Plan Review Details - Permit 23020213
Plan Review Stops For Permit 23020213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-07 Cont ID  
Sent By jbrooks Date 2023-03-07 Time 11:25 Rev Time 0.00
Received By jbrooks Date 2023-03-07 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-27 Cont ID  
Sent By jbrooks Date 2023-02-27 Time 12:24 Rev Time 0.00
Received By jbrooks Date 2023-02-27 Time 08:06 Sent To  
Notes
2023-02-27 12:24:50JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE
 RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP,
 ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION
 INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN
 PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C
 AREAS. (-70). ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING. SECOND REQUEST.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL7473-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By jbrooks Date 2023-02-07 Time 09:31 Rev Time 0.00
Received By jbrooks Date 2023-02-07 Time 07:38 Sent To  
Notes
2023-02-07 09:31:14JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 21-1130.01 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT (CAP
 SHEET) TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL22854-R1
 IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM
 BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT CONSIDER
 USING FL7473-R9.
 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE
 RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP,
 ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION
 INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN
 PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C
 AREAS. (-70). ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-07 Cont ID  
Sent By jbrooks Date 2023-03-07 Time 11:25 Rev Time 0.00
Received By jbrooks Date 2023-02-27 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-27 Cont ID  
Sent By jbrooks Date 2023-02-27 Time 12:24 Rev Time 0.00
Received By jbrooks Date 2023-02-13 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-07 Cont ID  
Sent By jbrooks Date 2023-02-07 Time 09:31 Rev Time 0.00
Received By jbrooks Date 2023-02-06 Time 15:31 Sent To  
Notes
***NONE***