Plan Review Details - Permit 23020122
Plan Review Stops For Permit 23020122
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-04-12 Cont ID  
Sent By rmcphers Date 2023-04-12 Time 08:06 Rev Time 0.00
Received By rmcphers Date 2023-04-12 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By rperdomo Date 2023-04-10 Time 10:22 Rev Time 0.00
Received By rperdomo Date 2023-04-07 Time 15:33 Sent To  
Notes
2023-04-10 10:27:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW
  
 1. AVAILABLE FAULT CURRENT
 NEC 110.24 STATES: FIELD MARKING. SERVICE EQUIPMENT IN
 OTHER THAN DWELLING UNITS SHALL BE LEGIBLY MARKED IN
 THE FIELD WITH THE MAXIMUM AVAILABLE FAULT CURRENT. THE
 FIELD MARKING(S) SHALL INCLUDE THE DATE THE FAULT
 CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 2. WORKING SPACE
 NEC TABLE 110.26(A) OR IRC E3405.2
 SECTION 110.26 REQUIRES ADEQUATE WORKING SPACE FOR ALL
 ELECTRICAL EQUIPMENT. NEC SECTION 110.26(A) REQUIRES A
 CLEAR SPACE AT LEAST 30 INCHES WIDE AND 36 INCHES DEEP
 IF THE EQUIPMENT IS LIKELY TO BE WORKED ON WHILE
 ENERGIZED.
  
 3. ELECTRICAL PANEL
 NEC 110.3(B) INSTALLATION AND USE. EQUIPMENT THAT IS
 LISTED, LABELED, OR BOTH SHALL BE INSTALLED AND USED IN
 ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE
 LISTING OR LABELING.
  
 4. NEC SECTION 110.26 SPACES ABOUT ELECTRICAL EQUIPMENT
 (A) ELECTRICAL PANELS MUST BE ACCESSIBLE
 (B) ELECTRICAL PANELS MUST BE REACHABLE
 (C) OCCUPANTS MUST HAVE READY ACCESS
 (D) ELECTRICAL PANELS CANNOT BE EXPOSED TO PHYSICAL
 DAMAGE
 (E) ELECTRICAL PANELS SHOULD BE CLEAR OF FLAMMABLE
 MATERIAL
  
 5. NEC 110.14(D) CONDUCTOR TERMINATION, TORQUE - WHERE
 TIGHTENING TORQUE VALUES ARE INDICATED ON EQUIPMENT OR
 INSTALLATION INSTRUCTIONS, A CALIBRATED TORQUE TOOL
 MUST BE USED TO ACHIEVE THE INDICATED TORQUE VALUE,
 UNLESS THE EQUIPMENT MANUFACTURER PROVIDES AN
 ALTERNATIVE METHOD OF ACHIEVING THE REQUIRED TORQUE.
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-04-20 Cont ID  
Sent By parking Date 2023-04-20 Time 13:19 Rev Time 0.00
Received By lquinone Date 2023-04-20 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-30 Cont ID  
Sent By clfranci Date 2023-05-30 Time   Rev Time 0.00
Received By clfranci Date 2023-05-30 Time   Sent To  
Notes
2023-05-30 11:45:04THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 4) MAINTAIN SEPERATION OF WORK / CONSTRUCTION AREA FROM
 GENERAL PUBLIC ACCESS.
  
 5) IF ANY EXIT ACCESS CORRIDORS ARE TEMPORARILY BLOCKED
 DUE TO CONSTRUCTION PLEASE INDICATE NEW EXIT ACCESS.
 ACCESS TO EXITS MUST BE CLEARLY INDICATED.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-07 Cont ID  
Sent By clfranci Date 2023-04-07 Time   Rev Time 0.00
Received By clfranci Date 2023-04-07 Time   Sent To  
Notes
2023-04-07 14:59:23THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 4) MAINTAIN SEPERATION OF WORK / CONSTRUCTION AREA FROM
 GENERAL PUBLIC ACCESS.
  
 5) IF ANY EXIT ACCESS CORRIDORS ARE TEMPORARILY BLOCKED
 DUE TO CONSTRUCTION PLEASE INDICATE NEW EXIT ACCESS.
 ACCESS TO EXITS MUST BE CLEARLY INDICATED.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-05-30 Cont ID  
Sent By ccole Date 2023-05-30 Time 14:11 Rev Time 0.00
Received By ccole Date 2023-05-30 Time 12:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-04-13 Cont ID  
Sent By ccole Date 2023-04-13 Time 15:02 Rev Time 0.00
Received By ccole Date 2023-04-13 Time 15:02 Sent To  
Notes
2023-04-13 15:03:311ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23020122
 4/13/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE M PLANS ALL HAVE KEY PLANS SHOWING TWO AREAS OF
 WORK. TO HELP EXPEDITE THE REVIEW PLEASE LABEL THE
 ROOMS AND PLANS ACCORDING TO THE MECHANICAL SCHEDULES
 (M801 & M802) WHICH SHOW B-1&2 IN THE BOILER PLANT AND
 B-H-1 & 2 IN THE BOILER ROOM- SEC. 107.2.1 WPB. PLEASE
 NOTE THE BOILER LOCATIONS IN THE SAFETY RELIEF VALVE
 SCHEDULE DO NOT MATCH THE LOCATIONS IN THE EQUIPMENT
 SCHEDULES.
  
 2) M202: PLEASE PROVIDE A KEYNOTE WHICH SHOWS THE TYPES
 AND SIZES OF GAS PIPING SHOWN IN THE ENLARGED PLANS,
 AND PROVIDE A KEYNOTE WHICH REFERENCES THE LOCATION OF
 THE GAS TRAIN DETAIL. IT APPEARS TO BE DETAIL 6/M402.
 PLEASE PROVIDE THE SIZES OF GAS PIPING SHOWN IN THE
 DETAIL AND THE SYSTEM PRESSURES BEFORE AND AFTER THE
 REGULATORS (PRV'S)- SEC. 402.3 & 410.2 FBC FG. PLEASE
 NOTE A COMPLETE REVIEW CANNOT BE COMPLETED WITHOUT THE
 MBH OF B-1&2 WHICH IS NOT SHOWN LISTED IN THE SCHEDULE.
  
 3) M202: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 FOR B-1&2 AND PROVIDE CALCULATIONS- SEC. 304.1 FBC FG.
 NOTE 14 INDICATES A NEW SUPPLY FAN SAF-1 ON THE ROOF
 ABOVE THE BOILER PLANT. IS THIS THE SOURCE OF THE
 COMBUSTION AIR? PLEASE PROVIDE FURTHER DETAILS.
  
 4) M202: PROVIDE A BOILER VENTING DIAGRAM THAT SHOWS
 THE TYPE AND SIZE OF VENT FLUE, AND VENT FLUE RUN
 LENGTH FROM BOILER OUTLET TO TERMINATION CAP ABOVE THE
 ROOF- SECS. 502.5, 503.1, & 631.2 FBC FG.
  
 5) M202: PLEASE SHOW THE CLEARANCE DISTANCE
 MEASUREMENTS FROM THE BOILER FLUE OUTLETS TO THE SAF-1
 INTAKE- SEC. 501.3.1. FBC M.
  
 6) M802 & M803: PLEASE SHOW IN THE SCHEDULE NOTES FOR
 THE BOILERS THAT THEY ARE LISTED IN ACCORDANCE WITH THE
 REQUIREMENTS OF ANSI Z21.13/CSA 4.9 OR UL 795- SEC.
 631.1 FBC FG.
  
 7) M203: PLEASE PROVIDE A KEYNOTE WHICH SHOWS THE TYPES
 AND SIZES OF GAS PIPING SHOWN IN THE ENLARGED PLANS FOR
 H-B-1 & H-B-2, AND PROVIDE A KEYNOTE WHICH REFERENCES
 THE LOCATION OF THE GAS TRAIN DETAIL. IT APPEARS TO BE
 DETAIL 4/M403. PLEASE PROVIDE THE SIZES OF GAS PIPING
 SHOWN IN THE DETAIL AND THE SYSTEM PRESSURES BEFORE AND
 AFTER THE REGULATORS (PRV'S)- SEC. 402.3 & 410.2 FBC
 FG.
  
 8) M203: PLEASE INCLUDE ROOF DEMOLITION AND RENOVATION
 PLANS FOR THE BOILER ROOM AS WERE PROVIDED FOR THE
 BOILER PLANT ROOM- SEC. 107.2.1 WPB.
  
 9) M203 INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 FOR H-B-1 & H-B-2 AND PROVIDE CALCULATIONS- SEC. 304.1
 FBC FG.
  
 10) M203: PROVIDE A BOILER VENTING DIAGRAM THAT SHOWS
 THE TYPE AND SIZE OF VENT FLUE, AND VENT FLUE RUN
 LENGTH FROM BOILER OUTLET TO TERMINATION CAP ABOVE THE
 ROOF- SECS. 502.5, 503.1, & 631.2 FBC FG.
  
 11) M802 & M803: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR
 THE GAS REGULATORS- SEC. 410.2.
  
 12) M101: THE PLAN SHOWS AN EXISTING GAS LINE SUPPLYING
 A TEMPORARY STEAM BOILER. I WAS UNABLE TO LOCATE A
 PERMIT OR APPROVED PLANS FOR THE GAS PIPING AND
 TEMPORARY BOILER INSTALLATIONS. PLEASE PROVIDE COMPLETE
 PLANS AND DETAILS INCLUDING A GAS RISER DRAWING- SEC.
 107.3.5.1.5 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-15 Cont ID  
Sent By hmoser Date 2023-06-15 Time 10:44 Rev Time 0.00
Received By hmoser Date 2023-05-26 Time 15:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-21 Cont ID  
Sent By aoliver Date 2023-04-21 Time 08:16 Rev Time 0.00
Received By aoliver Date 2023-04-06 Time 12:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By hmoser Date 2023-06-15 Time 10:44 Rev Time 0.00
Received By hmoser Date 2023-06-15 Time 09:30 Sent To  
Notes
2023-06-15 10:44:02PASS PROVISO
 REFER TO SECTION 1011 TEST 2020 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-12 Cont ID  
Sent By medwards Date 2023-04-12 Time 16:05 Rev Time 0.00
Received By medwards Date 2023-04-12 Time 16:05 Sent To  
Notes
2023-04-12 16:05:301ST REVIEW FMC
 PERMIT: 23020122
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE ON THE MECHANICAL DEMO DRAWINGS, THE SIZES
 OF THE BOILERS BEING REPLACED ALONG WITH THE FUEL
 SOURCE FOR THESE EXISTING BOILERS. PROVIDE THE NEW
 BOILER SIZES AND FUEL TYPE ON THE NEW DESIGN DRAWINGS.
 FBC 107.3.5
  
 2) SHEET M801 INDICATES THAT THE FUEL SOURCE FOR B-1
 AND B-2 TO BE FUEL OIL. SHEET M704 HAS A NATURAL GAS
 DETECTOR DETAIL DRAWING. WHAT IS THIS FOR? IF IT
 ISN???T NEEDED PLEASE REMOVE. FBC 107.3.5
  
 3) PROVIDE THE COMBUSTION AIR CALCULATIONS FOR THESE
 BOILERS. FMC 701.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By ccole Date 2023-05-30 Time 14:13 Rev Time 0.00
Received By ccole Date 2023-05-30 Time 12:02 Sent To  
Notes
2023-05-30 14:19:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23020122
 5/30/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M202 & M203: PLEASE SHOW THE LOCATIONS OF
 REQUIRED POTABLE WATER BACKFLOW PREVENTERS FOR THE DCW
 SUPPLY LINES TO BOILERS AND ASSOCIATED EQUIPMENT- SEC.
 608.17.2 FBC P. PLEASE PROVIDE EQUIPMENT SCHEDULES FOR
 THE DEVICES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-04-13 Cont ID  
Sent By ccole Date 2023-04-13 Time 15:03 Rev Time 0.00
Received By ccole Date 2023-04-13 Time 08:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-30 Cont ID  
Sent By ccole Date 2023-05-30 Time 14:12 Rev Time 0.00
Received By ccole Date 2023-05-30 Time 14:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-13 Cont ID  
Sent By ccole Date 2023-04-13 Time 15:18 Rev Time 0.00
Received By ccole Date 2023-04-13 Time 15:18 Sent To  
Notes
2023-04-13 15:21:481ST SIGNATURE REVIEW
 PERMIT- 23020122
 4/13/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLANS DO NOT HAVE VERIFIABLE DIGITAL
 SIGNATURES AND SEALS BY THE ENGINEER OF RECORD AS
 REQUIRED BY FL. STATUTE 471.025, AND SECTION
 61G15-23.005 FAC. THE SIGNATURES ARE COPIES OF THE
 ORIGINALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2023-04-12 16:04:58MECHANICAL DIGITAL SIGNATURES ARE COPIES OF THE
 ORIGINAL. ME