Plan Review Details - Permit 23020478
Plan Review Stops For Permit 23020478
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 11:02 Sent To  
Notes
2023-06-30 11:02:42REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC 107.2.1
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR DOORS,
 WINDOW SYSTEMS, ROOFING SYSTEMS AND EXTERIOR SYSTEMS
 LISTED ON THE DRAWINGS.
  
 2) I DO NOT SEE A LIST OF DEFERRED ITEMS ON DRAWING G
 101 AS NOTED IN THE CORRECTIONS LETTER - - EXTERIOR
 WINDOW, DOOR, ROOFING SYSTEM AND EXTERIOR WALL CLADDING
 SYSTEMS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO
 BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC WPB
 107.3.4.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2023-06-01 Time 13:05 Sent To  
Notes
2023-06-01 13:07:50REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC 107.2.1
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR DOORS,
 WINDOW SYSTEMS, ROOFING SYSTEMS AND EXTERIOR SYSTEMS
 LISTED ON THE DRAWINGS.
  
 2) I DO NOT SEE A LIST OF DEFERRED ITEMS ON DRAWING G
 101 AS NOTED IN THE CORRECTIONS LETTER - - EXTERIOR
 WINDOW, DOOR, ROOFING SYSTEM AND EXTERIOR WALL CLADDING
 SYSTEMS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO
 BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC WPB
 107.3.4.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 11:46 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 11:38 Sent To  
Notes
2023-04-19 11:43:32REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC 107.2.1
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR DOORS,
 WINDOW SYSTEMS AND ROOFING SYSTEMS LISTED ON THE
 DRAWINGS.
  
 2) PLEASE SHOW EXTERIOR WALL CLADDING ATTACHMENTS TO
 THE STEEL FRAMING (ATTACHMENT TYPE, SIZE AND ON CENTER
 SPACING) OR PROVIDE A PRODUCT APPROVAL FOR THE WALL
 CLADDING SYSTEM - FBC WPB 107.2.1
  
 3) WINDOW, DOOR, ROOFING SYSTEM AND EXTERIOR WALL
 CLADDING SYSTEMS MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 FBC WPB 107.3.4.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By rmcphers Date 2023-02-24 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2023-02-24 Time 09:57 Sent To  
Notes
2023-02-24 10:32:29REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC 107.2.1
  
 1) PLEASE PROVIDE THE DETAILS FOR THE "6" LIGHT GAUGE
 FRAMING WITH EXTERIOR STO STUCCO SYSTEM".
  
 2) PLEASE PROVIDE DETAILS FOR THE "POWDER COATED ALUM.
 STOREFRONT SYSTEM WITH FROSTED GLAZING"
  
 3) PLEASE PROVIDE THE ROOFING SYSTEM PRODUCT APPROVALS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-11 Cont ID  
Sent By jleahy Date 2023-07-11 Time 16:38 Rev Time 0.00
Received By jleahy Date 2023-07-11 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By jleahy Date 2023-03-10 Time 18:11 Rev Time 0.00
Received By jleahy Date 2023-03-10 Time 18:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-24 Cont ID  
Sent By pleduc Date 2023-02-24 Time   Rev Time 0.00
Received By pleduc Date 2023-02-24 Time 12:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-11 Cont ID  
Sent By jleahy Date 2023-07-11 Time 16:38 Rev Time 0.00
Received By jleahy Date 2023-06-29 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 13:13 Rev Time 0.00
Received By rmcphers Date 2023-05-31 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 11:53 Rev Time 0.00
Received By rmcphers Date 2023-04-18 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By avolcy Date 2023-03-24 Time 08:24 Rev Time 0.00
Received By avolcy Date 2023-02-23 Time 14:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 13:13 Rev Time 0.00
Received By rmcphers Date 2023-06-01 Time 13:13 Sent To  
Notes
2023-06-01 13:13:42SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS E-PB01 AND E-PB02 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By rmcphers Date 2023-04-19 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 11:49 Sent To  
Notes
2023-04-19 11:53:49SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS E-PB01 AND E-PB02 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-24 Cont ID  
Sent By rmcphers Date 2023-02-24 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2023-02-24 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-24 Cont ID  
Sent By AVolcy Date 2023-03-24 Time 08:21 Rev Time 0.00
Received By avolcy Date 2023-03-24 Time 08:21 Sent To  
Notes
2023-03-24 08:23:54THIS REVIEW IS LIMITED TO THE ELEVATOR AND ENCLOSURE
 ONLY
  
 THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 81-20, AS
 APPROVED BY THE CITY COMMISSION AND AS MAY BE AMENDED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved