Plan Review Details - Permit 23020586
Plan Review Stops For Permit 23020586
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-02-18 Cont ID  
Sent By cpuell Date 2023-02-18 Time 08:15 Rev Time 0.00
Received By cpuell Date 2023-02-18 Time 08:15 Sent To  
Notes
2023-02-18 08:15:16ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By jgomez Date 2023-03-13 Time 13:29 Rev Time 0.00
Received By jgomez Date 2023-03-10 Time 18:42 Sent To  
Notes
2023-03-13 13:29:29RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020586
 935 CHARLES ST
  
 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE:12.1 FEET BASED ON NAVD
 1988. CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO
 (2) FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION
 (SEC. 18-284 CITY ORDINANCE NO. 4729-17). THEREFORE,
 THE REQUIRED FINISH FLOOR ELEVATION IS 14.1 FEET MIN.
 NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY THE PROPOSED
 FINISHED ELEVATION IN ALL ROOMS IN ALL FLOOR PLANS.
 ALSO, DESIGNER OF RECORD NEEDS TO SPECIFY THE FINISH
 ELEVATION ALL THE EQUIPMENT SERVING THE BUILDING. SEE
 SURVEY FOR EXISTING GRADE ELEVATIONS.
  
 DURING THE PERMITTING/CONSTRUCTION OF THIS STRUCTURE
 THREE DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED (SEC. 107.3.5.1.1 CITY AMENDMENTS):
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 NOTE:
 NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE NOW FOR REVIEW.
  
 2- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY THE
 OWNER/AGENT AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 4- NEED INFORMATION TO SHOW COMPLIANCE WITH BEDROOM #2
 EGRESS WINDOW.
 CLEARLY SPECIFY SIZE OF CASEMENT WINDOW AND PROVIDE
 MANUFACTURER'S SPECS SHOWING THAT SPECIFIED SIZE MEETS
 ALL THE EGRESS REQUIREMENTS.
 NOTE: COORDINATE WITH SIZE OF WINDOW OPENINGS SHOWN ON
 THE SECOND FLOOR PLAN.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 5- BASED ON TABLE R301.2(2) FBC-RESIDENTIAL AND HEIGHT
 AND EXPOSURE ADJUSTMENT TABLE R301.2(3) FBC-RESIDENTIAL
 THE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-2 AND A-4 ARE TOO LOW. REVISE DESIGN PRESSURES AS
 REQUIRED BASED ON OPENING ZONE LOCATION (4 OR 5) AND
 BUILDING MEAN ROOF HEIGHT. (I USED 30 FEET MEAN ROOF
 HEIGHT FROM THE TABLE FOR REFERENCE). REVISE DESIGN
 PRESSURES ON SHEET A-2 AND A-4 AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 6- SECOND FLOOR FRAMING PLAN DOESN'T SPECIFY TRUSS SIZE
 AND SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY TRUSS
 TOP CHORD LIVE AND DEAD LOADS AND BOTTOM CHORD LIVE AND
 DEAD LOADS. R301.1 FBC-RESIDENTIAL.
 NOTE: INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 FBC-RESIDENTIAL.
  
 9- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 10- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1
 FBC-RESIDENTIAL.
  
 11- GUARDRAILS: DESIGNER OF RECORD TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY GUARDRAILS AS REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 12- STAIR SECTION: PROVIDE DETAILS/SPECIFICATIONS FOR
 STAIRWAY FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 14- ROOFING UNDERLAYMENT: PROVIDE SPECIFICATIONS
 SHOWING HOW COMPLYING WITH THE NEW 2020 CODE
 REQUIREMENT FOR ROOFING UNDERLAYMENT. SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 CLARIFY TYPICAL ROOF NOTE ON SHEET A-4. SPECIFY CORRECT
 ROOFING UNDERLYAMENT BASED ON PROPOSED ROOFING
 MATERIAL.
  
 15- ROOF SHEATHING: PLYWOOD SHEATHING NAILING SCHEDULE:
 REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY
 WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE
 TYPE, SIZE AND SPACING. NOTE: NEED TO USE RING SHANK
 NAILS. ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: ALSO, REVISE INFORMATION SPECIFIED ON SHEET S-4
 TO MATCH. REVISE DIAPHRAGM SCHEDULE TABLE, FASTENER
 SCHEDULE TABLE AND ROOF SHEATHING DIAGRAM TO MATCH.
 COORDINATE WITH ABOVE REQUIREMENT.
  
 16- PROVIDE DETAIL/SPECS FOR STEEL COLUMNS CONNECTION
 TO TRUSS GIRDER THAT MATCHES PROPOSED INSTALLATION.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 17- PROPOSED ROOF FINISH IS NOT CLEAR. ARCHITECT
 SPECIFIES ROOF TILE BUT PRODUCT APPROVAL SUBMITTED IS
 FOR METAL PANELS. REVISE AS REQUIRED TO MATCH. ALSO,
 ARCHITECT SPECIFIES NON VENTED ATTIC BUT RIDGE VENT
 PRODUCT APPROVAL WAS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 18- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 19-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
  
 A)ENTRY DOOR.
 B)GARAGE EXTERIOR SWING DOORS.
 C)GARAGE OVERHEAD DOOR. SEE SIZES ON PLANS.
 D)CASEMENT WINDOWS.
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 F)ROOF FINISH. NOTE: COORDINATE WITH ITEM #17 ABOVE.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. COORDINATE
 WITH ITEM #17 ABOVE.
 H)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 I)ROOF VENTS IF SPECIFIED BY THE ARCHITECT. SEE PLANS.
 J)RIDGE ROOF VENT SPECIFIED BY THE ARCHITECT. SEE
 PLANS.
 K) HIP & RIDGE METAL SUPPORT TO BE USED IF TILE
 SPECIFIED ON PLANS.
 L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS.
 M) ROOF TILE (IF SPECIFIED BY ARCHITECT AND CLEARLY
 MARK ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 20- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PRODUCT APPROVALS LISTED ON SHEET A-4 DON'T MATCH
 PRODUCT APPROVALS SUBMITTED. REVISE/COORDINATE AS
 REQUIRED TO MATCH PRODUCT APPROVALS SUBMITTED.
  
 21- -STRUCTURAL LEDGER SPECIFICATIONS SHOWN ON THE
 TYPICAL WALL SECTION ON SHEET A-4 AND SPECIFICATIONS
 SHOWN ON THE LEDGER TABLE ON SHEET S-2 DON'T MATCH.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 22- RESIDENTIAL GARAGE FIRE SEPARATION: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR DWELLING-
 GARAGE FIRE SEPARATION AS REQUIRED BY SEC. R302.6
 FBC-RESIDENTIAL AND TABLE R302.6 FBC-RESIDENTIAL.
  
 23- PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS INSTALLATION. SPECIFY FASTENING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 24- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $323936.00. OWES
 $3543.93.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By rperdomo Date 2023-03-06 Time 11:02 Rev Time 0.00
Received By rperdomo Date 2023-03-06 Time 09:26 Sent To  
Notes
2023-03-06 11:01:24FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
 (FOR EXAMPLE: STAIRWAY)
  
 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN
 SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By jgomez Date 2023-03-13 Time 13:33 Rev Time 0.00
Received By jgomez Date 2023-02-17 Time 11:23 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By jgomez Date 2023-03-13 Time 13:32 Rev Time 0.00
Received By jgomez Date 2023-03-13 Time 13:32 Sent To  
Notes
2023-03-13 13:33:26IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 08:29 Rev Time 0.00
Received By medwards Date 2023-02-24 Time 08:29 Sent To  
Notes
2023-02-24 08:29:231ST REVIEW FMC
 PERMIT: 23020586
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC R402
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By jgomez Date 2023-03-13 Time 13:30 Rev Time 0.00
Received By jgomez Date 2023-03-13 Time 13:30 Sent To  
Notes
2023-03-13 13:31:13FLOOD ZONE AE. NFIP REVIEW:
  
 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE:12.1 FEET BASED ON NAVD
 1988. CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO
 (2) FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION
 (SEC. 18-284 CITY ORDINANCE NO. 4729-17). THEREFORE,
 THE REQUIRED FINISH FLOOR ELEVATION IS 14.1 FEET MIN.
 NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY THE PROPOSED
 FINISHED ELEVATION IN ALL ROOMS IN ALL FLOOR PLANS.
 ALSO, DESIGNER OF RECORD NEEDS TO SPECIFY THE FINISH
 ELEVATION ALL THE EQUIPMENT SERVING THE BUILDING. SEE
 SURVEY FOR EXISTING GRADE ELEVATIONS.
  
 DURING THE PERMITTING/CONSTRUCTION OF THIS STRUCTURE
 THREE DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED (SEC. 107.3.5.1.1 CITY AMENDMENTS):
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 NOTE:
 NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE NOW FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By rwbrown Date 2023-02-21 Time 11:44 Rev Time 0.00
Received By rwbrown Date 2023-02-21 Time 11:43 Sent To  
Notes
2023-02-21 11:45:411ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.2.1 - BOTH BATHROOMS HAVE 2 TRAPPED
 FIXTURES UPSTREAM OF THE VENTED FIXTURES CONNECTION.
 ONLY ONE TRAPPED FIXTURE IS ALLOWED UPSTREAM OF THE
 VENTED FIXTURE'S CONNECTION TO THE HORIZONTALL WET
 VENTED BRANCH.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By jgomez Date 2023-03-13 Time 13:31 Rev Time 0.00
Received By jgomez Date 2023-03-13 Time 13:31 Sent To  
Notes
2023-03-13 13:32:25ROOFING REVIEW:
 SEE BUILDING REVIEW COMMENTS REGARDING PRODUCT
 APPROVALS. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 08:31 Rev Time 0.00
Received By medwards Date 2023-02-24 Time 08:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By VBroglia Date 2023-03-06 Time 14:34 Rev Time 0.00
Received By vbroglia Date 2023-03-06 Time 14:33 Sent To  
Notes
2023-03-06 14:34:313/6/2023 FAILED
  
 ALL NEW CONSTRUCTION REQUIRES A LANDSCAPE PERMIT IN THE
 SYSTEM, PLEASE APPLY FOR A LANDSCAPE PERMIT.
  
 PLEASE NOTE, NO PLANS NEED TO BE SUBMITTED AT THIS
 TIME, BUT A LANDSCAPE PERMIT NUMBER NEEDS TO BE
 OBTAINED
  
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  