Plan Review Details - Permit 23020808
Plan Review Stops For Permit 23020808
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By cpuell Date 2023-02-23 Time 16:22 Rev Time 0.00
Received By cpuell Date 2023-02-23 Time 16:22 Sent To  
Notes
2023-02-23 16:22:34ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By rperdomo Date 2023-04-03 Time 10:53 Rev Time 0.00
Received By rperdomo Date 2023-04-03 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-08 Cont ID  
Sent By rperdomo Date 2023-03-08 Time 12:21 Rev Time 0.00
Received By rperdomo Date 2023-03-08 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By pleduc Date 2023-03-24 Time   Rev Time 0.00
Received By pleduc Date 2023-03-24 Time 15:58 Sent To  
Notes
2023-03-24 16:03:23FIRE PROVISO:
  
  
 ENSURE COMPLIANCE WITH THE REQUIRERMENTS OF NFPA 101,
 CH 7, MEANS OF EGRESS.
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By pleduc Date 2023-02-23 Time   Rev Time 0.00
Received By pleduc Date 2023-02-23 Time 12:17 Sent To  
Notes
2023-02-23 12:26:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF 360 S
 ROSEMARY # 1100; HOWEVER, THE PLAN SHEETS, IWITHIN THE
 TITLE BLOCK, INDICATE SUITE 201 AND A SEPARATE SHEET,
 SUITE 401.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE WHICH IS
 CORRECT AND MAKE CORRECTIONS AS APPLICABLE.
  
  
 1A) EACH SUITE SHOULD HAVE BE UNDER SEPARATE PERMITS,
 PLEAE REVIEW WITH THE BUILDING DEPT REQUIREMENTS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
  
  
 2) THERE IS NO INDICATION OF THE ACCESS CONTROL
 COMPLYING WITH THE REQUIRMENTS OF NFPA 101, CH 7, MEANS
 OF EGRESS.
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW, ENSURE COMPLAINCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGMENT
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-04 Cont ID  
Sent By aoliver Date 2023-04-04 Time 08:08 Rev Time 0.00
Received By aoliver Date 2023-03-24 Time 15:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-09 Cont ID  
Sent By rmcdouga Date 2023-03-09 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2023-02-22 Time 10:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-09 Cont ID  
Sent By rmcdouga Date 2023-03-09 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2023-03-09 Time 10:56 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved