Plan Review Details - Permit 23020356
Plan Review Stops For Permit 23020356
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 15:17 Rev Time 0.00
Received By jgomez Date 2023-06-21 Time 13:40 Sent To  
Notes
2023-06-21 15:18:22TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE:
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A
 MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT
 PLYWOOD SHEATHING BETWEEN UNITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-20 Cont ID  
Sent By jgomez Date 2023-06-20 Time 16:37 Rev Time 0.00
Received By jgomez Date 2023-06-20 Time 16:20 Sent To  
Notes
2023-06-20 16:38:06RESIDENTIAL(R3) RE-ROOF THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020356
 6132 UNITED ST
  
 ORIGINAL COMMENT:
 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED.
 GENERAL LIMITATIONS ON PAGE 5 OF 7 DON'T LIST TILE BOND
 ADHESIVE AS ONE OF THE ADHESIVES APPROVED TO BE USED
 WITH THIS UNDERLAYMENT. NEED TO PROVIDE PRODUCT
 APPROVAL FOR UNDERLAYMENT THAT ALLOWS TILE BOND TO BE
 USED.
 F.A.C. 61G20.3.001.
  
 PREVIOUS COMMENT:
 A)NEED TO MARK/SPECIFY ON NEW FLORIDA PRODUCT APPROVAL
 FL22525-R6 SUBMITTED WHICH APPROVED ASSEMBLY IS GOING
 TO BE INSTALLED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
  
 PREVIOUS COMMENT:
 B)IT IS NOT CLEAR WHICH UNDERLAYMENT IS GOING TO BE
 INSTALLED. FLORIDA PRODUCT APPROVAL FL22525-R6
 SUBMITTED IS HIGHLIGHTED WITH POLYSTICK MTS PLUS ON
 TABLE 2 BUT IT IS S HIGHLIGHTED WITH POLYSTICK TU MAX
 ON TABLE 2 ON PAGE 4 OF 9.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 CONTRACTOR HIGHLIGHTED POLYSTICK MTS PLUS AS THE
 SELECTED UNDERLAYMENT. THIS UNDERLAYMENT IS NOT
 APPROVED FOR ADHESIVE-SET APPLICATIONS. CONTRACTOR IS
 USING ADHESIVE TO INSTALL THE ROOF TILES. THIS
 UNDERLAYMENT CAN'T BE USED.
  
  
 PREVIOUS COMMENT:
 C)CLEARLY IDENTIFY WHICH SUBSTRATE OPTION FROM TABLE 3
 ON PAGE 5 OF 9 OF FLORIDA PRODUCT APPROVAL FL22525-R6
 SUBMITTED IS GOING TO BE INSTALLED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE:
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A
 MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT
 PLYWOOD SHEATHING BETWEEN UNITS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By jgomez Date 2023-06-16 Time 18:42 Rev Time 0.00
Received By jgomez Date 2023-06-16 Time 17:37 Sent To  
Notes
2023-06-16 18:43:10RESIDENTIAL(R3) RE-ROOF SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020356
 6132 UNITED ST
  
 1-ROOF TILE NOA 22-0201.07 AND ROOF TILE ADHESIVE NOA
 21-1006.03 SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE
 TO BE USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC R301.2.1 FBC-RESIDENTIAL.
 NOTE: SYSTEM ON PAGE 7 AS NOTED ON TILE BOND NOA
 DOESN'T MATCH TILE PROFILE. COORDINATE PADDY SIZE AND
 ROOF TILE PROFILE WITH ROOF TILE NOA TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 THE APPLICATION STATUS FOR NEW FLORIDA PRODUCT APPROVAL
 FL7849-R17 SUBMITTED SAYS "APPLIED FOR". IT IS NOT
 APPROVED YET. NEED APPROVED PRODUCT APPROVAL.
 FAC 61G20.3.001
  
  
 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED.
 GENERAL LIMITATIONS ON PAGE 5 OF 7 DON'T LIST TILE BOND
 ADHESIVE AS ONE OF THE ADHESIVES APPROVED TO BE USED
 WITH THIS UNDERLAYMENT. NEED TO PROVIDE PRODUCT
 APPROVAL FOR UNDERLAYMENT THAT ALLOWS TILE BOND TO BE
 USED.
 F.A.C. 61G20.3.001.
  
 RESPONSE:
 A)NEED TO MARK/SPECIFY ON NEW FLORIDA PRODUCT APPROVAL
 FL22525-R6 SUBMITTED WHICH APPROVED ASSEMBLY IS GOING
 TO BE INSTALLED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)IT IS NOT CLEAR WHICH UNDERLAYMENT IS GOING TO BE
 INSTALLED. FLORIDA PRODUCT APPROVAL FL22525-R6
 SUBMITTED IS HIGHLIGHTED WITH POLYSTICK MTS PLUS ON
 TABLE 2 BUT IT IS S HIGHLIGHTED WITH POLYSTICK TU MAX
 ON TABLE 2 ON PAGE 4 OF 9.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C)CLEARLY IDENTIFY WHICH SUBSTRATE OPTION FROM TABLE 3
 ON PAGE 5 OF 9 OF FLORIDA PRODUCT APPROVAL FL22525-R6
 SUBMITTED IS GOING TO BE INSTALLED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE:
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A
 MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT
 PLYWOOD SHEATHING BETWEEN UNITS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-26 Cont ID  
Sent By jgomez Date 2023-05-26 Time 18:25 Rev Time 0.00
Received By jgomez Date 2023-05-26 Time 17:33 Sent To  
Notes
2023-05-26 18:25:46RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020356
 6132 UNITED ST
  
 1-ROOF TILE NOA 22-0201.07 AND ROOF TILE ADHESIVE NOA
 21-1006.03 SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE
 TO BE USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC R301.2.1 FBC-RESIDENTIAL.
 NOTE: SYSTEM ON PAGE 7 AS NOTED ON TILE BOND NOA
 DOESN'T MATCH TILE PROFILE. COORDINATE PADDY SIZE AND
 ROOF TILE PROFILE WITH ROOF TILE NOA TO AVOID
 CONFLICTS/DELAYS.
  
 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED.
 GENERAL LIMITATIONS ON PAGE 5 OF 7 DON'T LIST TILE BOND
 ADHESIVE AS ONE OF THE ADHESIVES APPROVED TO BE USED
 WITH THIS UNDERLAYMENT. NEED TO PROVIDE PRODUCT
 APPROVAL FOR UNDERLAYMENT THAT ALLOWS TILE BOND TO BE
 USED.
 F.A.C. 61G20.3.001.
  
 3- HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE
 INSTALLATION AS REQUIRED BY SEC. R905.3.7.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE
 WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE
 INSTALLATION MANUAL (6TH EDITION) OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
 ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE
 PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND
 CLEARLY MARK ATTACHMENT METHOD.
  
 TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE:
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A
 MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT
 PLYWOOD SHEATHING BETWEEN UNITS.
  
 5- CLARIFY WHY SUBMITTING NOA FOR SHINGLES. SEC.
 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 15:18 Rev Time 0.00
Received By jgomez Date 2023-06-21 Time 13:40 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-20 Cont ID  
Sent By jgomez Date 2023-06-20 Time 16:38 Rev Time 0.00
Received By jgomez Date 2023-06-20 Time 16:20 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-16 Cont ID  
Sent By jgomez Date 2023-06-16 Time 18:43 Rev Time 0.00
Received By jgomez Date 2023-06-08 Time 08:23 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-26 Cont ID  
Sent By jgomez Date 2023-05-26 Time 18:25 Rev Time 0.00
Received By jgomez Date 2023-05-24 Time 14:16 Sent To I
Notes
***NONE***