| 2023-03-03 15:02:53 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23020793 |
| | 3/3/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | INDICATING THE REQUIRED AND PROVIDED NUMBER OF |
| | FIXTURES. PLEASE NOTE THAT SERVICE SINKS AND DRINKING |
| | FOUNTAINS ARE REQUIRED FIXTURES FOR THE A3 OCCUPANCY. |
| | THE PLAN DOES NOT APPEAR TO SHOW A SERVICE SINK AND |
| | ONLY ONE DRINKING FOUNTAIN IS SHOWN- NO FEWER THAN TWO |
| | SHALL BE PROVIDED- SEC. 410.3 FBC P. |
| | |
| | 2) SHEET 3: THE VENTING FOR THE FIXTURES AS SHOWN IN |
| | THE SANITARY ISOMETRIC IS NOT IN COMPLIANCE WITH THE |
| | FOLLOWING FBC P CODE SECTIONS. |
| | A) SEC. 911.1: THE COMMON VENTS FOR THE SHOWERS AND FOR |
| | THE LAVS SHALL CONNECT AT THE INTERCONNECTION OF THE |
| | FIXTURE DRAINS OR DOWNSTREAM OF THE INTERCONNECTION. |
| | B) SECS. 912.1 & 912.2.1: BATHROOM HORIZONTAL WET |
| | VENTING REQUIRES EACH WET VENTED FIXTURE DRAIN TO |
| | CONNECT INDEPENDENTLY TO THE WET VENT, AND THE REQUIRED |
| | DRY VENT FOR THE SYSTEM SHALL BE AN INDIVIDUAL OR |
| | COMMON VENT. |
| | C) SECS. 202, 910.1 & 912.1: THE URINAL REQUIRES AN |
| | INDIVIDUAL VENT. IT IS NOT INCLUDED AS A FIXTURE IN A |
| | BATHROOM GROUP AND THE FIXTURE DRAIN SHALL NOT CONNECT |
| | TO THE HORIZONTAL WET VENT. |
| | D) SECS 901.2.1, 910.1, & 912.1: NO VENTING IS SHOWN |
| | FOR THE WATER CLOSETS (WC) |
| | 2) SHEET 3: A MEANS OF LIMITING THE HOT WATER |
| | TEMPERATURE OTHER THAN THE THERMOSTAT SHALL BE PROVIDED |
| | FOR THE INSTA-HOT WATER HEATER- SEC. 607.1.1 FBC P. |
| | PLEASE PROVIDE AN ASSE APPROVED MASTER THERMOSTATIC |
| | MIXING VALVE. |
| | |
| | 3) SHEET 3: TEMPERED WATER SHALL BE DELIVERED FROM THE |
| | LAVATORIES IN COMPLIANCE WITH SEC. 419.5. PLEASE |
| | TEMPERATURE LIMITING DEVICES SUCH AS MIXING VALVES FOR |
| | TEMPERED WATER SHALL CONFORM TO ASSE 1070- SEC. |
| | 607.1.2. |
| | |
| | 4) SHEET 3: THE 1/2-INCH FIXTURE SUPPLY PIPES TO THE |
| | PUBLIC LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2 FT. |
| | LENGTHS FROM THE HOW WATER SOURCE PER TABLE C404.5.1 |
| | FBC ENERGY. PROVIDE EITHER POINT OF USE WATER HEATERS |
| | AT EACH LAVATORY OR A RECIRCULATION PUMP FOR THE HOT |
| | WATER SYSTEM. |
| | |
| | 5) SHEET 3: PROVIDE A PLUMBING FIXTURE SCHEDULE AND |
| | EQUIPMENT SCHEDULE FOR THE WATER HEATER- SEC 502.1 FBC |
| | P, AND TABLE C404.2 FBC ENERGY. |
| | |
| | 6) SHEET 1: REFER TO SECS. 213.3.1 & 604.8.1.6 AND |
| | PROVIDE ACCESSIBLE LAVATORIES IN EACH OF THE ACCESSIBLE |
| | MEN"S AND WOMEN'S TOILET COMPARTMENTS. |
| | |
| | 7) SHEET 1: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS |
| | PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | C) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| | D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 8) SHEET 1: THE ACCESSIBLE SHOWERS DO NOT APPEAR TO BE |
| | DESIGNED AS EITHER TRANSFER OR ROLL-IN TYPE SHOWERS AS |
| | REQUIRED PER SECS 608- 610 FBC ACC. TRANSFER TYPE UNITS |
| | SHALL BE 36X36 INCHES ( NO MORE AND NO LESS) AND ROLL |
| | IN TYPES SHALL BE 30-INCHES WIDE MINIMUM BY 60-INCHES |
| | DEEP MINIMUM. THE SHOWERS WOULD MEET COMPLIANCE AS |
| | ROLL-IN TYPES IF THEY HAD MINIMUM 60-INCHES WIDE |
| | ENTRIES ON THEIR FACES, HOWEVER THE DRAWINGS SHOW |
| | 36-INCH ENTRIES. OTHER DETAILS REQUIRED PER FBC ACC: |
| | A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.2 |
| | B) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.2. |
| | |
| | 9) SHEET 1: MISSING ACCESSIBLE DRINKING FOUNTAIN |
| | DETAILS PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2 |
| | B) KNEE AND TOE CLEARANCES- SECS. 602.2 & 306. |
| | C) SPOUT HEIGHTS- SEC. 602.4 & 602.7. |
| | D) THE FOUNTAINS SHALL NOT PROTRUDE INTO THE |
| | CIRCULATION SPACE GREATER THAN 4-INCHES- SEC. 307 FBC |
| | ACC. BECAUSE THERE IS NO PLUMBING FIXTURE SCHEDULE IT |
| | IS NOT KNOW IF THE FOUNTAINS WILL HAVE CANE SWEEP |
| | APRONS. IF THEY DO NOT, THEN THEY MUST BE RECESSED IN A |
| | NICHE OR GUARDED ON EACH SIDE IN SOME MANNER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |