Plan Review Details - Permit 23020793
Plan Review Stops For Permit 23020793
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By lbond Date 2023-03-02 Time 07:57 Rev Time 0.00
Received By lbond Date 2023-03-02 Time 07:57 Sent To  
Notes
2023-03-02 08:01:14BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23020793
  
 REVIEWED: MARCH 2, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS REVIEW:
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By lbond Date 2023-03-02 Time 08:56 Rev Time 0.00
Received By lbond Date 2023-03-02 Time 08:56 Sent To  
Notes
2023-03-02 08:57:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23010785
  
 REVIEWED: MARCH 2, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
  
 COMMENTS:
  
 1) REVIEW WATER COOLER ACCORDING TO F.B.C ACCESSIBILITY
 602
 2) PROVIDE ONE MIRROR LOCATION FOR ACCESSIBLE SINK
 ACCORDING TO F.B.C ACCESSIBILITY 603.3
 3) PROVIDE ONE ACCESSIBLE SINK PER BATHROOM ACCORDING
 TO F.B.C ACCESSIBILITY 606.1
 4) PROVIDE ROLL IN ACCESSIBLE SHOWER WITH SEAT WALL AND
 GRAB BAR ACCORDING TO F.B.C ACCESSIBILITY 602
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By mpeterso Date 2023-03-14 Time 15:04 Rev Time 0.00
Received By mpeterso Date 2023-03-14 Time 14:30 Sent To  
Notes
2023-03-14 15:14:26ELECTRIC REVIEW FAILED
 1) THE ELECTRIC LOAD CALCULATION PROVIDED IS FOR A
 DWELLING. THE SPACE PROPOSED IS A COMMERCIAL SPACE.
 PLEASE PROVIDE THE APPLICABLE ELECTRIC LOAD CALCULATION
 IN ACCORDANCE WITH NEC ARTICLE 220
 2) THE ELECTRIC RISER PROVIDED DETAILS 2/0 CONDUCTORS
 WITH AN AMPACITY OF175 AMPS AND ONLY ALLOWED A 175 AMP
 OVERCURRENT DEVICE. . PLEASE PROVIDE CONDUCTORS WITH
 AMPACITY ADEQUATE FOR A 200 AMP COMMERCIAL ELECTRIC
 SERVICE AS SHOWN.NEC 310.15
 3) PLEASE DETAIL NEW WIRING PROVIDED FOR NEW AIR
 CONDITIONING 3. IN ADDITION, ENSURE TO INCLUDE THIS
 LOAD IN THE CORRECTED LOAD CALCULATION. FBC 107.2 AND
 NEC 220
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-01 Cont ID  
Sent By pleduc Date 2023-03-01 Time   Rev Time 0.00
Received By pleduc Date 2023-03-01 Time 13:02 Sent To  
Notes
2023-03-01 13:24:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF 2 EXITS; HOWEVER, THERE
 APPEARS TO BE SLIDING DOOR TYPES INBETWEEN THE TWO
 AREAS.
  
 THESE SLIDING DOORS HAVE NO INDICATORS THAT THE COMPLY
 WITH THE EXIT DOOR REQUIRMENTS OF NFPA 101, CH 12, NEW
 ASSEMBLY & CH 7, MEANS OF EGRESS.
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
 1A) THE 2 EXITS DOOR DO NOT INDICATE THE EXIT HARDWARE
 & LOCKS/LATCHES AS REQUIRED AND NOTED ABOVE AND:
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
 2) THERE IS NO INDICATION OF THE FLOOR FINISH THAT
 MEETS THE REQUIREMENTS OF NFPA 101,
  
 12.3.3.5 INTERIOR FLOOR FINISH.
 12.3.3.5.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 12.3.3.5.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS COR RIDORS AND IN SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH
 12.3.6 SHALL BE NOT LESS THAN CLASS II.
 12.3.3.5.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR 10.2.7.2,
 AS APPLICABLE
  
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
 3) THERE IS NO INDICATION OF THE CEILING & WALL FINISH
 THAT MEETS THE REQUIREMENTS OF NFPA 101,
  
 12.3.3 INTERIOR FINISH.
 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2
  
 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING
 FINISH MATERIALS
 COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B
 IN GENERAL
 ASSEMBLY AREAS HAVING OCCUPANT LOADS OF MORE THAN 300
 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANT LOADS
 OF 300 OR FEWER
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-14 Cont ID  
Sent By mpeterso Date 2023-03-14 Time 15:14 Rev Time 0.00
Received By mpeterso Date 2023-02-28 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By medwards Date 2023-03-07 Time 07:50 Rev Time 0.00
Received By medwards Date 2023-03-07 Time 07:50 Sent To  
Notes
2023-03-07 07:50:491ST REVIEW FMC
 PERMIT: 23020793
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS ADDRESS IS A RETAIL STORE, THIS YOGA STUDIO
 WILL BE CHANGING THE USE FROM RETAIL TO BUSINESS.
 PROVIDE A CHANGE OF USE APPLICATION FOR THIS BUILDING.
  
 2) THE NEW AHU-3 INFORMATION PACKET IS SHOWING ON PAGE
 11 OF 13 THAT THE UNIT CHOSEN DOES NOT HAVE A HEATER
 INSTALLED. THE ENERGY CALCULATIONS FOR THIS AHU-3 IS
 SIZED FOR A TOTAL BTU LOAD OF HEAT REQUIRED AS 16,478.
 PLEASE SHOW THE REQUIRED HEAT FOR THIS UNIT. FEC
 C403.2.1
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION OF EACH SPACE AND THE
 CORRESPONDING OCCUPANCY DENSITY FROM THAT MOST
 RESEMBLING THE USE OF SPACE FROM FMC TABLE 403.3.1.1
 AND NOT THE ARCHITECTS EGRESS COUNT. FMC 403.3.1.1.
  
 4) SHOW THE LOCATIONS OF THE OUTDOOR AIR INTAKE
 OPENINGS. FMC 401.4
  
 5) THE MECHANICAL DRAWING MUST SHOW ALL THE DOORS IN
 THE SPACE AND WINDOWS AND ENTRANCE AND EXIT DOORS. FBC
 107.3.5
  
 6) PROVIDE THE SUPPLY CFM???S OF EACH AHU AND SHOW THE
 REQUIRED SMOKE DETECTORS AT THE SUPPLY SIDE OF EACH
 UNIT. FMC 606.1
  
 7) PROVIDE A ROOF DRAWING SHOWING THE LOCATION OF THE
 NEW AHU-3 CONDENSING UNIT AND THAT THE LOCATION WILL
 MEET THE GUARD REQUIREMENTS OF FMC 304.11
  
 8) SHOW THE CONDENSATE DISPOSAL LOCATIONS ON THE
 DRAWING. FMC 307.2.1
  
 9) THE BATH EXHAUST FANS TERMINATION MUST ALSO INCLUDE
 A SCREEN. FMC 501.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By ccole Date 2023-03-03 Time 15:00 Rev Time 0.00
Received By ccole Date 2023-03-03 Time 12:20 Sent To  
Notes
2023-03-03 15:02:531ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23020793
 3/3/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES. PLEASE NOTE THAT SERVICE SINKS AND DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES FOR THE A3 OCCUPANCY.
 THE PLAN DOES NOT APPEAR TO SHOW A SERVICE SINK AND
 ONLY ONE DRINKING FOUNTAIN IS SHOWN- NO FEWER THAN TWO
 SHALL BE PROVIDED- SEC. 410.3 FBC P.
  
 2) SHEET 3: THE VENTING FOR THE FIXTURES AS SHOWN IN
 THE SANITARY ISOMETRIC IS NOT IN COMPLIANCE WITH THE
 FOLLOWING FBC P CODE SECTIONS.
 A) SEC. 911.1: THE COMMON VENTS FOR THE SHOWERS AND FOR
 THE LAVS SHALL CONNECT AT THE INTERCONNECTION OF THE
 FIXTURE DRAINS OR DOWNSTREAM OF THE INTERCONNECTION.
 B) SECS. 912.1 & 912.2.1: BATHROOM HORIZONTAL WET
 VENTING REQUIRES EACH WET VENTED FIXTURE DRAIN TO
 CONNECT INDEPENDENTLY TO THE WET VENT, AND THE REQUIRED
 DRY VENT FOR THE SYSTEM SHALL BE AN INDIVIDUAL OR
 COMMON VENT.
 C) SECS. 202, 910.1 & 912.1: THE URINAL REQUIRES AN
 INDIVIDUAL VENT. IT IS NOT INCLUDED AS A FIXTURE IN A
 BATHROOM GROUP AND THE FIXTURE DRAIN SHALL NOT CONNECT
 TO THE HORIZONTAL WET VENT.
 D) SECS 901.2.1, 910.1, & 912.1: NO VENTING IS SHOWN
 FOR THE WATER CLOSETS (WC)
 2) SHEET 3: A MEANS OF LIMITING THE HOT WATER
 TEMPERATURE OTHER THAN THE THERMOSTAT SHALL BE PROVIDED
 FOR THE INSTA-HOT WATER HEATER- SEC. 607.1.1 FBC P.
 PLEASE PROVIDE AN ASSE APPROVED MASTER THERMOSTATIC
 MIXING VALVE.
  
 3) SHEET 3: TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORIES IN COMPLIANCE WITH SEC. 419.5. PLEASE
 TEMPERATURE LIMITING DEVICES SUCH AS MIXING VALVES FOR
 TEMPERED WATER SHALL CONFORM TO ASSE 1070- SEC.
 607.1.2.
  
 4) SHEET 3: THE 1/2-INCH FIXTURE SUPPLY PIPES TO THE
 PUBLIC LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2 FT.
 LENGTHS FROM THE HOW WATER SOURCE PER TABLE C404.5.1
 FBC ENERGY. PROVIDE EITHER POINT OF USE WATER HEATERS
 AT EACH LAVATORY OR A RECIRCULATION PUMP FOR THE HOT
 WATER SYSTEM.
  
 5) SHEET 3: PROVIDE A PLUMBING FIXTURE SCHEDULE AND
 EQUIPMENT SCHEDULE FOR THE WATER HEATER- SEC 502.1 FBC
 P, AND TABLE C404.2 FBC ENERGY.
  
 6) SHEET 1: REFER TO SECS. 213.3.1 & 604.8.1.6 AND
 PROVIDE ACCESSIBLE LAVATORIES IN EACH OF THE ACCESSIBLE
 MEN"S AND WOMEN'S TOILET COMPARTMENTS.
  
 7) SHEET 1: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 C) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
 D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 8) SHEET 1: THE ACCESSIBLE SHOWERS DO NOT APPEAR TO BE
 DESIGNED AS EITHER TRANSFER OR ROLL-IN TYPE SHOWERS AS
 REQUIRED PER SECS 608- 610 FBC ACC. TRANSFER TYPE UNITS
 SHALL BE 36X36 INCHES ( NO MORE AND NO LESS) AND ROLL
 IN TYPES SHALL BE 30-INCHES WIDE MINIMUM BY 60-INCHES
 DEEP MINIMUM. THE SHOWERS WOULD MEET COMPLIANCE AS
 ROLL-IN TYPES IF THEY HAD MINIMUM 60-INCHES WIDE
 ENTRIES ON THEIR FACES, HOWEVER THE DRAWINGS SHOW
 36-INCH ENTRIES. OTHER DETAILS REQUIRED PER FBC ACC:
 A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.2
 B) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2.
  
 9) SHEET 1: MISSING ACCESSIBLE DRINKING FOUNTAIN
 DETAILS PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2
 B) KNEE AND TOE CLEARANCES- SECS. 602.2 & 306.
 C) SPOUT HEIGHTS- SEC. 602.4 & 602.7.
 D) THE FOUNTAINS SHALL NOT PROTRUDE INTO THE
 CIRCULATION SPACE GREATER THAN 4-INCHES- SEC. 307 FBC
 ACC. BECAUSE THERE IS NO PLUMBING FIXTURE SCHEDULE IT
 IS NOT KNOW IF THE FOUNTAINS WILL HAVE CANE SWEEP
 APRONS. IF THEY DO NOT, THEN THEY MUST BE RECESSED IN A
 NICHE OR GUARDED ON EACH SIDE IN SOME MANNER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-01 Cont ID  
Sent By lbond Date 2023-03-01 Time 16:41 Rev Time 0.00
Received By lbond Date 2023-03-01 Time 16:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-07 Cont ID  
Sent By VBroglia Date 2023-03-07 Time 09:57 Rev Time 0.00
Received By vbroglia Date 2023-03-07 Time 09:57 Sent To  
Notes
***NONE***