Plan Review Details - Permit 23020399
Plan Review Stops For Permit 23020399
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-15 Cont ID  
Sent By cthroop Date 2023-05-15 Time 06:28 Rev Time 0.00
Received By cthroop Date 2023-05-09 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-04 Cont ID  
Sent By cthroop Date 2023-04-04 Time 07:16 Rev Time 0.00
Received By cthroop Date 2023-04-04 Time 06:37 Sent To  
Notes
2023-04-04 07:19:292ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1.PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE
 PROPOSED WINDOWS AND EXT. DOORS.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By cthroop Date 2023-03-07 Time 07:44 Rev Time 0.00
Received By cthroop Date 2023-03-07 Time 06:32 Sent To  
Notes
2023-03-07 07:48:431ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE AN EXISTING FLOOR PLAN OF THE ENTIRE
 STRUCTURE. IDENTIFY LOCATION OF WORK. (BUILDING AND
 ELECTRICAL)
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
 (AS APPLICABLE)
  
 2. INCLUDE A NARRATIVE (SCOPE OF WORK) FOR THE PROPOSED
 WORK. (BUILDING AND ELECTRICAL)
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-02 Cont ID  
Sent By mpeterso Date 2023-05-02 Time 11:18 Rev Time 0.00
Received By mpeterso Date 2023-05-02 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By mpeterso Date 2023-04-05 Time 11:47 Rev Time 0.00
Received By mpeterso Date 2023-04-05 Time 11:39 Sent To  
Notes
2023-04-05 12:00:29ELECTRIC REVIEW FAILED
  
 1) PREVIOUS COMMENT NOT ADDRESSED. PLEASE PROVIDE A
 WORK SCOPE AND NOTE ON PLANS NEW VERSUS EXISTING WORK.
 IF ALL ITEMS ON PLANS ARE NEW PLEASE STATE WITH A NOTE
 ALL WORK DETAILED IS NEW AND IS TO COMPLY WITH ALL
 CURRENT BUILDING AND ELECTRICAL CODES. FBC 107.2
 2)PLEASE PROVIDE PRINTED NAME AND SIGNATURE OF THE
 PERSON WHO PREPARED THE ELECTRICAL DESIGN SHALL BE ON
 THE DRAWINGS- SEC. 107.2.1 WPB. PLEASE NOTE THAT AN
 ELECTRICAL SUB-CONTRACTOR APPLICATION SHALL BE
 SUBMITTED TO THE WPB BUILDING DEPT.- SEC. 105.1 WPB.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-14 Cont ID  
Sent By mpeterso Date 2023-02-14 Time 11:53 Rev Time 0.00
Received By mpeterso Date 2023-02-14 Time 11:28 Sent To  
Notes
2023-02-14 12:09:38ELECTRIC PLAN REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL
 ELECTRIC WORK. CLEARLY DISTINGUISH NEW WORK VERSUS WORK
 THAT IS EXISTING AND TO REMAIN. PLEASE INCLUDE ALL
 SWITCHES, RECEPTACLES, APPLIANCES, AIR CONDITIONING,
 WATER HEATERS, ELECTRIC PANELS AND METERS.
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 2) PLEASE PROVIDE AN ELECTRIC PANEL SCHEDULE DETAILING
 ALL CIRCUITS REQUIRED, CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION FOR EACH CIRCUIT. PLEASE INDICATE WHETHER
 CIRCUIT IS NEW OR EXISTING.
  
 FBC 107.2 AND NEC 215.5
  
 3) PLEASE PROVIDE AN ACCURATE ELECTRIC RISER DETAILING
 ELECTRIC PANEL, CONDUIT, CONDUCTOR AND OVERCURRENT
 PROTECTION SIZES. PLEASE INDICATE EQUIPMENT AS NEW OR
 EXISTING.
  
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER
 DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF
 THE FEEDERS.
  
 4) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY
 WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC
 FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT
 RECEPTACLE REQUIREMENTS.
  
 5) PROVIDE AN ELECTRIC LOAD CALCULATION DETAILING ALL
 ELECTRIC LOADS, AND APPLIANCES SUCH AS WATER HEATERS,
 RANGES, AIR CONDITIONING EQUIPMENT, ETC.
  
 NEC 220.40, THE CALCULATED LOAD OF A FEEDER OR SERVICE
 SHALL NOT BE LESS THAN THE SUM OF THE LOADS ON THE
 BRANCH CIRCUITS SUPPLIED
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-05-30 Cont ID  
Sent By amhamilt Date 2023-05-30 Time 10:26 Rev Time 0.00
Received By amhamilt Date 2023-05-30 Time 10:26 Sent To  
Notes
2023-05-30 10:27:04AS DISCUSSED, PLEASE ENSURE THAT *ONLY* DAMAGED WOOD IS
 REPLACED, AND THAT REPLACEMENT WOOD IS IN MATCHING
 WIDTH AND PROFILE TO EXISTING.
  
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By amhamilt Date 2023-04-24 Time 12:40 Rev Time 0.00
Received By amhamilt Date 2023-04-24 Time 12:40 Sent To  
Notes
2023-04-24 12:41:52THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE ADDRESS PREVIOUS COMMENT.
  
 PLEASE ALSO INDICATE ON WINDOW SCHEDULE FRAME COLOR,
 (SHOULD BE WHITE) GLASS COLOR (SHOULD BE CLEAR) AND IF
 ANY LOW E COATING WILL BE APPLIED TO WINDOWS (ONLY
 PERMISSIBLE ON SIDES AND REAR)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-03-23 Cont ID  
Sent By amhamilt Date 2023-03-23 Time 12:07 Rev Time 0.00
Received By amhamilt Date 2023-03-23 Time 12:07 Sent To  
Notes
2023-03-23 12:09:39THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PER SITE VISIT, PLEASE CONFIRM THAT ALL SIDING WILL BE
 CAREFULLY REMOVED AND REUSED, WINDOWS WILL BE REPLACED
 UNDER A SEPARATE PERMIT, AND ANY REPLACEMENT SIDING
 WILL BE LOCATED TO THE REAR OR ON ENCLOSED CARPORT, AND
 MATCHES IN WIDTH AND PROFILE TO EXISTING. PLEASE ALSO
 PROVIDE MORE INFORMATION ON ANY REPLACEMENT SIDING
 USED.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-30 Cont ID  
Sent By aoliver Date 2023-05-30 Time 13:46 Rev Time 0.00
Received By aoliver Date 2023-04-26 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-25 Cont ID  
Sent By aoliver Date 2023-04-25 Time 07:20 Rev Time 0.00
Received By aoliver Date 2023-03-29 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By aoliver Date 2023-03-24 Time 09:03 Rev Time 0.00
Received By aoliver Date 2023-02-10 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-27 Cont ID  
Sent By ccole Date 2023-04-27 Time 10:46 Rev Time 0.00
Received By ccole Date 2023-04-27 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-03 Cont ID  
Sent By ccole Date 2023-04-03 Time 08:07 Rev Time 0.00
Received By ccole Date 2023-04-03 Time 07:38 Sent To  
Notes
2023-04-03 08:08:042ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23020399
 4/3/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET EP1: THE VENTING FOR THE BATH 3 FIXTURES IS
 NOT IN COMPLIANCE WITH SECS. P3108.1 & P3108.2.1-
 HORIZONTAL WET VENTING FBC RES. TO FIX THE PROBLEM
 PROVIDE A VENT FOR THE LAVATORY FIXTURE DRAIN AND
 EITHER VENT THROUGH THE ROOF OR CONNECT TO ANOTHER VENT
 GOING THROUGH THE ROOF.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PERSON WHO
 PREPARED THE PLUMBING DESIGN SHALL BE ON THE DRAWINGS-
 SEC. 107.2.1 WPB. PLEASE NOTE THAT A PLUMBING
 SUB-CONTRACTOR APPLICATION SHALL BE SUBMITTED TO THE
 WPB BUILDING DEPT.- SEC. 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By ccole Date 2023-02-13 Time 11:51 Rev Time 0.00
Received By ccole Date 2023-02-13 Time 11:26 Sent To  
Notes
2023-02-13 11:52:531ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23020399
 2/13/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW COMMENT #1
 BELOW AND IF YOU HAVE QUESTIONS PLEASE CONTACT ME.
  
 1) PLEASE PROVIDE THE SCOPE OF WORK FOR PLUMBING AND
 GAS ON THE FLOOR PLAN OR ON A SEPARATE PLAN- SEC.
 107.2.1 WPB. PLEASE NOTE THAT RISER DRAWINGS ARE
 REQUIRED FOR NEW SANITARY DRAINAGE AND VENT PIPING, AND
 FOR NEW GAS PIPING INSTALLATIONS - SEC. 107.3.5.3 (12,
 13) WPB MINIMUM PLAN REVIEW CRITERIA FOR RESIDENTIAL
 (ONE AND TWO FAMILY).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-05-15 Cont ID  
Sent By cthroop Date 2023-05-15 Time 06:28 Rev Time 0.00
Received By cthroop Date 2023-05-09 Time 16:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-07 Cont ID  
Sent By cthroop Date 2023-03-07 Time 07:44 Rev Time 0.00
Received By cthroop Date 2023-03-07 Time 06:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2023-03-23 Cont ID  
Sent By amhamilt Date 2023-03-23 Time 12:07 Rev Time 0.00
Received By amhamilt Date 2023-03-23 Time 12:07 Sent To  
Notes
***NONE***