Plan Review Details - Permit 23011254
Plan Review Stops For Permit 23011254
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-02-13 Cont ID  
Sent By jwitmer Date 2023-02-13 Time 12:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-02-13 Cont ID  
Sent By jwitmer Date 2023-02-13 Time 13:00 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-08 Cont ID  
Sent By pleduc Date 2023-02-08 Time   Rev Time 0.00
Received By pleduc Date 2023-02-08 Time 15:12 Sent To  
Notes
2023-02-08 15:14:212/8/23
  
 RECEIVED AN EMAIL FROM MARGARITA TRINIDAD, FLORIDA
 NOTARY PUBLIC, JMT SOLUTIONS LLC, STATING THE TILE WILL
 BE PORCELAIN.
  
 FIRE REVIEW PASSED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By pleduc Date 2023-02-01 Time   Rev Time 0.00
Received By pleduc Date 2023-02-01 Time 14:32 Sent To  
Notes
2023-02-01 14:38:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED TILE FLOORING.
  
 TILE FLOORING CAN HAVE DIFFERNET MEANING/DESCRIPTIONS
 AND IS MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE
 TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED AND PROVIDE A NOTE ON THE FLOOR
 PLAN THE TYPE.
  
 OR, IF IT IS PROPOSED TO BE LVT, VINYL FLOORING,
 WOOD/VINYL LAMINATES, ETC., PLEASE PROVIDE TH PRODUCT
 SPEC SHEETS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-13 Cont ID  
Sent By jwitmer Date 2023-02-13 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 17:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***