Plan Review Details - Permit 23011125
Plan Review Stops For Permit 23011125
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-26 Cont ID  
Sent By jgomez Date 2023-05-26 Time 09:35 Rev Time 0.00
Received By jgomez Date 2023-05-26 Time 09:35 Sent To  
Notes
2023-05-26 09:35:39RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011125
 214 LINDA LN
  
 1- REVISE ENGINEER CALCULATIONS SUBMITTED:
 A) THE NAIL FASTENING SPACING SPECIFIED BY THE ENGINEER
 DOESN'T MATCH THE NAIL FASTENING SPACING LISTED IN THE
 NOA 18-0919.12 ON PAGE 55 OF 67 FOR A MAXIMUM DESIGN
 PRESSURES OF -52.5PSF. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 B)THE ROOF ZONES DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER ARE TOO LOW. IT LOOKS LIKE ENGINEER IS USING
 ASCE-7-10 INSTEAD OF CURRENT ASCE-7-16. REVISE AS
 REQUIRED. SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 C)ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR ALL 4
 NEW ROOF ZONES.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 D)ENGINEER TO REVISE THE PERIMETER WIDTH DIMENSION AND
 THE CORNER ZONES DIMENSIONS. SEE ASCE 7-16 AND REVISE
 AS REQUIRED.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-15 Cont ID  
Sent By jgomez Date 2023-05-15 Time 11:09 Rev Time 0.00
Received By jgomez Date 2023-05-15 Time 09:29 Sent To  
Notes
2023-05-15 11:09:26RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011125
 214 LINDA LN
  
 1- REVISE ENGINEER CALCULATIONS SUBMITTED:
 A) THE NAIL FASTENING SPACING SPECIFIED BY THE ENGINEER
 DOESN'T MATCH THE NAIL FASTENING SPACING LISTED IN THE
 NOA 18-0919.12 ON PAGE 55 OF 67 FOR A MAXIMUM DESIGN
 PRESSURES OF -52.5PSF. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)THE ROOF ZONES DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER ARE TOO LOW. IT LOOKS LIKE ENGINEER IS USING
 ASCE-7-10 INSTEAD OF CURRENT ASCE-7-16. REVISE AS
 REQUIRED. SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 C)ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR ALL 4
 NEW ROOF ZONES.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 D)ENGINEER TO REVISE THE PERIMETER WIDTH DIMENSION AND
 THE CORNER ZONES DIMENSIONS. SEE ASCE 7-16 AND REVISE
 AS REQUIRED.
 SEC. R301.2.1.1 FBC-RESIDENTIAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By jbrooks Date 2023-04-04 Time 11:39 Rev Time 0.00
Received By jbrooks Date 2023-04-04 Time 08:05 Sent To  
Notes
2023-04-04 11:39:58JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA
 NO.: 18-0919.12 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED CORRESPONDING TO ENGINEERS CALCULATIONS. PAGES #1
 & #2, INSTALLATION INSTRUCTIONS FOR SYSTEM E (3)
 PAGE(S) #55 & #56 AND LIMITATIONS PAGE(S) #67. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER; TO CORRECT EXPOSURE
 CATEGORY, DESIGN PRESSURES & NAILING PATTERNS. THE
 EXPOSURE CATEGORY FOR 214 LINDA LN WEST PALM BEACH, FL
 33405 IS EXPOSURE CATEGORY D.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN
 ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-26 Cont ID  
Sent By jgomez Date 2023-05-26 Time 10:06 Rev Time 0.00
Received By jgomez Date 2023-05-26 Time 09:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-15 Cont ID  
Sent By jgomez Date 2023-05-15 Time 11:09 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 09:47 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-04 Cont ID  
Sent By jbrooks Date 2023-04-04 Time 11:40 Rev Time 0.00
Received By jbrooks Date 2023-04-03 Time 12:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-26 Cont ID  
Sent By jgomez Date 2023-05-26 Time 09:36 Rev Time 0.00
Received By jgomez Date 2023-05-26 Time 09:36 Sent To  
Notes
2023-05-26 09:37:31CALCULATIONS HAVE ENGINEER'S EMBOSSED SEAL AND WET
 SIGNATURE DATED 5-15-23. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 10:52 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 10:51 Sent To  
Notes
2023-05-09 10:54:11CALCULATIONS HAVE ENGINEER'S EMBOSSED SEAL AND WET
 SIGNATURE DATED 4/4/23. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By jbrooks Date 2023-04-04 Time 11:34 Rev Time 0.00
Received By jbrooks Date 2023-04-04 Time 11:33 Sent To  
Notes
2023-04-04 11:34:36JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS IS A COPY OF A WET SIGNATURE. PLEASE
 UPLOAD A VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  