Plan Review Details - Permit 23020537
Plan Review Stops For Permit 23020537
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By jwitmer Date 2023-03-21 Time 13:06 Rev Time  
Received By jwitmer Date 2023-03-21 Time 12:56 Sent To  
Notes
2023-03-21 13:05:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23020537
 ADD: 2414 FLORIDA AVE.
 CONT: THE CURY GROUP
 TEL: 561-533-8888 EX 500
 E-MAIL:
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 21ST/ 2023
 ACTION: DENIED
  
 1) 2020 W. P. B. ADMINISTRATIVE CODE107.3.5 MINIMUM
 PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 SURVEY / SITE PLAN
  
 2) 2020 FBC-B SECTION 3105.3.4.1. MATERIALS. WHEN
 FABRIC IS USED TO COVER AWNINGS OR FABRIC OVER COVERED
 FRAMES SHALL MEET THE FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM
 E-84 OR UL 723.
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-27 Cont ID  
Sent By pleduc Date 2023-04-27 Time   Rev Time 0.00
Received By pleduc Date 2023-04-27 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By pleduc Date 2023-02-23 Time   Rev Time 0.00
Received By pleduc Date 2023-02-23 Time 13:12 Sent To  
Notes
2023-02-23 13:18:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE HAS NO OBJECTIONS TO THE FRAMING DETAILS HOWEVER,
 ADDITIONAL INFO IS NEEDED FOR THE FINAL INSTALL.
  
 1) THERE IS AN INDICATION OF THE CANOPY COVER MATERILA
 AND/OR A FLAME RATING CERTIFICATE.
  
 25.2.2 FLAME PROPAGATION PERFORMANCE.
 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME
 PROPAGATION
 PERFORMANCE CRITERIA CONTAINED IN TEST METHOD 2 OF NFPA
 701,
 STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF
 TEXTILES
 AND FILMS. [101: 11.11.2.1]
 25.2.2.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE TENT
 FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER
 EVIDENCE OF
 ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ.
 (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY
 OTHER
 INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO
 THE
 AHJ. [101: 11.11.2.2]
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE DETAILS.
  
  
  
 2) THERE IS NO SITE PLAN INDICATING THE PROPOSED
 LOCATION OF THE CANOPY.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-05-12 Cont ID  
Sent By amhamilt Date 2023-05-12 Time 16:08 Rev Time 0.00
Received By amhamilt Date 2023-05-12 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-22 Cont ID  
Sent By asangele Date 2023-05-22 Time 10:51 Rev Time 0.00
Received By asangele Date 2023-05-22 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-03-21 Time   Rev Time 0.00
Received By amcgrego Date 2023-02-22 Time 13:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 12:48 Sent To  
Notes
2023-05-09 13:29:13AWNING ROOF COVER:
 CARLISLE SURE WELD TPO ROOF COVERING
 COMBUSTIBLE: CLASS A
 INCREASED FASTENING ON TARGET ENGINEERING, INC.
 NOA # 16-0413.02
 P1= -62.28
 P2= -74.84
 P3= 129.60

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 13:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-21 Cont ID  
Sent By jwitmer Date 2023-03-21 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2023-03-21 Time 13:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-22 Cont ID  
Sent By asangele Date 2023-05-22 Time 10:51 Rev Time 0.00
Received By asangele Date 2023-05-22 Time 10:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-02-28 Cont ID  
Sent By ASangele Date 2023-02-28 Time 10:49 Rev Time 0.00
Received By asangele Date 2023-02-28 Time 10:49 Sent To  
Notes
2023-02-28 10:50:542/28/2023
 FAILED
  
 PLEASE PROVIDE A SURVEY AND SITE PLAN AND SHOW WHERE
 THE CANOPY WILL BE LOCATED AND LABEL THE SETBACKS OF
 THE CANOPY.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]