Plan Review Details - Permit 23020116
Plan Review Stops For Permit 23020116
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 16:22 Rev Time 0.00
Received By rmcphers Date 2023-04-24 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-23 Cont ID  
Sent By rmcphers Date 2023-03-23 Time 15:43 Rev Time 0.00
Received By rmcphers Date 2023-03-23 Time 15:43 Sent To  
Notes
2023-03-23 15:43:45REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) JOB COST APPEARS TO BE LOW - JOB COST NEEDS TO
 INCLUDE ALL MATERIAL AND LABOR COST - PROVIDE A COST
 BREAK DOWN OF ALL MATERIAL AND LABOR - PLEASE REVISE
 THE BUILDING PERMIT APPLICATION SHOWING THE TOTAL COST.
 FBC WPB 109.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By rmcphers Date 2023-02-24 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2023-02-24 Time 11:28 Sent To  
Notes
2023-02-24 11:32:50REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) JOB COST APPEARS TO BE LOW - JOB COST NEEDS TO
 INCLUDE ALL MATERIAL AND LABOR COST - PROVIDE A COST
 BREAK DOWN OF ALL MATERIAL AND LABOR - PLEASE REVISE
 THE BUILDING PERMIT APPLICATION SHOWING THE TOTAL COST.
 FBC WPB 109.3

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2023-05-18 Cont ID  
Sent By mpeterso Date 2023-05-18 Time 08:24 Rev Time 0.00
Received By mpeterso Date 2023-05-18 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-05-04 Cont ID  
Sent By jleahy Date 2023-05-04 Time 16:47 Rev Time 0.00
Received By jleahy Date 2023-05-04 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-04-24 Cont ID  
Sent By mpeterso Date 2023-04-24 Time 11:58 Rev Time 0.00
Received By mpeterso Date 2023-04-24 Time 11:58 Sent To  
Notes
2023-04-24 12:24:19ELECTRIC REVIEW FAILED
  
 1) ELECTRICAL RESPONSE FROM ENGINEER OF RECORD STATES
 SHEET INCORRECTLY STATES THAT ALL NEW ELECTRIC IS
 INSTALLED. THIS PLAN REVIEWER FINDS NOTES STATING ONLY
 NEW ELECTRIC WORK IS IN STORAGE ROOM AND BEDROOM 1.
 PLEASE CORRECT AS APPLICABLE. FBC 107.2
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 2) ENGINEER OF RECORD STATES FURTHER AS FOLLOWS. PLEASE
 INDICATE ALL NEW ELECTRIC IS INSTALLED ON SHEET EP-1.
 PLEASE PROVIDE CLARITY AS TO WHAT THIS STATEMENT MEANS
 PLEASE CORRECT AS APPLICABLE. FBC 107.2
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 3) PLEASE PROVIDE AN ELECTRIC RISER DETAILING METER,
 DISCONNECTS, ELECTRIC PANELS, CONDUIT, CONDUCTOR AND
 OVERCURRENT PROTECTION SIZES. PLEASE INDICATE EQUIPMENT
 AS NEW OR EXISTING. NEC 215.5
  
 4) SHEET EP-1 STATES THER IS AN EXISTING REMOTE LAUNDRY
 STRUCTURE. A REVIEW OF PREVIOUS PERMITS AND PROPERTY
 APPRAISER RECORDS DO NOT DETAIL A REMOTE STRUCTURE ON
 THE PROPERTY. PLEASE PROVIDE DOCUMENTS DETAILING THE
 STRUCTURE WAS PERMITED . FBC 107.2
  
 5) IF THE REMOTE STRUCTURE WAS PERMITTED PLEASE DETAIL
 COMPLIANCE WITH NEC 225.30
  
 NEC 225.30 A BUILDING OR OTHER STRUCTURE THAT IS SERVED
 BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT
  
 6) IF THERE IS AN ADDITIONAL ELECTRIC PANEL AT THE
 REMOTE STRUCTURE PLEASE DETAIL THIS PANEL IN THE RISER
 DIAGRAM ALONG WITH THE REQUIRED GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER NEC 250.32
  
 NEC 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-27 Cont ID  
Sent By mpeterso Date 2023-03-27 Time 10:33 Rev Time 0.00
Received By mpeterso Date 2023-03-27 Time 10:33 Sent To  
Notes
2023-03-27 10:37:07ELECTRIC REVIEW FAILED
 PREVIOUS COMMENTS NOT ADDRESSED
 PLEASE INDICATE THE ELECTRICAL WIRING THAT WAS EXISTING
 AND ELECTRICAL WIRING THAT IS NEW.
 PLEASE PROVIDE A REASONABLE VALUE FOR THE PROJECT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By mpeterso Date 2023-02-09 Time 15:58 Rev Time 0.00
Received By mpeterso Date 2023-02-09 Time 15:58 Sent To  
Notes
2023-02-09 16:04:20ELECTRIC REVIEW FAILED
  
 1) SHEET A-3 DETAILS ALL NEW ELECTRIC HAS BEEN
 INSTALLED. PLEASE INDICATE ALL NEW ELECTRIC IS
 INSTALLED ON SHEET EP-1.
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL
  
 2) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-25 Cont ID  
Sent By asangele Date 2023-05-25 Time 12:40 Rev Time 0.00
Received By asangele Date 2023-05-25 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-18 Cont ID  
Sent By mpeterso Date 2023-05-18 Time 08:29 Rev Time 0.00
Received By mpeterso Date 2023-05-11 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 16:23 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-29 Cont ID  
Sent By asangele Date 2023-03-29 Time 13:25 Rev Time 0.00
Received By asangele Date 2023-03-29 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-24 Cont ID  
Sent By rmcphers Date 2023-02-24 Time 11:33 Rev Time 0.00
Received By rmcphers Date 2023-02-07 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 13:37 Rev Time 0.00
Received By medwards Date 2023-03-24 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By medwards Date 2023-02-13 Time 17:38 Rev Time 0.00
Received By medwards Date 2023-02-13 Time 17:38 Sent To  
Notes
2023-02-13 17:40:51PLEASE EXPLAIN THE AS BUILT PLANS. WHERE ARE THE DEOM
 PLANS, WHERE ARE THE ORIGINAL DESIGN PLANS? IT IS
 UNCLEAR AS TO WHAT HAS BEEN CHANGED AT THIS RESIDENCE.
 WHY IS THERE ONLY A MECHANICAL DESIGN FOR THE BEDROOM?
 PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL
 DESGN AT THIS RESIDENCE. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-05-15 Cont ID  
Sent By ccole Date 2023-05-15 Time 13:00 Rev Time 0.00
Received By ccole Date 2023-05-15 Time 12:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-23 Cont ID  
Sent By ccole Date 2023-03-23 Time 08:35 Rev Time 0.00
Received By ccole Date 2023-03-23 Time 08:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-08 Cont ID  
Sent By ccole Date 2023-02-08 Time 12:10 Rev Time 0.00
Received By ccole Date 2023-02-08 Time 11:36 Sent To  
Notes
2023-02-08 12:11:271ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23020116
 2/8/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET EP-1: THE PLUMBING DIAGRAMS DO NOT INDICATE
 THAT THE BUILDING DRAINS FOR THE LAUNDRY BUILDING AND
 FOR THE HOUSE HAVE AT LEAST ONE VENT PIPE EACH THAT
 EXTENDS TO THE OUTDOORS- SEC. P3102.1 FBC RES.
  
 2) EP-1: PROVIDE FIXTURE AND BRANCH DRAIN PIPE SIZES
 FOR THE KITCHEN SINK AND WASHING MACHINE- TABLES
 P3005.4.1 & P3201.7 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-18 Cont ID  
Sent By mpeterso Date 2023-05-18 Time 08:29 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-23 Cont ID  
Sent By rmcphers Date 2023-03-23 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2023-03-23 Time 15:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By mpeterso Date 2023-02-09 Time 16:05 Rev Time 0.00
Received By mpeterso Date 2023-02-09 Time 16:05 Sent To  
Notes
2023-02-09 16:07:18SIGNATURE REVIEW FAILED
  
 1) SHEET A-1 IS NOT DIGITALLY SIGNED AS REQUIRED.
 PLEASE CORRECT AS OUTLINED BELOW.
  
 DIGITALLY SUBMITTED DOCUMENTS ARE PREFERRED
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 5 Status P Date 2023-05-25 Cont ID  
Sent By asangele Date 2023-05-25 Time 12:40 Rev Time 0.00
Received By asangele Date 2023-05-25 Time 12:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2023-05-16 Cont ID  
Sent By asangele Date 2023-05-16 Time 15:48 Rev Time 0.00
Received By asangele Date 2023-05-16 Time 15:48 Sent To  
Notes
2023-05-16 16:04:41FAILED
 5/6/2023
  
 REPEAT COMMENT
  
 NEEDS TO PROVIDE PROPERTY SURVEY WITH APPLICATION
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-04-24 Cont ID  
Sent By asangele Date 2023-04-24 Time 16:11 Rev Time 0.00
Received By asangele Date 2023-04-24 Time 16:11 Sent To  
Notes
2023-04-24 16:15:09FAILED
 4/24/2023
  
 REPEAT COMMENT
  
 PROPERTY IS LOCATED IN SINGLE FAMILY ZONING CANNOT HAVE
 AN ADDITIONAL UNIT.
 A 220 VOLT CANNOT BE INSTALLED BECAUSE YOU WOULD NOT BE
 ALLOWED TO HAVE A STOVE IN THE SPACE.
  
 PLANS ARE STILL INDICATING A 220 VOLT OUTET ON
 MECHANICAL PLAN
  
 ACCESORY STRUCTURE DOES NOT MEET MIMIMUM SETBACK
 REQUIREMENTS
 SIDE SETBACK 5FT
 REAR SETBACK 5FT
  
 NEEDS TO PROVIDE PROPERTY SURVEY WITH APPLICATION
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-29 Cont ID  
Sent By asangele Date 2023-03-29 Time 13:21 Rev Time 0.00
Received By asangele Date 2023-03-29 Time 13:21 Sent To  
Notes
2023-03-29 13:25:42FAILED
 3/29/2023
  
 REPEAT COMMENT
  
 PROPERTY IS LOCATED IN SINGLE FAMILY ZONING CANNOT HAVE
 AN ADDITIONAL UNIT.
 A 220 VOLT CANNOT BE INSTALLED BECAUSE YOU WOULD NOT BE
 ALLOWED TO HAVE A STOVE IN THE SPACE.
  
 PLANS ARE STILL INDICATING A 220 VOLT OUTET ON
 MECHANICAL PLAN
  
 ACCESORY STRUCTURE DOES NOT MEET MIMIMUM SETBACK
 REQUIREMENTS
 SIDE SETBACK 5FT
 REAR SETBACK 5FT
  
 NEEDS TO PROVIDE PROPERTY SURVEY WITH APPLICATION
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By asangele Date 2023-02-13 Time 13:53 Rev Time 0.00
Received By asangele Date 2023-02-13 Time 13:53 Sent To  
Notes
2023-02-13 13:57:43FAILED
 2/13/2023
  
 PROPERTY IS LOCATED IN SINGLE FAMILY ZONING CANNOT HAVE
 AN ADDITIONAL UNIT.
 A 220 VOLT CANNOT BE INSTALLED BECAUSE YOU WOULD NOT BE
 ALLOWED TO HAVE A STOVE IN THE SPACE.
  
 ACCESORY STRUCTURE DOES NOT MEET MIMIMUM SETBACK
 REQUIREMENTS
 SIDE SETBACK 5FT
 REAR SETBACK 5FT
  
 NEEDS TO PROVIDE PROPERTY SURVEY WITH APPLICATION
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]