Plan Review Details - Permit 23020340
Plan Review Stops For Permit 23020340
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By shill Date 2023-02-22 Time 12:48 Rev Time 0.00
Received By shill Date 2023-02-22 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By shill Date 2023-02-16 Time 11:48 Rev Time 0.00
Received By shill Date 2023-02-16 Time 11:48 Sent To  
Notes
2023-02-16 11:49:28FBC107, SCOPE NOT CLEAR. APPLICATION IS FOR PASS
 THROUGH IN EXTERIOR WALL. PLAN APPEARS TO SHOW PROPOSED
 WORK IN THE INTERIOR WALL.
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-30 Cont ID  
Sent By pleduc Date 2023-03-30 Time   Rev Time 0.00
Received By pleduc Date 2023-03-30 Time 10:48 Sent To  
Notes
2023-03-30 10:58:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF THE OCCUPANCY
 CLASSIFICATION OF BOTH SPACES AND THE INTENT OF THE
 OCCUPANCY.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE OCCUPANCY DETAILS.
  
  
 2) THERE IS NO INDICATION OF NUMBER OF EXITS AND TRAVEL
 DISTANCES IN COMPLINACE WITH THE OCCUPANCY
 CLASSIFICATION NOTED IN # 1.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING COMPLIANCE
 WITH APPLICABLE CODE WITHIN NFPA 101.
  
  
  
 3) IT APPEARS THAT THE PROPOSED OPENING IS WITHIN A
 FIRE RATED SEPARATION, HOWEVER, THERE IS NO INDICATION
 OF THE NUMERICAL CALL OUT FOR THE # 1 TYP WALL TYPE
 THOUGH ITS A CMU.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 IF IT IS A REUIRED FIRE RATED SEPARATION THE OPENING IS
 REQUIRED TO HAVE THE SAME FIRE RATING.
  
 PLEASE PROVIDE THE WALL TYPE DETAILS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-16 Cont ID  
Sent By shill Date 2023-02-16 Time 11:50 Rev Time 0.00
Received By shill Date 2023-02-16 Time 11:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-16 Cont ID  
Sent By shill Date 2023-02-16 Time 11:51 Rev Time 0.00
Received By shill Date 2023-02-16 Time 11:51 Sent To  
Notes
***NONE***