SITE PLAN IDENTIFYING ALL STRUCTURES. FBC 107.2 NOT | | | ADDRESSED | | | | | | 2) A NARRATIVE WORK SCOPE FOR EACH STRUCTURE. FBC 107.2 | | | PARTIALLY ADDRESSED. PLANS STATE REPLACE WIRING AS | | | NEEDED. PLAN REVIEW REQUIRES MORE SPECIFICITY. WHICH | | | WIRING IS TO BE REPLACED AND WHICH IS TO REMAIN? NO | | | SWITCHES OR OUTLETS ARE INDICATED AS REMAINING OR TO BE | | | REPLACED, IF ALL ARE TO BE REPLACED THEN STATE IT. | | | | | | 3) A SITE PLAN LOCATING ALL METERS, DISCONNECTS, | | | ELECTRIC PANELS, AIR CONDITIONING EQUIPMENT AND ALL | | | OTHER RELEVANT ELECTRICAL EQUIPMENT. LABEL ALL | | | EQUIPMENT AS APPLICABLE. IF THERE IS MORE THAN ONE, | | | LABEL THEM ACCORDINGLY AS A, B, C ETC.. NEC 215.5 AND | | | FBC 107.2 | | | NOT ADDRESSED | | | | | | 4) PROVIDE A RISER DIAGRAM DETAILING ALL METERS, | | | DISCONNECTS, ELECTRIC PANELS AND SUBPANELS. INCLUDE ALL | | | CONDUIT, CONDUCTOR AND EQUIPMENT SIZES. INCLUDE ALL | | | GROUNDING ELECTRODE SYSTEMS. INCLUDE ALL NEW PROPOSED | | | EQUIPMENT AND SUB PANELS. THERE IS A SUBMITTAL FOR A | | | NEW POOL INSTALLATION THAT DETAILS ADDITIONAL ELECTRIC | | | LOADS TO BE INSTALLED. IF THIS IS A SUB PANEL, INCLUDE | | | THIS IN THE RISER. NEC 215.5 AND FBC 107.2 | | | NOT ADDRESSED. FLOOR PLANS DETAIL 2 ELECTRIC PANELS IN | | | ONE STRUCTURE AND 1 IN THE OTHER. RISER DETAILS A METER | | | AND 2 ELECTRIC PANELS. PLEASE PROVIDE A CORRECT | | | ELECTRIC RISER DIAGRAM. 2/0 CU WIRE IS DETAILED | | | INCORRECTLY FOR A 225 AMP PANEL. THIS WIRE HAS AN | | | AMPACITY OF 175 AMPS. #6 CU WIRE IS DETAILED FOR A 125 | | | AMP PANEL WITH A 100 AMP BREAKER AS OVERCURRENT | | | PROTECTION. #6 WIRE HAS AN AMPACITY OF 65 AMPS. | | | ELECTRIC FLOOR PLAN DOES NOT DETAIL ELECTRIC METER OR | | | PROPOSED POOL EQUIPMENT. | | | | | | 5) PROVIDE ALL PANEL SCHEDULES WITH ALL ELECTRIC LOADS | | | LISTED. NEC 215.5 AND FBC 107.2 | | | NOT ADDRESSED. SUBMITTAL IS STILL UNCLEAR WHERE AND HOW | | | MANY ELECTRIC PANELS EXIST. | | | | | | 6) PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. INCLUDE | | | ALL AIR CONDITIONING, WATER HEATERS, PUMPS, RANGES AND | | | OTHER ELECTRIC APPLIANCES. NEC 215.5 AND FBC 107.2 | | | NOT ADDRESSED | | | | | | 7) PROVIDE AN ACCURATE LOAD CALCULATION FOR EACH PANEL. | | | NEC 215.5 AND FBC 107.2 | | | NOT ADDRESSED. SUBMITTAL LACKS CLARITY. SEE PRIOR | | | COMMENTS. | | | | | | 8) PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE ENTIRE | | | SERVICE USING ONE OF THE TWO METHODS DESCRIBED IN NEC | | | ARTICLE 220 (STANDARD OR OPTIONAL) DETAIL ON | | | CALCULATION WHICH METHOD WAS USED. NEC 215.5 AND FBC | | | 107.2 | | | NOT ADDRESSED. SUBMITTAL LACKS CLARITY. CALCULATION | | | METHOD IS NOT DETAILED. DETAIL ALL LOADS USED TO ARRIVE | | | AT TOTAL GENERAL ELECTRICAL LOAD. SEE PRIOR COMMENTS. | | | | | | 9) PROVIDE ELECTRIC FLOOR PLANS FOR BOTH STRUCTURES. | | | INCLUDE ALL ELECTRIC OUTLETS, SWITCHES, RECEPTACLES, | | | APPLIANCES AND OTHER ELECTRICAL WIRING AS OUTLINED IN | | | NEC ARTICLE 210. FBC 107.2 | | | NOT ADDRESSED. SEE PRIOR COMMENTS. ONLY ONE SMALL | | | APPLIANCE CIRCUIT IS DETAILED. | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-05-02 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-05-02 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2023-05-02 14:11:29 | ELECTRIC REVIEW FAILED | | | | | | 1) THIS SUBMITTAL WORK SCOPE IS VERY UNCLEAR. ONE, THIS | | | IS FOR RENOVATION OF 2 STRUCTURES, HOWEVER ONLY ONE | | | ELECTRIC PLAN WAS SUBMITTED. PLEASE PROVIDE THE | | | FOLLOWING: | | | | | | 1) SITE PLAN IDENTIFYING ALL STRUCTURES. FBC 107.2 | | | | | | 2) A NARRATIVE WORK SCOPE FOR EACH STRUCTURE. FBC 107.2 | | | | | | 3) A SITE PLAN LOCATING ALL METERS, DISCONNECTS, | | | ELECTRIC PANELS, AIR CONDITIONING EQUIPMENT AND ALL | | | OTHER RELEVANT ELECTRICAL EQUIPMENT. LABEL ALL | | | EQUIPMENT AS APPLICABLE. IF THERE IS MORE THAN ONE, | | | LABEL THEM ACCORDINGLY AS A, B, C ETC.. NEC 215.5 AND | | | FBC 107.2 | | | | | | 4) PROVIDE A RISER DIAGRAM DETAILING ALL METERS, | | | DISCONNECTS, ELECTRIC PANELS AND SUBPANELS. INCLUDE ALL | | | CONDUIT, CONDUCTOR AND EQUIPMENT SIZES. INCLUDE ALL | | | GROUNDING ELECTRODE SYSTEMS. INCLUDE ALL NEW PROPOSED | | | EQUIPMENT AND SUB PANELS. THERE IS A SUBMITTAL FOR A | | | NEW POOL INSTALLATION THAT DETAILS ADDITIONAL ELECTRIC | | | LOADS TO BE INSTALLED. IF THIS IS A SUB PANEL, INCLUDE | | | THIS IN THE RISER. NEC 215.5 AND FBC 107.2 | | | | | | 5) PROVIDE ALL PANEL SCHEDULES WITH ALL ELECTRIC LOADS | | | LISTED. NEC 215.5 AND FBC 107.2 | | | | | | 6) PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. INCLUDE | | | ALL AIR CONDITIONING, WATER HEATERS, PUMPS, RANGES AND | | | OTHER ELECTRIC APPLIANCES. NEC 215.5 AND FBC 107.2 | | | | | | 7) PROVIDE AN ACCURATE LOAD CALCULATION FOR EACH PANEL. | | | NEC 215.5 AND FBC 107.2 | | | | | | 8) PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE ENTIRE | | | SERVICE USING ONE OF THE TWO METHODS DESCRIBED IN NEC | | | ARTICLE 220 (STANDARD OR OPTIONAL) DETAIL ON | | | CALCULATION WHICH METHOD WAS USED. NEC 215.5 AND FBC | | | 107.2 | | | | | | 9) PROVIDE ELECTRIC FLOOR PLANS FOR BOTH STRUCTURES. | | | INCLUDE ALL ELECTRIC OUTLETS, SWITCHES, RECEPTACLES, | | | APPLIANCES AND OTHER ELECTRICAL WIRING AS OUTLINED IN | | | NEC ARTICLE 210. FBC 107.2 | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-07 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-07 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2023-03-07 16:49:56 | ELECTRIC REVIEW FAILED | | | | | | 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR | | | PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED | | | INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM | | | PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE | | | CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE | | | MAIN SERVICE FEEDERS FROM THE METER TO PANEL A, | | | ACCORDING TO NEC 220.40, STANDARD CALCULATION OR | | | 220.80, OPTIONAL CALCULATION. | | | 2) BOTH RANGES ARE LISTED AS HAVING A LOAD OF 3KW, THE | | | MINIMUM LOAD AS PER NEC 220.55 IS 8KW. PLEASE CORRECT | | | LOAD CALCULATIONS FOR BOTH PANEL A AND B AS APPLICABLE | | | 3) PANEL B IS LISTED AS A 50 AMP PANEL, HOWEVER THE | | | LOAD LISTED ON THE LOAD CALCULATION IS STATED AS | | | 28,6886 WATTS. 28886/240= 120 AMPS. PLEASE CORRECT THE | | | PANEL SIZE AND FEEDERS AS APPLICABLE. NEC 215.2, FEEDER | | | CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN | | | REQUIRED TO SUPPLY THE LOAD AS CALCULATED | | | 4) PLEASE PROVIDE A WORK SCOPE AND ELECTRIC FLOOR PLAN | | | FOR DWELLING WITH THE GARAGE. FBC 107.2 | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL | | | 5) PROVIDE CORRECT ADDRESSES ON ALL PLANS FOR BOTH | | | STRUCTURES. FBC 107.2 | | | 6) CORRECTLY LABEL EACH ELECTRIC PANEL AS APPLICABLE. | | | FBC 107.2 | | | 7) PROVIDE AN ELECTRIC RISER THAT DETAILS THE CORRECT | | | EQUIPMENT SIZES AND GROUNDING ELECTRODE SYSTEMS AS | | | REQUIRED PER NEC 250.32 BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED | | | 8) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT | | | THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC | | | 210.52(E)(3) | | | NEC 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. | | | BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE | | | DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE | | | DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET | | | ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-06-01 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-06-01 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2023-06-01 09:42:01 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PREVIOUS COMMENTS NOT ADDRESSED SEE PREVIOUS COMMENTS. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-04-03 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-04-03 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2023-04-03 11:19:52 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PLANS DO NOT SEEM TO ACCURATELY REFLECT EXISTING AND | | | PROPOSED ELEVATIONS, PLEASE REVISE. PLEASE ALSO PROVIDE | | | MORE DETAILS REGARDING WINDOWS (FRAME COLOR, GLASS | | | COLOR). GARAGE DOOR CANNOT BE INFILLED, CAN BE REMOVED | | | BUT MUST BE REPLACED TO STILL REFLECT THE VISIUAL | | | APPEARANCE OF A GARAGE DOOR. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-14 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-05 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-26 |
Time |
16:19 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-04 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-24 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-07-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-22 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-22 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2023-07-22 06:49:27 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THE DETACHED HOUSE FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | CHRIS MONTELLO | | | 561-805-6733 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-02 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-02 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2023-05-02 11:56:25 | 2ND REVIEW FMC | | | PERMIT: 23020859 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED SHEET A-4 SUBMITTED THIS CYCLE SHOWS THE | | | DRYER LOCATION AND NEW MINI-SPLITS. PROVIDE THE ENERGY | | | CALCULATIONS FOR THESE NEW MINI-SPLITS. PROVIDE THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THESE | | | MINI-SPLITS. PROVIDE THE ANCHORING DETAILS FOR THE | | | MINI-SPLIT CONDENSING UNIT. PROVIDE A MECHANICAL | | | DRAWING SHOWING THESE CHANGES AND THE DRYER DUCT | | | INCLUDING THE SIZE AND TERMINATION LOCATION. FBC | | | 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-27 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-27 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2023-02-27 10:33:13 | 1ST REVIEW FMC | | | PERMIT: 23020859 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THE | | | DRYER DUCT LOCATION CHANGE. PROVIDE A NOTE ON THE | | | DRAWING SPECIFYING THE DRYER DUCT MATERIAL AND | | | TERMINATION LOCATION. FRC M1502 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-07-17 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-07-17 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2023-07-17 08:23:15 | 3RD PLUMBING REVIEW | | | | | | THERE WERE NO CHANGES FROM THE PREVIOUS REVIEW. PLEASE | | | ADDRESS COMMENTS BELOW. | | | | | | 1. 2020 FRC P3101.2.1 - THE ISOMETRIC DOES NOT SHOW | | | COMPLIANT VENTING METHODS. EACH BATHROOM DOES NOT SHOW | | | A VENT ANYWHERE ON THE HORIZONTAL BRANCH FOR EITHER | | | BATHROOM. THE WASHING MACHINE ALSO DOES NOT SHOW A | | | VENT. PLEASE SHOW A CODE COMPLIANT VENTING | | | CONFIGURATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-27 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-27 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2023-07-17 08:22:56 | 2ND PLUMBING REVIEW | | | | | | THERE WERE NO CHANGES FROM THE PREVIOUS REVIEW. PLEASE | | | ADDRESS COMMENTS BELOW. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - - THE RISER | | | SUBMITTED DOES NOT MATCH THE LAYOUT. THE WASHER AND | | | DOUBLE SINK (KITCHEN?) ARE NOT NEXT TO EACH OTHER AS | | | DEPICTED ON THE ISOMETRIC. | | | | | | 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SHOWS THE | | | TUB AND SHOWER DISCHARGING ABOVE (VERTICALLY) THE | | | LAVATORY WHICH IS NOT POSSIBLE. | | | | | | PLEASE SUBMIT AN ISOMETRIC THAT MATCHES THE FLOOR PLAN | | | AND MEETS CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | | | 2023-04-27 08:29:24 | 2ND PLUMBING REVIEW | | | | | | THERE WERE NO CHANGES FROM THE PREVIOUS REVIEW. PLEASE | | | ADDRESS COMMENTS BELOW. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - - THE RISER | | | SUBMITTED DOES NOT MATCH THE LAYOUT. THE WASHER AND | | | DOUBLE SINK (KITCHEN?) ARE NOT NEXT TO EACH OTHER AS | | | DEPICTED ON THE ISOMETRIC. | | | | | | 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SHOWS THE | | | TUB AND SHOWER DISCHARGING ABOVE (VERTICALLY) THE | | | LAVATORY WHICH IS NOT POSSIBLE. | | | | | | PLEASE SUBMIT AN ISOMETRIC THAT MATCHES THE FLOOR PLAN | | | AND MEETS CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-27 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-27 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2023-02-27 08:13:40 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - - THE RISER | | | SUBMITTED DOES NOT MATCH THE LAYOUT. THE WASHER AND | | | DOUBLE SINK (KITCHEN?) ARE NOT NEXT TO EACH OTHER AS | | | DEPICTED ON THE ISOMETRIC. | | | | | | 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SHOWS THE | | | TUB AND SHOWER DISCHARGING ABOVE (VERTICALLY) THE | | | LAVATORY WHICH IS NOT POSSIBLE. | | | | | | PLEASE SUBMIT AN ISOMETRIC THAT MATCHES THE FLOOR PLAN | | | AND MEETS CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-17 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-17 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-05 |
Time |
19:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-05 |
Time |
19:06 |
Sent To |
|
|
| Notes |
| 2023-06-05 19:08:05 | SIGNATURE REVIEW FOR ALL DRAWINGS SIGNED AND SEALED BY | | | RONALD W GUSTAINUS PE AND FOR SHEET SD1 SIGNED AND | | | SEALED BY GARY MCDOUGLE PE: | | | | | | 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE | | | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY | | | FBPE. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. | | | | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-06-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-27 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-06-06 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2023-06-06 16:49:09 | SEE SIGNATURE REV 3 COMMENTS AND RESUBMIT | | | THANKS |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-06 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-06 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2023-03-06 16:24:35 | ARCHITECT DIGITAL SIGNATURE FAILED | | | ENGINEER STRUCTURAL ALTERATION OK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-05-24 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-24 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-24 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2023-05-24 11:01:45 | LANDSCAPE PERMIT STILL REQUIRED, SEE PREVIOUS COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-04-03 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-04-03 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2023-04-03 11:40:21 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | THE VALUE OF THE CONSTRUCTION ($75,000.00) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($112,344.00) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE | | | PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR | | | ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO | | | CONFORMITY. | | | | | | REASON: | | | FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE | | | IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT | | | VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR | | | STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY | | | THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN | | | INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE | | | CONCLUSION OF THE PROJECT. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|