| 2023-04-20 13:09:23 | RESIDENTIAL(R3) THIRD BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23020491 | | | 324 SUMMA ST | | | | | | | | | ORIGINAL COMMENT: | | | 3- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE | | | DIGITAL SIGNATURE. | | | | | | PREVIOUS COMMENT: | | | ENGINEER'S DRAWINGS SUBMITTED HAVE A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE | | | NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A | | | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE | | | DIGITAL SIGNATURE OF THE ENGINEER AS REQUIRED BY SEC. | | | 61G15-23.004 FAC AND CHAPTER 471 F.S. | | | | | | ALSO, ENGINEER'S DIGITAL SIGNATURE DOESN'T SEEM TO | | | COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. IT | | | DOESN'T HAVE THE REQUIRED TEXT BOX LANGUAGE. IT ONLY | | | SHOWS DIGITALLY SIGNED BY DEWEY A. LEBLANC AND THE | | | DATE. IT DOESN'T IDENTIFY THE ENGINEER'S LICENSE | | | NUMBER. | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | NEW RESPONSE TO INFORMAION SUBMITTED ON 04/20/23: | | | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF SEC. 61G15-23.004. IT DOESN'T HAVE THE | | | REQUIRED TEXT BOX LANGUAGE. IT ONLY SHOWS DIGITALLY | | | SIGNED BY DEWEY A. LEBLANC AND THE DATE. IT DOESN'T | | | IDENTIFY THE ENGINEER'S LICENSE NUMBER AND THE REST OF | | | THE REQUIRED TEXT BOX LANGUAGE | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-19 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-19 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2023-04-19 14:20:05 | RESIDENTIAL(R3)SECOND BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23020491 | | | 324 SUMMA ST | | | | | | | | | PREVIOUS COMMENT: | | | 3- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE | | | DIGITAL SIGNATURE. | | | | | | RESPONSE: | | | ENGINEER'S DRAWINGS SUBMITTED HAVE A COPY OF THE | | | ENGINEER???S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE | | | NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A | | | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE | | | DIGITAL SIGNATURE OF THE ENGINEER AS REQUIRED BY SEC. | | | 61G15-23.004 FAC AND CHAPTER 471 F.S. | | | | | | ALSO, ENGINEER'S DIGITAL SIGNATURE DOESN'T SEEM TO | | | COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. IT | | | DOESN'T HAVE THE REQUIRED TEXT BOX LANGUAGE. IT ONLY | | | SHOWS DIGITALLY SIGNED BY DEWEY A. LEBLANC AND THE | | | DATE. IT DOESN'T IDENTIFY THE ENGINEER'S LICENSE | | | NUMBER. | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-21 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-21 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2023-03-21 18:40:36 | RESIDENTIAL (R3)BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23020491 | | | 324 SUMMA ST | | | | | | NOTE: | | | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. | | | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL | | | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN | | | THE FLORIDA BUILDING CODE. | | | | | | 1- SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE | | | AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH | | | THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING | | | BUILDING. | | | | | | 2- FBC R 703.4, FBC B 1405.4, A FLASHING DETAIL OR | | | SPECIFICATION IS REQUIRED. THIS COMMENT CAN BE RESOLVED | | | BY DOING ONE OF THE FOLLOWING: | | | | | | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED | | | AND NOTE THE CODE REFERENCE - EXAMPLE "FLASHING IN | | | ACCORDANCE WITH FBC R 703.4/B 1405.4 WILL BE | | | INSTALLED". | | | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS | | | MAY INCLUDE MORE THAN ONE OPTION | | | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN | | | ONE OPTION | | | | | | 3- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE | | | DIGITAL SIGNATURE. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-21 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-20 |
Time |
17:15 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-20 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-20 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2023-04-20 13:05:27 | RECEIVE EMAIL FROM LISA. JG. | | | LISA REIMAN, AREA PERMIT MANAGER | | | GO PERMITS, LLC | | | 330.885.4916 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-19 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-14 |
Time |
15:07 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-21 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-01 |
Time |
09:22 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-21 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-21 |
Time |
18:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-20 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-20 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2023-04-20 13:09:54 | DIGITAL SIGNATURE REVIEW: | | | | | | PREVIOUS COMMENT: | | | 1- ENGINEER'S DRAWINGS SUBMITTED HAVE A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE | | | NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A | | | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE | | | DIGITAL SIGNATURE OF THE ENGINEER AS REQUIRED BY SEC. | | | 61G15-23.004 FAC AND CHAPTER 471 F.S. | | | | | | ALSO, ENGINEER'S DIGITAL SIGNATURE DOESN'T SEEM TO | | | COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. IT | | | DOESN'T HAVE THE REQUIRED TEXT BOX LANGUAGE. IT ONLY | | | SHOWS DIGITALLY SIGNED BY DEWEY A. LEBLANC AND THE | | | DATE. IT DOESN'T IDENTIFY THE ENGINEER'S LICENSE | | | NUMBER. | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | NEW RESPONSE TO INFORMATION SUBMITTED ON 04/20/23: | | | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF SEC. 61G15-23.004. IT DOESN'T HAVE THE | | | REQUIRED TEXT BOX LANGUAGE. IT ONLY SHOWS DIGITALLY | | | SIGNED BY DEWEY A. LEBLANC AND THE DATE. IT DOESN'T | | | IDENTIFY THE ENGINEER'S LICENSE NUMBER AND THE REST OF | | | THE REQUIRED TEXT BOX LANGUAGE | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-19 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-19 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2023-04-19 14:20:47 | DIGITAL SIGNATURE REVIEW: | | | | | | 1- ENGINEER'S DRAWINGS SUBMITTED HAVE A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE | | | NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A | | | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE | | | DIGITAL SIGNATURE OF THE ENGINEER AS REQUIRED BY SEC. | | | 61G15-23.004 FAC AND CHAPTER 471 F.S. | | | | | | ALSO, ENGINEER'S DIGITAL SIGNATURE DOESN'T SEEM TO | | | COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. IT | | | DOESN'T HAVE THE REQUIRED TEXT BOX LANGUAGE. IT ONLY | | | SHOWS DIGITALLY SIGNED BY DEWEY A. LEBLANC AND THE | | | DATE. IT DOESN'T IDENTIFY THE ENGINEER'S LICENSE | | | NUMBER. | | | | | | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING | | | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-21 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-21 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2023-03-21 18:41:47 | DIGITAL SIGNATURE: | | | | | | 1- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE | | | DIGITAL SIGNATURE. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|