| Plan Review Stops For Permit 23020134 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-03 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-03 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2023-02-03 12:57:46 | ADDRESS APPROPRIATE FOR PROJECT. FUTURE GUEST BUILDING | | | MAY REQUIRE AN ADDITIONA ADDRESS BUT WILL BE REVIEWED | | | ONCE IT IS APPLIED FOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-24 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2023-07-21 08:56:07 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ELEVATION CERTIFICATE - NEEDS CORRECTIONS - | | | | | | A8(C) - SHOULD BE 200 SQ. IN. - SINCE THE FLOOD VENTS | | | COVER 200 SQUARE INCHES | | | | | | A9(C) - SHOULD BE 600 SQ. IN. - SINCE THE FLOOD VENTS | | | COVER 200 SQUARE INCHES | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-16 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-16 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2023-06-16 13:30:41 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE CLOSET STANDS ALONE AS AN ENCLOSURE - THE GARAGE | | | WILL NEED ADDITIONAL FLOOD VENTS TO EQUAL THE REQUIRED | | | SQUARE INCHES OF FLOOD VENTS - FBC R322.2.2 | | | | | | 2) PLEASE PROVIDE THE SMART FLOOD VENT ICC EVALUATION | | | REPORT AND THE PRODUCT APPROVAL. FBC WPB 107.1 | | | | | | 3) ELEVATION CERTIFICATE - NEEDS CORRECTIONS - PER FEMA | | | ELEVATION CERTIFICATE INSTRUCTIONS | | | | | | A8(A) - THE CLOSET IS AN ENCLOSURE - SHOW THE CLOSET | | | SQUARE FOOTAGE | | | A8(B) - SHOW THE NUMBER OF FLOOD VENTS FOR THIS | | | ENCLOSURE | | | A8(C) - SHOW THE AREA OF FLOOD VENTS FOR THE ENCLOSURE | | | A9(B) - SHOW HOW MANY FLOOD VENTS FOR THE GARAGE | | | A9(C) - SHOW THE TOTAL OPEN AREA OF THE FLOOD VENTS FOR | | | THE GARAGE | | | A9(D) - SMART VENT IS AN ENGINEERED VENT | | | C2(A) - WOULD BE THE ENCLOSURE ELEVATION | | | C2(B) - WOULD BE THE NEXT HIGHER FLOOR | | | C2(E) - SHOW THE EQUIPMENT ELEVATION. | | | THE ELEVATION CERTIFICATE WILL NEED TO BE DIGITALLY | | | SIGNED BY THE SURVEYOR - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-31 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-31 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2023-03-31 13:19:16 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE SIZE AND LOCATIONS OF THE REQUIRED | | | FLOOD VENTS FOR THE GARAGE AND AC CLOSET - FBC R322.2.2 | | | | | | 2) PLEASE SHOW THE EQUIPMENT (AC) ELEVATIONS - FBC | | | R322.1.6 | | | | | | 3) PLEASE PROVIDE DETAILS FOR THE ROOF TILE ATTACHMENT | | | - FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE | | | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, | | | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, | | | MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED | | | | | | 4) ELEVATION CERTIFICATE - NEEDS CORRECTIONS - | | | A5 - THE LONGITUDE NUMBER SHOULD BE A NEGATIVE NUMBER. | | | A9(B) - SHOW HOW MANY FLOOD VENTS. | | | A9(C) - SHOW THE TOTAL OPEN AREA OF THE FLOOD VENTS. | | | B1 - INCLUDE THE COMMUNITY NUMBER. | | | C2(D) - THE ELEVATION NUMBER APPEARS TO BE INCORRECT - | | | THERE IS A DROP OF 4" ON DRAWING A-1 AND A DROP OF 5 | | | 1/2" ON DRAWING S-1 | | | C2(E) - SHOW THE EQUIPMENT ELEVATION. | | | SECTION "D" DESCRIBE THE TYPE OF EQUIPMENT | | | | | | 5) THE PAVING, GRADING AND DRAINAGE PLAN DOES NOT SHOW | | | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-15 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-15 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2023-02-15 11:56:54 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE FINISHED FLOOR ELEVATION TO BE 2 | | | FOOT ABOVE FEMA BASE FLOOD ELEVATION -- CITY ORDINANCE | | | NO. 4729-1 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA | | | BUILDING CODE, RESIDENTIAL. | | | (A) R322.2.1 ELEVATION REQUIREMENTS. 1. BUILDINGS AND | | | STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS | | | COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED | | | TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO | | | FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER IS | | | HIGHER. | | | | | | 2) PLEASE SHOW THE FLOOD VENT SIZES AND LOCATIONS IF | | | REQUIRED - FBC R322.2.2 | | | | | | 3) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC WPB 107.3.5.3 | | | | | | 4) PLEASE SHOW THE EQUIPMENT (AC, WATER HEATER ETC.) | | | ELEVATIONS - FBC R322.1.6 | | | | | | 5) PLEASE SHOW THE STEP DOWN DIMENSIONS - FRONT ENTRY, | | | SHOWER, GARAGE TO LIVING SPACE, PATIOS ETC. | | | | | | 6) PLEASE SHOW THE TRUSS FLOOR/CEILING DRAFT STOP | | | LOCATION AND TYPE - FBC R302.12 | | | | | | 7) PLEASE SHOW THE WINDOW SILL HEIGHT FOR THE OPERABLE | | | WINDOWS WHICH MAY REQUIRE GUARDS - R312.2.1 | | | | | | 8) PLEASE PROVIDE DOCUMENTATION FOR THE SPRAY FOAM | | | INSULATION - FBC R316.3 SURFACE BURNING | | | CHARACTERISTICS. | | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | | | 9) PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL FRONT | | | PAGES FOR PRODUCT APPROVAL FL7473-R9 | | | | | | 10) PLEASE CIRCLE THE ROOF TILE ATTACHMENT TO BE USED | | | IN THE ROOF TILE PRODUCT APPROVAL - IF USING ADHESIVE | | | PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE ROOF TILE | | | ADHESIVE. | | | | | | 11) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE | | | SITE PLAN OR PROVIDE A STORM WATER PLAN - FBC 107.2.5 | | | SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH | | | THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A | | | SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW | | | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-04-05 |
Time |
20:48 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-04-05 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-02-10 |
Time |
20:44 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-02-10 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2023-02-10 20:44:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 2. METER CAN OF INSUFFICIENT SIZE. FOR A 150A AND 100A | | | SERVICE DISCONNECT MINIMUM SIZE METERCAN IS 400AMPS | | | (320AMPS CONTINUOUS). NEC 110.3B | | | | | | 3. SERVICE ENTRANCE CONDUCTORS OF INSUFFCIENT SIZE | | | GOING TO LINE GUTTER FOR 250AMP SERVICE. NEC 230.42 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-04-06 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-04-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-30 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-30 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-03 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-03 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2023-02-03 13:54:58 | 1ST GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (13) - THERE ARE GAS | | | APPLIANCES SHOWN, BUT NO GAS DETAILS. PLEASE SUBMIT THE | | | GAS ISOMETRIC FOR REVIEW. BE SURE TO INCLUDE PIPE SIZES | | | AND DISTANCES, MATERIALS TO BE USED, PRESSURES USED IN | | | SIZING, AND VENTING AND COMBUSTION AIR CALCULATIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-24 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-13 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-21 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-21 |
Time |
17:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-18 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-18 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-02-16 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-16 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-15 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-15 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2023-02-15 13:09:48 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-04 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-04 |
Time |
13:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-06 |
Time |
06:16 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-06 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2023-02-06 06:17:17 | 1ST REVIEW FMC | | | PERMIT: 23020134 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE EXPLAIN WHY THE AHU IS NOT LISTED ON THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | | | | 2) PROVIDE SIZES FOR ALL FLEX DUCT ON THE DRAWINGS. FBC | | | 107.3.5 | | | | | | 3) SHEETS M-1 AND M-2: THE DRYER EXHAUST MATERIAL SHALL | | | BE 28 GAUGE METAL. FRC M1502.4.1 | | | | | | 4) PLEASE PROVIDE A RETURN AIR PATH BACK TO AHU-1 FROM | | | THE MASTER BEDROOM WHEN THE MASTER BEDROOM DOORS ARE | | | CLOSED. FRC M1602.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-21 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2023-07-21 08:56:47 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2023-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-16 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-16 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2023-06-16 14:02:36 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-31 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-31 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2023-03-31 13:27:04 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-15 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-15 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2023-02-15 13:11:29 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-30 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-30 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-03 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-03 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2023-02-03 13:50:57 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. UPSTAIRS BATHROOMS - NOT MORE THAN ONE WET-VENTED | | | FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION. FOR ALL 3 | | | BATHROOMS UPSTAIRS, THE WATER CLOSET AND SHOWER OR TUB | | | ARE CONNECTING ON THE HIGH SIDE OF THE VENTED FIXTURES | | | CONNECTION. ONLY ONE IS ALLOWED. | | | | | | 2. DOWNSTAIRS BATHROOM - 2020 FPC P3104.4 - THE DRY | | | VENT FOR THE TWO SHOWER TRAPS IS NOT ALLOWED TO BE | | | HORIZONTAL UNTIL IT IS 6" ABOVE THE FLOOD RIM OF THE | | | FIXTURES SERVED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2023-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-16 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-16 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2023-06-16 13:49:47 | ROOFING SYSTEM TO BE DEFERRED PER RESPONSE LETTER |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-31 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-31 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2023-03-31 13:27:26 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-15 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-15 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2023-02-15 13:10:22 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-21 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-16 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-16 |
Time |
14:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-31 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-31 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2023-03-31 13:29:46 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE PAVING, GRADING AND DRAINAGE PLAN DOES NOT SHOW | | | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-15 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-15 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-21 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-21 |
Time |
17:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-18 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-18 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2023-04-18 14:40:13 | | | | PLEASE ATTACH PROPERTY SURVEY | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-02-16 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-16 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2023-02-16 13:48:51 | FAILED | | | 2/16/2023 | | | | | | | | | ALL NEW CONSTRUCTION PROPERTIES ARE REQUIRED TO HAVE | | | LANDSCAP PERMITS IN THE SYSTEM. | | | | | | SEPARATE PERMIT REQUIRED FOR | | | | | | ACCESSORY STRUCTURE | | | POOL/SPA | | | FENCE/GATE | | | MECHICANAL EQUIPMENT | | | AC EQUIPMENT | | | DRIVEWAY | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] |
|
|