| 2023-03-28 11:02:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23011451 |
| | ADD: 1805 N FLAGLER DR # 219 |
| | CONT: PM BUILDERS |
| | TEL: 561-425-8525 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MARCH 28TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THE SHEET A1 DEMO PLAN NOTE # 7 STATES |
| | REMOVE EXISTING FLOORING AS SHOWN. SHEETA2 THE PROPOSED |
| | FLOOR PLAN. NOTE ON THE PLAN STATES NEW FLOOR MATERIAL |
| | PICKED BY OWNER. CONTRACTOR LETTER PROVIDES PORCELAIN |
| | PLANK TILE, BUT NOT REVIEWED BY THE DESIGNER OF RECORD |
| | FOR AREVIEW. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | 3-22-2023 SUBMITTED TEST REPORT FOR PROFLEX MSC 90 8.0 |
| | INCH SLAB, NO DROPPED CEILING. 1801-1805 N. FLAGLER DR. |
| | HAVE 7 INCH SLABS ( PERMIT 99040411) NOT 8 INCH SLABS, |
| | PROFLEX MSC 90 HAS NO TEST FOR 6 INCH SLABS , NOR FLAME |
| | SPREAD. |
| | |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 1A) 2ND REVIEW. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 1B) 2N REVIEW. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) 2ND REVIEW. FLAME SPREAD- FBC-B 2020 603.1. |
| | EXCEPTION 2. (TILE & MARBLE) INSULATION INSTALLED |
| | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | OR |
| | 1C) 2ND REVIEW. FBC-B 804.4.4.1 SOFT FLOOR FINISHES |
| | (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING) |
| | WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 |
| | ???PILL TEST??? (CPSC 16 CFR PART 1630) OR WITH ASTM |
| | D2859. |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253. |
| | |
| | 2) NEW COMMENT. SHEET A-2 TYPICAL DROPPED SOFFIT HAS |
| | NOT PROVIDED THE TYPE OF ANCHOR AND SPACING OF ANCHOR |
| | OR DEPTH OF ANCHOR TO THE CONCRETE DECK ABOVE THIS A |
| | GENERIC DETAIL AND STATES THE CONTRACTOR IS TO INSTALL |
| | METAL FRAMING AS PER GYPSUM CONSTRUCTION HANDBOOK THE |
| | DESIGN PROFESSIONAL HAS TO TAKE OWNERSHIP, THIS MAY |
| | ALSO BE OUT OF THE INTERIOR DESIGNER LICENSE SCOPE. FS |
| | 481.2131. |
| | THE SAME HOLDS TRUE FOR PIPES THAT PENETRATE FIRE RATED |
| | WALLS (2020 FBC-BUILDING 714.3) AND PENETRATIONS, FIRE |
| | RESISTANCE RATED ASSEMBLIES, (FBC-BUILD. 714.3.1.1). |
| | MEMBRANE PENETRATIONS (2020 FBC-BUILD. 714.3.2). |
| | A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |