| Plan Review Stops For Permit 23020702 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-10 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-10 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-23 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-23 |
Time |
08:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-04-13 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-04-13 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
jcooley |
Date |
2023-03-23 |
Time |
19:22 |
Rev Time |
0.00 |
| Received By |
jcooley |
Date |
2023-03-23 |
Time |
07:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-17 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-07 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-06 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-22 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-10 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-10 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-27 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-27 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2023-03-27 13:45:42 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23020702 | | | 3/27/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS PL-1, PL-2 & PL-3: THE PLANS HAVE CONFLICTING | | | INFORMATION PER THE ITEMS LISTED BELOW- SEC. 107.2.1 | | | WPB. | | | | | | A) PL-1 & PL-2 SPECIFY A 10,000 GALLON POOL HOWEVER THE | | | FLOW RATE AND TDH CALCULATIONS ON PL-3 ARE BASED ON | | | 4,680 GALLONS. | | | | | | B) PL-2 & PL-3: THE POOL PIPING DIAGRAM ON PL-2 DOES | | | NOT MATCH THE POOL PIPING SCHEMATIC ON PL-3. IT APPEARS | | | THE DIAGRAM IS A COPY AND PASTE DETAIL. PLEASE REVISE | | | IT OR REMOVE IT. | | | | | | C) PL-2 & PL-3: A 2HP SPA PUMP IS SPECIFIED ON PL-2. | | | A1.65 HP SPA AND POOL PUMP IS SPECIFIED ON P-3. | | | | | | D) PL-1, PL-2 & PL-3: A CHANNEL DRAIN IS SHOWN IN THE | | | SPA ON PL-1 & PL-2, HOWEVER THE PL-3 PIPING SCHEMATIC | | | SHOWS TWO INDIVIDUAL ROUND DRAINS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2023-04-06 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2023-04-06 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2023-04-06 10:10:43 | PRIVATE PROVIDER INSPECTIONS ONLY APPROVED | | | PP DOCUMENTTS UNDER 21100614 | | | RICHARD GATHRIGHT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-10 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-10 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-03-23 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-23 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-23 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2023-03-23 08:23:44 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23020702 | | | | | | REVIEWED: MARCH 23, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) THE PLANS SHEETS FOR THE PROJECT ARE NOT DIGITALLY | | | SIGNED BY THE ARCHITECT OF RECORD AS REQUIRED BY FL. | | | STATUTE AND SEC.: 61G1-16.005 FLORIDA ADMINISTRATIVE | | | CODE. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR | | | DIGITAL SIGNATURES AND SEALS CAPABLE OF BEING VERIFIED. | | | THE PLANS SUBMITTED FOR REVIEW ARE COPIES OF A SIGNED | | | AND SEALED PAPER PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-17 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-17 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-03-27 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-03-27 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2023-03-27 16:23:32 | 3/27/2023 FAIELD | | | | | | 1. POOL EQUPIMENT NEEDS TO SHOW SETBACKS, PER THE | | | ZONING CODE MECHANICAL EQUIPMENT CANNOT ENCORCH 4 FEET | | | INTO A REQUIRED SETBACK | | | | | | 2. PLEASE SHOW THE POOL SETBACKS FROM WATER'S EDGE TO | | | THE PROPERTY LINE | | | | | | 3. PLEASE SHOW THE SETBACKS OF THE DECKING- A MIN OF 2 | | | FEET IS REQUIRED | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | PLANNER | | | [email protected] | | | |
|
|