| Plan Review Stops For Permit 23020256 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-15 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-15 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2023-02-15 08:44:31 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-24 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-24 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2023-02-24 15:02:01 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE - FBC | | | R807.1 THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN | | | 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE | | | LOCATED IN A HALLWAY OR OTHER LOCATION WITH READY | | | ACCESS. | | | | | | 2) DRAFT STOP IS SHOWN IN THE ROOF TRUSSES - WHICH WILL | | | REQUIRE 2 ATTIC ACCESS. DRAFT STOP IS NOT REQUIRED IN | | | THE ATTIC. | | | | | | 3) PLEASE SHOW THE DRAFT STOP IN THE FLOOR TRUSSES PER | | | - FBC R302.12 DRAFTSTOPPING. | | | IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE | | | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A | | | FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED | | | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED | | | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE | | | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. | | | | | | 4) PLEASE PROVIDE THE DOCUMENTATION (ICC EVALUATION | | | REPORT) FOR THE ICYNENE FOAM INSULATION - FBC R316.3 | | | | | | 5) PRODUCT APPROVAL (NOA 20-0429.11) FOR THE SLIDING | | | GLASS DOOR IS NOT ON THE LIST SHOWN ON THE WINDOW/DOOR | | | SCHEDULE AND IS APPROVED FOR SMALL MISSILE IMPACT WHICH | | | IS GLAZING ABOVE 30' ELEVATION - PLEASE PROVIDE THE | | | SHUTTER PRODUCT APPROVAL FOR THIS SLIDING GLASS DOOR - | | | FBC R301.2.1.2 | | | | | | 6) PRODUCT APPROVAL (FL16107-R13) FOR THE OVERHEAD | | | GARAGE DOOR HAS A MAXIMUM WIDTH OF 9' - THE PROPOSED | | | OVERHEAD GARAGE DOOR SHOWN ON THE DRAWING IS 16' - | | | PLEASE PROVIDE A PRODUCT APPROVAL FOR THE 16' WIDE | | | DOOR. PLEASE REVISE THE PRODUCT APPROVALS ON THE | | | WINDOW/DOOR SCHEDULE. | | | | | | 7) PRODUCT APPROVAL (FL21138.12) FOR THE SWING DOOR HAS | | | A MAXIMUM DESIGN PRESSURE OF (-50) PLEASE SHOW THE | | | LOCATION FOR THESE DOORS - SOME OF THE EXTERIOR DOORS | | | SHOWN ON THE WINDOW/DOOR SCHEDULE DRAWING SHOW THAT A | | | HIGHER PRESSURE IS REQUIRED. | | | | | | 8) PLEASE DESCRIBE HOW THE ROOF COMPONENTS (TILE - | | | UNDERLAYMENT) ARE ATTACHED OR CIRCLE THE ROOF SYSTEM | | | ATTACHMENTS IN THE PRODUCT APPROVALS - IF USING | | | ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. | | | FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE | | | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, | | | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, | | | MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND | | | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND | | | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT | | | BY AN ARCHITECT OR ENGINEER CERTIFYING SUITABILITY FOR | | | THE SPECIFIC SITE MUST BE SUBMITTED WITH THE | | | CONSTRUCTION DOCUMENTS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-02-16 |
Time |
23:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-02-16 |
Time |
20:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-31 |
Time |
05:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-29 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-24 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-16 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-09 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-02-15 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-04-13 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-29 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2023-04-06 15:56:42 | RECEIPT MU-2023-014812 - $49.23 PAID | | 2023-03-29 07:49:01 | 3/29/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-24 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-24 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2023-02-24 15:02:37 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-31 |
Time |
05:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-31 |
Time |
05:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-17 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-17 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2023-03-17 07:47:09 | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | SUBMITTED THIS CYCLE SPECS THE AHU-1 AS A 3 - TON | | | SYSTEM AND AHU - 2 AS A 3 - TON SYSTEM BUT THE | | | EQUIPMENT SCHEDULE ON THE M-1 SHEET SPECS. EACH UNIT TO | | | BE A 5 - TON UNIT. THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS AND THE EQUIPMENT SCHEDULE MUST BE WITHN | | | THE 1.15 TIMES SIZING ACCORDING TO: FEC R403.7.1.2 | | | | | | 2) THE KITCHEN HOOD MAY REQUIRE MAKE-UP AIR. FRC | | | M1503.4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-16 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-16 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2023-02-16 16:21:31 | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | FEC R403.7.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-16 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-16 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2023-03-29 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2023-03-29 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2023-03-29 11:23:16 | PRIVATE PROVIDER INSPECTIONS | | | DOCUMENTS SENT TO FILENET |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-24 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-24 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2023-02-24 15:03:02 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-31 |
Time |
05:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-31 |
Time |
05:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-20 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-24 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-24 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2023-02-16 16:22:22 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-03-24 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-24 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
AVolcy |
Date |
2023-03-09 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-09 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2023-03-09 12:07:30 | 03.09.23 - FAILED | | | | | | BUILDING HEIGHT NOT MEASURED AS DEFINED BY THE LAND | | | DEVELOPMENT REGULATIONS. BUILDING, HEIGHT OF, MEANS THE | | | VERTICAL DISTANCE FROM THE MEAN GRADE OF A LOT AT THE | | | FRONTAGE OF THE BUILDING TO THE HIGHEST POINT OF THE | | | TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK | | | LINE OF A MANSARD ROOF, OR TO THE MID-HEIGHT LEVEL | | | BETWEEN EAVES AND RIDGE FOR GABLE, HOP, AND GAMBREL | | | ROOFS. | | | UPDATE ELEVATIONS TO ILLUSTRATE THAT THE MAX HEIGHT OF | | | 30FT FOR THIS DISTRICT (SF14) IS NOT BEING EXCEEDED. | | | | | | NEW SINGLE FAMILY AND ALL OTHER NEW STRUCTURES REQUIRE | | | A LANDSCAPE PERMIT BE SUBMITTED OR USE THE CONDITIONAL | | | APPROVAL FORM. | | | APPLY FOR A SEPARATE LANDSCAPE PERMIT AS PART OF THE | | | RESUBMITTAL. | | | | | | SEPARATE PERMIT REQUIRED FOR: | | | FENCE/WALL, DRIVEWAY, POOL, GENERATOR, | | | MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, LANDSCAPE, | | | ACCESSORY STRUCTURE, OTHER | | | | | | DECK CANNOT ENCROACH INTO THE EASEMENT. |
|
|