| Plan Review Stops For Permit 23020604 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-13 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-13 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-02 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-02 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2023-03-02 10:16:08 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23020604 | | | | | | REVIEWED: MARCH 2, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENT: | | | | | | ASBESTOS REVIEW: | | | | | | FAILED PLAN REVIEW: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-02 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-02 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-08 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-08 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2023-03-08 16:31:59 | NO ELECTRIC WORK SHOWN, REVIEWED OR APPROVED. MP |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-02 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2023-03-02 10:49:39 | FIRE PROVISO: | | | | | | ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS | | | ARE MAINTAINED & REPAIRED IF DAMAGED. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-21 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-10 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-08 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-01 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-07 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-07 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2023-03-07 09:15:01 | NO MECHANICAL SHOWN IN THE SCOPE OF THIS PROJECT. ME |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-21 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-21 |
Time |
16:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-13 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-13 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2023-03-13 09:05:44 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 23020604 | | | 3/13/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | FAIR HOUSING DESIGN ACT MANUAL- FHDA | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE FAIR HOUSING DESIGN ACT AFFIDAVIT IS NOT | | | APPROVED BECAUSE THE LISTED DESIGNER- RAYMOND DIBBLE- | | | WHOSE PRINTED AND SIGNATURE IS ON THE DOCUMENT, IS NOT | | | THE DESIGNER OF THE PROJECT. SHEET A-1 BEARS THE | | | PRINTED NAME AND SIGNATURE OF THE GENERAL CONTRACOR | | | REMON RUDGE. GENERAL CONTRACTORS IN ACCORDANCE WITH FL. | | | STATUTE 489.113 ARE PERMITTED TO DRAW THE REMODELING | | | PLANS. THE OWNER OR ANY OTHER UNLICENSED SHALL NOT | | | PREPARE THE DESIGN AND SHALL NOT BE LISTED AS THE | | | DESIGNER ON THE AFFIDAVIT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-06 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-06 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2023-03-06 11:19:06 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23020604 | | | 3/6/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | FAIR HOUSING DESIGN ACT MANUAL- FHDA | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS A1 & P1- FAIR HOUSING ACT COMPLIANCE: THE | | | PRADO CONDOMINIUMS- 600 S. DIXIE HWY. ARE SUBJECT TO | | | COMPLIANCE WITH FAIR HOUSING ACCESSIBILITY GUIDELINES | | | WHICH CAME INTO EFFECT FOR MULTIFAMILY HOUSING BUILT | | | FOR FIRST OCCUPANCY AFTER MARCH 13, 1991. | | | A) REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL AND | | | SHOW A 30X48-INCH CLEAR FLOOR SPACE DIAGRAM POSITIONED | | | PARALLEL TO THE NEW SHOWER AND FLUSH WITH THE NEW | | | FAUCET CONTROL WALL. | | | | | | B) REFER TO PAGES 6.12 & 6.13 OF THE FDHA MANUAL AND | | | PROVIDE AN ELEVATION DETAIL FOR THE SHOWER THAT SHOWS | | | THE LOCATIONS OF REQUIRED GRAB BAR REINFORCEMENTS. | | | | | | PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE | | | GUIDELINES FOR THE BATHROOM ALTERATIONS, THE OWNER AND | | | DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE | | | A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE | | | ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET | | | THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY | | | GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO | | | REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF | | | REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, | | | PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A | | | COPY OF THE FAIR HOUSING AFFIDAVIT. | | | | | | 2) P1 & P2: THE PRINTED NAME OF THE FL. LICENSED | | | CONTRACTOR SHALL BE ON THE PLUMBING PLANS- SEC. 107.2.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-02 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-02 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|