Plan Review Details - Permit 23020662
Plan Review Stops For Permit 23020662
Review Stop AFFIDAVIT PRIVATE PROVIDER AFFIDAVIT
Rev No 1 Status P Date 2023-03-28 Cont ID  
Sent By ccole Date 2023-03-28 Time 11:41 Rev Time 0.00
Received By ccole Date 2023-03-28 Time 11:41 Sent To  
Notes
2023-03-21 15:38:10 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-03 Cont ID  
Sent By rmcdouga Date 2023-04-03 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2023-04-03 Time 13:57 Sent To  
Notes
2023-04-03 14:09:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO
 PAD ANCHORING DETAILS. PROVIDE THE WINDLOAD DATA ON THE
 GENERATOR PAD DRAWINGS. IF A PREFABRICATED GENERATOR
 PAD WILL BE USED, SUBMIT SIGNED AND SEALED SITE
 SPECIFIC ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-31 Cont ID  
Sent By mpeterso Date 2023-03-31 Time 08:02 Rev Time 0.00
Received By mpeterso Date 2023-03-31 Time 07:42 Sent To  
Notes
2023-03-31 08:03:08AUDIT OF ELECTRICAL PLANS PASSED. MP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-03 Cont ID  
Sent By rmcdouga Date 2023-04-03 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2023-03-31 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-31 Cont ID  
Sent By aoliver Date 2023-03-31 Time 10:36 Rev Time 0.00
Received By aoliver Date 2023-03-17 Time 10:36 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2023-03-21 Time   Rev Time 0.00
Received By   Date 2023-03-21 Time   Sent To  
Notes
2023-03-21 15:39:25NTBO, INITIAL DOCS WITH MASTER
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-03 Cont ID  
Sent By rmcdouga Date 2023-04-03 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2023-04-03 Time 13:58 Sent To  
Notes
2023-04-03 14:03:59THE DESIGN PROFESSIONAL'S DIGITAL SIGNATURES ON THE
 DRAWINGS CAN NOT BE CERTIFIED. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC 61G1
 OR FS 471 & FAC 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-27 Cont ID  
Sent By VBroglia Date 2023-03-27 Time 15:32 Rev Time 0.00
Received By vbroglia Date 2023-03-27 Time 15:32 Sent To  
Notes
***NONE***