Plan Review Details - Permit 23011089
Plan Review Stops For Permit 23011089
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-02-23 Cont ID  
Sent By cpuell Date 2023-02-23 Time 11:52 Rev Time 0.00
Received By cpuell Date 2023-02-23 Time 11:52 Sent To  
Notes
2023-02-23 11:52:47APPLICANT PROVIDED SITE PLAN. ADDRESS APPROPRIATE FOR
 PROJECT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By cpuell Date 2023-02-15 Time 16:49 Rev Time 0.00
Received By cpuell Date 2023-02-15 Time 16:48 Sent To  
Notes
2023-02-15 16:49:42PLEASE PROVIDE A SITE PLAN OR AERIAL MAP SHOWING THE
 EXACT BUILDING TO BE WORKED ON. PLEASE EMAIL RESPONSE
 TO [email protected] OR CALL 561-805-6659.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2023-06-01 Time 15:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2023-04-24 Time 14:31 Sent To  
Notes
2023-04-24 14:33:12THE ASBESTOS SURVEY IS NOT REQUIRED - THE LETTER FROM
 THE CONTRACTOR IS REQUIRED.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By rmcphers Date 2023-03-10 Time 11:52 Rev Time 0.00
Received By rmcphers Date 2023-03-10 Time 11:52 Sent To  
Notes
2023-03-10 11:53:27PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2023-06-01 Time 15:01 Sent To  
Notes
2023-06-01 15:03:22HOSPITAL REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL
 FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787)
 - (FL4553)
  
 2) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
 I CHECK THE ELECTRONIC SIGNATURE FOR THE DRAWINGS
 UPLOADED TO PROJECTDOX BY OPENING THEM IN ???ADOBE
 READER???. THE ???ADOBE READER??? STATES WHETHER THEY
 ARE AN ORIGINAL ELECTRONICALLY SIGNED DOCUMENT. WHEN
 ELECTRONICALLY SIGNED DRAWINGS ARE PRINTED OUT, THEY
 LOSE THEIR ELECTRONIC SIGNATURE. ELECTRONICALLY SIGNED
 DRAWINGS NEED TO BE MOVED AROUND IN THE COMPUTER FROM
 PLACE TO PLACE. FROM THE ARCHITECT???S OR ENGINEER???S
 COMPUTER TO YOUR COMPUTER TO THE CITY???S ELECTRONIC
 PLAN REVIEW (PROJECTDOX). MAYBE YOURS WERE PRINTED OUT
 AT SOME TIME?
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 14:28 Rev Time 0.00
Received By rmcphers Date 2023-04-24 Time 13:39 Sent To  
Notes
2023-04-24 14:01:13HOSPITAL REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10
 SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD
 MATCH.
  
 2) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL
 FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787)
 - (FL4553) - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD
 FBC WPB 107.3.4
  
 3) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS
 ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT
 SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A
 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY.
 IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT
 AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING
 ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH
 805.
  
 4) PLEASE SHOW THE FIRE RATED CEILING ASSEMBLY DESIGN
 NUMBER - FBC 703.3
  
 5) PLEASE SHOW THE FIRE RATED WALL ASSEMBLY DESIGN
 NUMBER ON THE WALL SCHEDULE - FBC 703.3
  
 6) CANNOT FIND THE DOOR HARDWARE SET DESCRIPTIONS - FBC
 WPB 107.2.1
  
 7) THE PLYWOOD ADDED TO THE EXTERIOR WALLS SHOULD BE
 FIRE RETARDANT PER FBC 602.3
  
 8) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By rmcphers Date 2023-03-10 Time 12:09 Rev Time 0.00
Received By rmcphers Date 2023-03-09 Time 12:29 Sent To  
Notes
2023-03-10 11:30:20HOSPITAL REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING G0.00 - UNDER "PROJECT INFORMATION" SHOWS
 RISK CATEGORY IV AND A WIND SPEED OF 178MPH - WIND
 SPEED SHOULD BE 180MPH PER FBC WPB SECTION 120.
  
 2) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10
 SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD
 MATCH.
  
 3) DRAWING G0.00 - UNDER "PROJECT INFORMATION" THE FIRE
 RATINGS SHOULD BE SHOWN PER FBC TABLE 601 FOR A
 CONSTRUCTION TYPE III A.
  
 4) DRAWINGS SHOW OCCUPANCY TYPE "I 2" PLEASE SHOW IF
 CONDITION 1 OR CONDITION 2 - FBC 308.4
  
 5) PLEASE SHOW THE CORRIDOR WALLS TO BE SMOKE
 PARTITIONS PER FBC 407.3
 407.2 CORRIDORS CONTINUITY AND SEPARATION.
 CORRIDORS IN OCCUPANCIES IN GROUP I-2 SHALL BE
 CONTINUOUS TO THE EXITS AND SHALL BE SEPARATED FROM
 OTHER AREAS IN ACCORDANCE WITH SECTION 407.3 EXCEPT
 SPACES CONFORMING TO SECTIONS 407.2.1 THROUGH 407.2.6.
  
 6) PLEASE SHOW SMOKE PARTITION DETAILS PER FBC 710.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
  
 7) WALLS SURROUNDING THE LAUNDRY ROOM (1209) ARE SHOWN
 TO BE FIRE RATED BUT THE DOOR IS NOT - PLEASE CLARIFY
 FBC TABLE 716.5
  
 8) PLEASE SHOW THE PUBLIC RESTROOM WALL AND BASE BOARD
 FINISHES TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 9) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS FOR THE
 INTERIOR FINISHES - FBC 803.11 INTERIOR FINISH
 REQUIREMENTS BASED ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.11 FOR THE GROUP AND LOCATION DESIGNATED.
  
 10) DRAWING A5.10 SHOWS A VAPER BARRIER AND FIRE
 SEPARATION AT THE ROOF TRUSSES - PLEASE CLARIFY - WHAT
 TYPE OF VAPER BARRIER AND THE HOURLY FIRE RATING -
 PLEASE PROVIDE DETAILS - ROOF VENTILATION MAY BE NEEDED
 PER FBC 1203.2 VENTILATION REQUIRED. ENCLOSED ATTICS
 AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING
 MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATION OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN AND SNOW. BLOCKING AND BRIDGING SHALL
 BE ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF
 AIR. AN AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL
 BE PROVIDED BETWEEN THE INSULATION AND THE ROOF
 SHEATHING. THE NET FREE VENTILATING AREA SHALL BE NOT
 LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED.
  
 11) DRAWING A5.10 SHOW A FIRE SEPARATION AT THE ROOF
 TRUSSES - PLEASE CLARIFY - SHOW THE HOURLY FIRE RATING
 ASSEMBLY - PLEASE PROVIDE DETAILS - FBC 708.4
 CONTINUITY.
 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO.
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC
 WPB 107.3.4
  
 13) PLEASE SHOW THE WATER DRAINAGE FROM THE CANOPY ROOF
 SYSTEM - FBC 1503.7 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS.
 FBC 1808.7.4 "REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE".
  
 14) THE VERTICAL TOILET GRAB BAR IS NOT A REQUIREMENT
 IN THE FBC - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE
 THE GRAB BARS - FBC A 609.3 THE SPACE BETWEEN THE GRAB
 BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES
 (305 MM) MINIMUM.
  
 15) ACCESSIBLE RESTROOM = WHEN REFERRING TO THE
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR
 PLEASE USE THE WORDS "REFLECTIVE SURFACE" - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 16) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS
 ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT
 SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A
 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY.
 IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT
 AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING
 ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH
 805.
  
 17) PLEASE SHOW THE INCIDENTAL ROOMS (LAUNDRY, STORAGE,
 PATIENT ROOMS EQUIPPED WITH PADDED SURFACES, PHYSICAL
 PLANT MAINTENANCE SHOPS, WASTE AND LINEN COLLECTION,
 ETC) TO BE FIRE RATED PER FBC SECTION 509 - TABLE 509
 --- 509.4.1SEPARATION. WHERE TABLE 509 SPECIFIES A
 FIRE-RESISTANCE-RATED SEPARATION, THE INCIDENTAL USES
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY A FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH.
  
 18) SEPARATE PERMITS ARE REQUIRED FOR - GENERATOR,
 GENERATOR ENCLOSURE, OUTDOOR CANOPIES, PARKING LOT,
 FENCES.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By fgiaquin Date 2023-06-21 Time 12:03 Rev Time 0.00
Received By fgiaquin Date 2023-06-21 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By fgiaquin Date 2023-04-19 Time 19:44 Rev Time 0.00
Received By fgiaquin Date 2023-04-18 Time 20:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-27 Cont ID  
Sent By fgiaquin Date 2023-02-27 Time 20:17 Rev Time 0.00
Received By fgiaquin Date 2023-02-13 Time 20:00 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-02-13 Cont ID  
Sent By rrossano Date 2023-02-13 Time   Rev Time 0.00
Received By rrossano Date 2023-02-13 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-31 Cont ID  
Sent By clfranci Date 2023-05-31 Time   Rev Time 0.00
Received By clfranci Date 2023-05-31 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-04-17 Cont ID  
Sent By clfranci Date 2023-04-17 Time   Rev Time 0.00
Received By clfranci Date 2023-04-17 Time   Sent To  
Notes
2023-04-17 13:37:11THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 THE COMMENTS BELOW ARE REPEATED COMMENTS FROM THE FIRST
 REVIEW, NO RESPONSES WERE FOUND IN THE DOCUMENTS
 SUBMITTED RESPONDING TO THE COMMENTS BELOW.
  
 1) ON THE COVER SHEET YOU REFERENCE 2020 NATIONAL FIRE
 CODE AND THE MOST CURRENT IS NFPA 2018.
  
 2) IN REFERENCE TO NPFA 101 CHAPTER 18 TABLE 18.1.6.1,
 WHAT CLASSIFICATION WOULD YOU SELECT TO APPLY TOWARD
 YOUR CONSTRUCTION TYPE?
  
 3) WHAT IS THE RATING OF THE FIRE SEPARATION INDICATED
 ON 016 A5.00?
  
 4) PLEASE CLARIFY THE PERCENTAGE OF REHABILITATION
 BEING DONE IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.1.1.4.3 REHABILITATION.
 18.1.1.4.3.1 FOR PURPOSES OF THE PROVISIONS OF THIS
 CHAPTER, THE FOLLOWING
 SHALL APPLY:
 (1) A MAJOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF MORE THAN
 50 PERCENT, OR MORE THAN 4500 FT2 (420 M2), OF THE AREA
 OF THE SMOKE
 COMPARTMENT.
 (2) A MINOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF NOT MORE THAN 50 PERCENT, AND NOT MORE
 THAN 4500 FT2 (420 M2), OF THE AREA OF THE SMOKE
 COMPARTMENT.
  
 5) PROVIDE THE HORIZONTAL EXIT CAPACITY AND TOTAL
 EGRESS CAPACITY OF ANY OTHER EXITS FOR EACH COMPARTMENT
 IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING
 WITH 7.2.4 AND
 THE MODIFICATIONS OF 18.2.2.5.1 THROUGH 18.2.2.5.7
 SHALL BE PERMITTED.
 18.2.2.5.1 ACCUMULATION SPACE SHALL BE PROVIDED IN
 ACCORDANCE WITH
 18.2.2.5.1.1 AND 18.2.2.5.1.2.
 18.2.2.5.1.1 NOT LESS THAN 30 NET FT2 (2.8 NET M2) PER
 PATIENT IN A HOSPITAL
 OR NURSING HOME, OR NOT LESS THAN 15 NET FT2 (1.4 NET
 M2) PER RESIDENT IN
 A LIMITED CARE FACILITY, SHALL BE PROVIDED WITHIN THE
 AGGREGATED AREA OF
 CORRIDORS, PATIENT ROOMS, TREATMENT ROOMS, LOUNGE OR
 DINING AREAS, AND
 OTHER SIMILAR AREAS ON EACH SIDE OF THE HORIZONTAL
 EXIT.
 18.2.2.5.1.2 ON STORIES NOT HOUSING BEDRIDDEN OR
 LITTERBORNE PATIENTS,
 NOT LESS THAN 6 NET FT2 (0.56 NET M2) PER OCCUPANT
 SHALL BE PROVIDED ON
 EACH SIDE OF THE HORIZONTAL EXIT FOR THE TOTAL NUMBER
 OF OCCUPANTS IN
 ADJOINING COMPARTMENTS.
 18.2.2.5.2 THE TOTAL EGRESS CAPACITY OF THE OTHER EXITS
 (STAIRS, RAMPS,
 DOORS LEADING OUTSIDE THE BUILDING) SHALL NOT BE
 REDUCED BELOW ONE-THIRD
 OF THAT REQUIRED FOR THE ENTIRE AREA OF THE BUILDING.
  
 6) PLEASE PROVED THE MEASUREMENT OF THE WIDTH OF THE
 CORRIDORS PER NFPA 101 CHAPTER 18, 18.2.3.4.
  
 7) PLEASE PROVIDE THE MEASUREMENT OF THE DOOR WIDTH PER
 NFPA 101 CHAPTER 18,
 18.2.3.6 THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS
 OF EGRESS
 FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS,
 SUCH AS X-RAY,
 SURGERY, OR PHYSICAL THERAPY; AND NURSERY ROOMS SHALL
 BE AS FOLLOWS:
 (1) HOSPITALS AND NURSING HOMES ??? 411???2 IN. (1055
 MM)
 (2) PSYCHIATRIC HOSPITALS AND LIMITED CARE
 FACILITIES??? 32 IN. (810 MM)
  
 8) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT
  
  
 9) NO COMMON PATH OF TRAVEL WAS INDICATED ON THE PLANS.
  
  
  
 10) COMPARTMENT D HAS MULTIPLE EGRESS PATHS MARKED
 GOING THROUGH INTERVENING ROOMS OR SPACES WHICH IS NOT
 ALLOWED PER NFPA 101 CHAPTER 18,
  
 18.2.5.4* INTERVENING ROOMS OR SPACES. EVERY CORRIDOR
 SHALL PROVIDE
 ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN
 ACCORDANCE WITH SECTIONS
 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING
 ROOMS OR
 SPACES OTHER THAN CORRIDORS OR LOBBIES.
 A.18.2.5.4 THE TERM INTERVENING ROOMS OR SPACES MEANS
 ROOMS OR
 SPACES SERVING AS A PART OF THE REQUIRED MEANS OF
 EGRESS FROM ANOTHER ROOM.
  
 11) PLEASE ENSURE THAT THE SLEEPING SUITE TRAVEL
 DISTANCE IS IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.5.7.2.4 SLEEPING SUITE TRAVEL DISTANCE.
 (A) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 ACCESS DOOR TO ANOTHER SUITE, AN EXIT ACCESS CORRIDOR
 DOOR, OR A HORIZONTAL
 EXIT DOOR FROM THAT SUITE SHALL NOT EXCEED 100 FT (30
 M).
 (B) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 SHALL NOT EXCEED 200 FT (61 M).
  
 12) ACCORDING TO THE FOLLOWING CODE NOT LESS THEN TWO
 EXITS ARE REQUIRED. PLEASE INDICATE THE EXITS FROM EACH
 AREA AND THE TRAVEL DISTANCE FOR BOTH.
 18.2.4 NUMBER OF MEANS OF EGRESS.
 18.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 18.2.4.2 NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
 EVERY STORY.
 18.2.4.3 NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 18.2.4.4* EXITS FROM SMOKE COMPARTMENTS.
 A.18.2.4.4 AN EXIT IS NOT NECESSARY FOR EACH INDIVIDUAL
 SMOKE COMPARTMENT
 IF THERE IS ACCESS TO AN EXIT THROUGH OTHER SMOKE
 COMPARTMENTS
 WITHOUT PASSING THROUGH THE SMOKE COMPARTMENT OF FIRE
 ORIGIN.
 18.2.4.4.1 NOT LESS THAN TWO EXITS SHALL BE ACCESSIBLE
 FROM EACH SMOKE
 COMPARTMENT, AND EGRESS SHALL BE PERMITTED THROUGH AN
 ADJACENT
 COMPARTMENT(S), PROVIDED THAT THE TWO REQUIRED EGRESS
 PATHS ARE ARRANGED
 SO THAT BOTH DO NOT PASS THROUGH THE SAME ADJACENT
 SMOKE
 COMPARTMENT.
 18.2.4.4.2 A DOOR IN A SMOKE BARRIER SHALL NOT SERVE AS
 THE ONLY EXIT
 ACCESS FROM ANY SPACE IN A SMOKE COMPARTMENT.
  
  
  
 13) THE MOUNTING OF EMERGENCY EXIT SIGNS MUST BE OVER
 THE DOOR IN WHICH THE EGRESS PATHWAY GOES PER NFPA 101
 CHAPTER 7, 7.10.1.9 MOUNTING LOCATION
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 14) ROOM 1316 (HOUSE KEEPING STORAGE), 1035
 (MAINTENANCE SHOP) AND ALL SOILED ROOMS DO NOT SHOW
 FIRE RESISTANCE RATING. IF THESE ROOMS MEET THE
 REQUIREMENTS IN THE FOLLOWING CODE FROM NFPA 101
 CHAPTER 18 THEY MUST HAVE FIRE RESISTANCE RATING OR
 SMOKE PARTITIONS.
 18.3.2.1.2THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE RESISTANCE
 RATING IN ACCORDANCE WITH SECTION 8.3:
 (1) BOILER AND FUEL-FIRED HEATER ROOMS
 (2) CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)
 (3) PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND
 MATERIALS IN QUANTITIES
 LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE
 HAZARD
 (4) PHYSICAL PLANT MAINTENANCE SHOPS
 (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL
 (242 L)
 (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64
 GAL (242 L)
 (7) STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND
 STORING COMBUSTIBLE
 MATERIAL
 18.3.2.1.3 THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY SMOKE PARTITIONS IN ACCORDANCE
 WITH SECTION 8.4:
 (1) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE
 MATERIALS IN
 QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A
 SEVERE
 HAZARD
 (2) STORAGE ROOMS LARGER THAN 50 FT2 (4.6 M2) BUT NOT
 EXCEEDING 100 FT2
 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL
 (9.4
  
 15) IT IS INDICATED YOU ARE INSTALLING VINYL AND
 CARPET FLOORING. ALL FLOORING MUST HAVE SPECS SUBMITTED
 FOR REVIEW.
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 16) ON SHEET 047 AC1.03 THERE ARE DIFFERENT LEVELS OF
 SECURITY. PLEASE INDICATE THE TYPE OF DOOR CLOSING OR
 LOCKING MECHANISMS ON EACH LEVEL OF SECURITY. HOW DO
 PATIENTS EGRESS IN A FIRE EMERGENCY?
  
  
  
  
  
 17) PLEASE ENSURE THAT THE SLEEPING SUITE SUPERVISION
 MEETS THE REQUIREMENTS OF NFPA 101 CHAPTER 18,
 18.2.5.7.2.1 SLEEPING SUITE SUPERVISION.
 (A) SLEEPING SUITES SHALL BE PROVIDED WITH CONSTANT
 STAFF SUPERVISION
 WITHIN THE SUITE.
 (B)* SLEEPING SUITES SHALL BE ARRANGED IN ACCORDANCE
 WITH ONE OF THE
 FOLLOWING:
 (1)* PATIENT SLEEPING ROOMS WITHIN SLEEPING SUITES
 SHALL PROVIDE ONE OF
 THE FOLLOWING:
 (A) THE PATIENT SLEEPING ROOMS SHALL BE ARRANGED TO
 ALLOW FOR
 DIRECT SUPERVISION FROM A NORMALLY ATTENDED LOCATION
 WITHIN
 THE SUITE, SUCH AS IS PROVIDED BY GLASS WALLS, AND
 CUBICLE CURTAINS
 SHALL BE PERMITTED.
 (B) ANY PATIENT SLEEPING ROOMS WITHOUT THE DIRECT
 SUPERVISION
 REQUIRED BY 18.2.5.7.2.1(B)(1)(A) SHALL BE PROVIDED
 WITH
 SMOKE DETECTION IN ACCORDANCE WITH SECTION 9.6 AND
 18.3.4.
 (2) SLEEPING SUITES SHALL BE PROVIDED WITH A TOTAL
 (COMPLETE) COVERAGE
 AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH
 9.6.2.9 AND
 18.3.4
  
 18) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 19) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 20) IF ACCESS CONTROL IS BEING UPDATED OR ADDED THERE
 MUST BE A PERMIT AND PLAN SUBMITTED SEPARATELY.
  
 21) IF THE HOOD SYSTEM/ HOOD SUPPRESSION IS BEING
 UPDATED OR ADDED THERE MUST BE A PERMIT AND PLAN
 SUBMITTED SEPARATELY.
  
 ALL RESPONSES SHOULD BE IN A NARRATIVE FORM AND ANY AND
 ALL CHANGES MUST B CLOUDED ON THE PLANS FOR RESUBMITTAL
 VIA BUILDING DEPARTMENT.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By clfranci Date 2023-02-09 Time   Rev Time 0.00
Received By clfranci Date 2023-02-09 Time   Sent To  
Notes
2023-02-09 12:40:48THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 1) ON THE COVER SHEET YOU REFERENCE 2020 NATIONAL FIRE
 CODE AND THE MOST CURRENT IS NFPA 2018.
  
 2) IN REFERENCE TO NPFA 101 CHAPTER 18 TABLE 18.1.6.1,
 WHAT CLASSIFICATION WOULD YOU SELECT TO APPLY TOWARD
 YOUR CONSTRUCTION TYPE?
  
 3) WHAT IS THE RATING OF THE FIRE SEPARATION INDICATED
 ON 016 A5.00?
  
 4) PLEASE CLARIFY THE PERCENTAGE OF REHABILITATION
 BEING DONE IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.1.1.4.3 REHABILITATION.
 18.1.1.4.3.1 FOR PURPOSES OF THE PROVISIONS OF THIS
 CHAPTER, THE FOLLOWING
 SHALL APPLY:
 (1) A MAJOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF MORE THAN
 50 PERCENT, OR MORE THAN 4500 FT2 (420 M2), OF THE AREA
 OF THE SMOKE
 COMPARTMENT.
 (2) A MINOR REHABILITATION SHALL INVOLVE THE
 MODIFICATION OF NOT MORE THAN 50 PERCENT, AND NOT MORE
 THAN 4500 FT2 (420 M2), OF THE AREA OF THE SMOKE
 COMPARTMENT.
  
 5) PROVIDE THE HORIZONTAL EXIT CAPACITY AND TOTAL
 EGRESS CAPACITY OF ANY OTHER EXITS FOR EACH COMPARTMENT
 IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING
 WITH 7.2.4 AND
 THE MODIFICATIONS OF 18.2.2.5.1 THROUGH 18.2.2.5.7
 SHALL BE PERMITTED.
 18.2.2.5.1 ACCUMULATION SPACE SHALL BE PROVIDED IN
 ACCORDANCE WITH
 18.2.2.5.1.1 AND 18.2.2.5.1.2.
 18.2.2.5.1.1 NOT LESS THAN 30 NET FT2 (2.8 NET M2) PER
 PATIENT IN A HOSPITAL
 OR NURSING HOME, OR NOT LESS THAN 15 NET FT2 (1.4 NET
 M2) PER RESIDENT IN
 A LIMITED CARE FACILITY, SHALL BE PROVIDED WITHIN THE
 AGGREGATED AREA OF
 CORRIDORS, PATIENT ROOMS, TREATMENT ROOMS, LOUNGE OR
 DINING AREAS, AND
 OTHER SIMILAR AREAS ON EACH SIDE OF THE HORIZONTAL
 EXIT.
 18.2.2.5.1.2 ON STORIES NOT HOUSING BEDRIDDEN OR
 LITTERBORNE PATIENTS,
 NOT LESS THAN 6 NET FT2 (0.56 NET M2) PER OCCUPANT
 SHALL BE PROVIDED ON
 EACH SIDE OF THE HORIZONTAL EXIT FOR THE TOTAL NUMBER
 OF OCCUPANTS IN
 ADJOINING COMPARTMENTS.
 18.2.2.5.2 THE TOTAL EGRESS CAPACITY OF THE OTHER EXITS
 (STAIRS, RAMPS,
 DOORS LEADING OUTSIDE THE BUILDING) SHALL NOT BE
 REDUCED BELOW ONE-THIRD
 OF THAT REQUIRED FOR THE ENTIRE AREA OF THE BUILDING.
  
 6) PLEASE PROVED THE MEASUREMENT OF THE WIDTH OF THE
 CORRIDORS PER NFPA 101 CHAPTER 18, 18.2.3.4.
  
 7) PLEASE PROVIDE THE MEASUREMENT OF THE DOOR WIDTH PER
 NFPA 101 CHAPTER 18,
 18.2.3.6 THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS
 OF EGRESS
 FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS,
 SUCH AS X-RAY,
 SURGERY, OR PHYSICAL THERAPY; AND NURSERY ROOMS SHALL
 BE AS FOLLOWS:
 (1) HOSPITALS AND NURSING HOMES ??? 411???2 IN. (1055
 MM)
 (2) PSYCHIATRIC HOSPITALS AND LIMITED CARE
 FACILITIES??? 32 IN. (810 MM)
  
 8) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT
  
  
 9) NO COMMON PATH OF TRAVEL WAS INDICATED ON THE PLANS.
  
  
  
 10) COMPARTMENT D HAS MULTIPLE EGRESS PATHS MARKED
 GOING THROUGH INTERVENING ROOMS OR SPACES WHICH IS NOT
 ALLOWED PER NFPA 101 CHAPTER 18,
  
 18.2.5.4* INTERVENING ROOMS OR SPACES. EVERY CORRIDOR
 SHALL PROVIDE
 ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN
 ACCORDANCE WITH SECTIONS
 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING
 ROOMS OR
 SPACES OTHER THAN CORRIDORS OR LOBBIES.
 A.18.2.5.4 THE TERM INTERVENING ROOMS OR SPACES MEANS
 ROOMS OR
 SPACES SERVING AS A PART OF THE REQUIRED MEANS OF
 EGRESS FROM ANOTHER ROOM.
  
 11) PLEASE ENSURE THAT THE SLEEPING SUITE TRAVEL
 DISTANCE IS IN ACCORDANCE WITH NFPA 101 CHAPTER 18,
 18.2.5.7.2.4 SLEEPING SUITE TRAVEL DISTANCE.
 (A) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 ACCESS DOOR TO ANOTHER SUITE, AN EXIT ACCESS CORRIDOR
 DOOR, OR A HORIZONTAL
 EXIT DOOR FROM THAT SUITE SHALL NOT EXCEED 100 FT (30
 M).
 (B) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING
 SUITE AND AN EXIT
 SHALL NOT EXCEED 200 FT (61 M).
  
 12) ACCORDING TO THE FOLLOWING CODE NOT LESS THEN TWO
 EXITS ARE REQUIRED. PLEASE INDICATE THE EXITS FROM EACH
 AREA AND THE TRAVEL DISTANCE FOR BOTH.
 18.2.4 NUMBER OF MEANS OF EGRESS.
 18.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 18.2.4.2 NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
 EVERY STORY.
 18.2.4.3 NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 18.2.4.4* EXITS FROM SMOKE COMPARTMENTS.
 A.18.2.4.4 AN EXIT IS NOT NECESSARY FOR EACH INDIVIDUAL
 SMOKE COMPARTMENT
 IF THERE IS ACCESS TO AN EXIT THROUGH OTHER SMOKE
 COMPARTMENTS
 WITHOUT PASSING THROUGH THE SMOKE COMPARTMENT OF FIRE
 ORIGIN.
 18.2.4.4.1 NOT LESS THAN TWO EXITS SHALL BE ACCESSIBLE
 FROM EACH SMOKE
 COMPARTMENT, AND EGRESS SHALL BE PERMITTED THROUGH AN
 ADJACENT
 COMPARTMENT(S), PROVIDED THAT THE TWO REQUIRED EGRESS
 PATHS ARE ARRANGED
 SO THAT BOTH DO NOT PASS THROUGH THE SAME ADJACENT
 SMOKE
 COMPARTMENT.
 18.2.4.4.2 A DOOR IN A SMOKE BARRIER SHALL NOT SERVE AS
 THE ONLY EXIT
 ACCESS FROM ANY SPACE IN A SMOKE COMPARTMENT.
  
  
  
 13) THE MOUNTING OF EMERGENCY EXIT SIGNS MUST BE OVER
 THE DOOR IN WHICH THE EGRESS PATHWAY GOES PER NFPA 101
 CHAPTER 7, 7.10.1.9 MOUNTING LOCATION
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 14) ROOM 1316 (HOUSE KEEPING STORAGE), 1035
 (MAINTENANCE SHOP) AND ALL SOILED ROOMS DO NOT SHOW
 FIRE RESISTANCE RATING. IF THESE ROOMS MEET THE
 REQUIREMENTS IN THE FOLLOWING CODE FROM NFPA 101
 CHAPTER 18 THEY MUST HAVE FIRE RESISTANCE RATING OR
 SMOKE PARTITIONS.
 18.3.2.1.2THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE RESISTANCE
 RATING IN ACCORDANCE WITH SECTION 8.3:
 (1) BOILER AND FUEL-FIRED HEATER ROOMS
 (2) CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)
 (3) PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND
 MATERIALS IN QUANTITIES
 LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE
 HAZARD
 (4) PHYSICAL PLANT MAINTENANCE SHOPS
 (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL
 (242 L)
 (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64
 GAL (242 L)
 (7) STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND
 STORING COMBUSTIBLE
 MATERIAL
 18.3.2.1.3 THE FOLLOWING AREAS SHALL BE CONSIDERED
 HAZARDOUS AREAS AND
 SHALL BE PROTECTED BY SMOKE PARTITIONS IN ACCORDANCE
 WITH SECTION 8.4:
 (1) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE
 MATERIALS IN
 QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A
 SEVERE
 HAZARD
 (2) STORAGE ROOMS LARGER THAN 50 FT2 (4.6 M2) BUT NOT
 EXCEEDING 100 FT2
 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL
 (9.4
  
 15) IT IS INDICATED YOU ARE INSTALLING VINYL AND
 CARPET FLOORING. ALL FLOORING MUST HAVE SPECS SUBMITTED
 FOR REVIEW.
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 16) ON SHEET 047 AC1.03 THERE ARE DIFFERENT LEVELS OF
 SECURITY. PLEASE INDICATE THE TYPE OF DOOR CLOSING OR
 LOCKING MECHANISMS ON EACH LEVEL OF SECURITY. HOW DO
 PATIENTS EGRESS IN A FIRE EMERGENCY?
  
  
  
  
  
 17) PLEASE ENSURE THAT THE SLEEPING SUITE SUPERVISION
 MEETS THE REQUIREMENTS OF NFPA 101 CHAPTER 18,
 18.2.5.7.2.1 SLEEPING SUITE SUPERVISION.
 (A) SLEEPING SUITES SHALL BE PROVIDED WITH CONSTANT
 STAFF SUPERVISION
 WITHIN THE SUITE.
 (B)* SLEEPING SUITES SHALL BE ARRANGED IN ACCORDANCE
 WITH ONE OF THE
 FOLLOWING:
 (1)* PATIENT SLEEPING ROOMS WITHIN SLEEPING SUITES
 SHALL PROVIDE ONE OF
 THE FOLLOWING:
 (A) THE PATIENT SLEEPING ROOMS SHALL BE ARRANGED TO
 ALLOW FOR
 DIRECT SUPERVISION FROM A NORMALLY ATTENDED LOCATION
 WITHIN
 THE SUITE, SUCH AS IS PROVIDED BY GLASS WALLS, AND
 CUBICLE CURTAINS
 SHALL BE PERMITTED.
 (B) ANY PATIENT SLEEPING ROOMS WITHOUT THE DIRECT
 SUPERVISION
 REQUIRED BY 18.2.5.7.2.1(B)(1)(A) SHALL BE PROVIDED
 WITH
 SMOKE DETECTION IN ACCORDANCE WITH SECTION 9.6 AND
 18.3.4.
 (2) SLEEPING SUITES SHALL BE PROVIDED WITH A TOTAL
 (COMPLETE) COVERAGE
 AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH
 9.6.2.9 AND
 18.3.4
  
 18) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 19) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 20) IF ACCESS CONTROL IS BEING UPDATED OR ADDED THERE
 MUST BE A PERMIT AND PLAN SUBMITTED SEPARATELY.
  
 21) IF THE HOOD SYSTEM/ HOOD SUPPRESSION IS BEING
 UPDATED OR ADDED THERE MUST BE A PERMIT AND PLAN
 SUBMITTED SEPARATELY.
  
 ALL RESPONSES SHOULD BE IN A NARRATIVE FORM AND ANY AND
 ALL CHANGES MUST B CLOUDED ON THE PLANS FOR RESUBMITTAL
 VIA BUILDING DEPARTMENT.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2023-06-01 Cont ID  
Sent By ccole Date 2023-06-01 Time 16:50 Rev Time 0.00
Received By ccole Date 2023-06-01 Time 11:35 Sent To  
Notes
2023-06-01 16:51:093RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 23011089
 6/1/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA- 58- 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #4 PRINTED BELOW
 FROM THE 1ST AND 2ND REVIEW STILL EXISTS. THE GAS
 SYSTEM AND PIPING COMPLIANCE INFORMATION REQUESTED
 SHALL BE ON THE RISER DRAWING ON SHEET P7.02.
  
 4) SHEET P7.02 NEW GAS RISER: PROVIDE THE MISSING GAS
 PIPING INFORMATION PREVIOUSLY REQUESTED UNDER 1ST
 REVIEW COMMENT #2.
 A) TYPES OF PIPING.
 B) TOTAL DEVELOPED LENGTHS OF EACH SYSTEM FROM THE TANK
 OR METER TO THE MOST REMOTE APPLIANCE OUTLET OR LOW
 PRESSURE REGULATOR.
 C) LOCATIONS OF REGULATORS AND SHUT OFF VALVES.
 D) LOW PRESSURE BRANCH AND CUT PIPING LENGTHS FROM THE
 REGULATORS TO THE BOILERS.
 E) PIPE SIZING TABLES.
 F) REGULATOR VENTING DETAILS
  
 NEW COMMENT BASED ON RESUBMITTED PLANS.
  
 1) C-400, P0.01, P2.01, P3.01 & P7.02 APPEAR TO SHOW
 THE LP AND NATURAL PIPING WILL BE RUN UNDERGROUND
 OUTSIDE THE BUILDING HOWEVER THE NOTES ON P0.02
 INDICATE GAS PIPING MATERIAL TO BE SCHEDULE 40 BLACK
 IRON PIPE. PLEASE INDICATE HOW THE PIPING WILL BE
 PROTECTED FROM CORROSION IN ACCORDANCE WITH SEC. 404.11
 FBC FG. AS AN ALTERNATE TO BLACK IRON PE OR CSST PIPING
 CAN BE INSTALLED UNDERGOUND ON THE EXTERIOR OF THE
 BUILDING, HOWEVER PLEASE NOTE PE SHALL NOT BE INSTALLED
 UNDERNEATH THE BUILDING- SEC. 404.17.1. IF CHOOSING TO
 USE PE PLEASE REVISE THE RISER DRAWING, THE NOTES, AND
 THE SIZING TABLE ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-17 Cont ID  
Sent By ccole Date 2023-04-17 Time 15:35 Rev Time 0.00
Received By ccole Date 2023-04-14 Time 15:19 Sent To  
Notes
2023-04-17 15:36:412ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 23011089
 4/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA- 58- 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR A SEPARATE PERMIT APPLICATION AND
 PLANS FOR THE LP TANK TO BE SUBMITTED- SEC. 105.1 &
 107.2.1 WPB.
  
 2) REVISE THE CIVIL PLANS TO SHOW THE NEW LP TANK
 LOCATION AND EXTERIOR PIPING RUN TO THE BUILDING- SEC.
 107.2.1 WPB.
  
 3) THE ENGINEER???S RESPONSE TO 1ST REVIEW GAS PIPING
 COMMENTS REFERENCES SHEET P0.01 WHICH PROVIDES
 INCORRECT GAS PIPING COMPLIANCE INFORMATION. PLEASE
 CORRECT PER ITEMS BELOW.
 A) NATURAL GAS PIPING SIZING SHALL BE BASED ON THE FBC
 -2020 FUEL GAS CODE.
 B) LP GAS PIPING SHALL BE BASED ON FBC-2020 FUEL GAS
 AND NFPA 58- 2017.
 C) LP GAS PIPE SIZING IS NOT BASED ON TABLE 402.4(2) OF
 THE IFGC. TABLE 402.4(2) IS A NATURAL GAS TABLE.
 D) LP GAS PIPING DOES NOT RUN FROM THE TANK TO THE
 METER (THERE IS NO LP METER SHOWN) AND IS NOT 300 FT.
 LONG- REFER TO RISER DRAWING ON P7.02.
 D) LP GAS PIPING DOES NOT RUN 100 FT ON HOUSE SIDE OF
 THE METER (THERE IS NO LP METER SHOWN) AND THE 100 FT.
 LENGTH IS NOT SHOWN ON THE RISER.
  
 4) SHEETS P7.02 NEW GAS RISER: PROVIDE THE MISSING GAS
 PIPING INFORMATION PREVIOUSLY REQUESTED UNDER 1ST
 REVIEW COMMENT #2.
 A) TYPES OF PIPING.
 B) TOTAL DEVELOPED LENGTHS OF EACH SYSTEM FROM THE TANK
 OR METER TO THE MOST REMOTE APPLIANCE OUTLET OR LOW
 PRESSURE REGULATOR.
 C) LOCATIONS OF REGULATORS AND SHUT OFF VALVES.
 D) LOW PRESSURE BRANCH AND CUT PIPING LENGTHS FROM THE
 REGULATORS TO THE BOILERS.
 E) PIPE SIZING TABLES.
 F) REGULATOR VENTING DETAILS
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By ccole Date 2023-02-06 Time 16:49 Rev Time 0.00
Received By ccole Date 2023-02-06 Time 15:38 Sent To  
Notes
2023-02-06 16:50:331ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23011089
 2/6/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.600: THE PLAN NOTES INDICATE BOTH NATURAL
 GAS AND PROPANE (LP) GAS EQUIPMENT AND PIPING SYSTEM
 WORK. PLEASE PROVIDE THE FOLLOWING MINIMUM PLAN REVIEW
 ITEMS PER SEC. 107.3.5.1.5 WPB.
 A) NATURAL GAS AND LP GAS RISER DRAWINGS.
 B) GAS EQUIPMENT AND APPLIANCE LOCATION PLANS INCLUDING
 PIPING RUNS THROUGH THE BUILDING.
 C) LP TANK LOCATION AND ADDITIONAL INFORMATION TO
 CLARIFY IF THE TANK IS NEW OR EXISTING. PLEASE NOTE A
 SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF A NEW
 LP TANK.
 D) COMBUSTION AIR PLANS AND CALCULATIONS.
 E) VENTING PLANS.
  
 2) THE GAS RISER DRAWINGS SHALL INCLUDE THE FOLLOWING
 INFORMATION PER CHAPTER 4 FBC FG.
 A) DELIVERY PRESSURE AT THE METER OR TANK.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND
 REGULATOR VENT PIPING DETAILS (IF APPLICABLE).
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-21 Cont ID  
Sent By fgiaquin Date 2023-06-21 Time 12:03 Rev Time 0.00
Received By fgiaquin Date 2023-05-30 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-25 Cont ID  
Sent By asangele Date 2023-04-25 Time 11:43 Rev Time 0.00
Received By asangele Date 2023-04-25 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By asangele Date 2023-03-24 Time 09:33 Rev Time 0.00
Received By asangele Date 2023-03-24 Time 09:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-03-10 Cont ID  
Sent By rmcphers Date 2023-03-10 Time 13:23 Rev Time 0.00
Received By rmcphers Date 2023-03-10 Time 13:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-06-20 Cont ID  
Sent By hmoser Date 2023-06-20 Time 10:56 Rev Time 0.00
Received By hmoser Date 2023-06-16 Time 15:22 Sent To  
Notes
2023-06-20 10:56:09PLAN DENIED
 1) PLEASE CLOUD THE CHANGES ON THE SCONED REVIEW
 SO WE CAN SEE WHAT CHANGES WERE MADE.SECTION 107 FBC.
 2) REFER TO SECTION 607.5.4 CORRIDOR/ SMOKE BARRIERS.
 IF YOU ARE USING SMOKE DAMPERS PLEASE SHOW DAMPERS ON
 ALL DUCT PENETRATING SMOKE BARRIER PARTITIONS ON THE
 PLAN. IF YOU ARE NOT
 USING SMOKE DANPERS SHOW ON THE PLAN WHAT EXCEPTION
 YOU ARE USING FROM 607.5.4 FBC (M) 2020
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6766

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-25 Cont ID  
Sent By medwards Date 2023-04-25 Time 10:04 Rev Time 0.00
Received By medwards Date 2023-04-25 Time 07:33 Sent To  
Notes
2023-04-25 10:04:352ND REVIEW FMC
 PERMIT: 23011089
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED WITH THIS 2ND CYCLE REVIEW. PLEASE SUBMIT
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS REFERENCED
 IN THE DESIGNERS 1ST REVIEW COMMENTS. FEC C403.2.1.
 THERE ARE 199 SUPPORTING DOCUMENTS FILES, PLEASE
 PROVIDE THE NAME OF THE FILE THAT CONTAINS THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS WHEN
 RESUBMITTING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By medwards Date 2023-02-23 Time 11:02 Rev Time 0.00
Received By medwards Date 2023-02-22 Time 15:28 Sent To  
Notes
2023-02-23 11:03:131ST REVIEW FMC
 PERMIT: 23011089
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DESIGN OF THIS PROJECT MUST MEET THE
 REQUIREMENTS OF ASHRAE 170-2013. FMC 407.1
  
 2) ARE THE MECHANICAL SYSTEMS LIKE FOR LIKE CHANGE
 OUTS? IF SO ADD A NOTE ON THE DRAWINGS STATING WHICH
 ARE AND WHICH ARE NEW SYSTEMS. ALL NEW SYSTEMS MUST
 INCLUDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS.
 FEC C403.2.1
  
 3) SHEETS M2.02A; ZM2.02B, M2.02C; PROVIDE A DESIGN
 THAT MINIMIZES THE SMOKE BARRIER PENETRATIONS
 REQUIREMENTS OF ASHRAE 170-2013 6.7.3 AND 6.7.4 AND
 SHOW THE REQUIRED SMOKE DAMPERS ON THE MECHANICAL
 DRAWINGS WHERE THE DUCTWORK PENETRATES THE SMOKE
 BARRIERS.
  
 4) SHOW THE RADIATION DAMPERS FOR THE RETURNS AND THE
 EXHAUST FANS IN THE PATIENT ROOMS AND BATHROOMS. FMC
 607.5.7
  
 5) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING
 THAT THE KITCHEN HOODS AND GREASE DUCTS WILL REQUIRE A
 SEPARATE PERMIT, DOCUMENT SUBMITTAL AND PLAN REVIEW AS
 THEY WILL NOT BE REVIEWED FROM THIS SUBMITTAL.
  
 6) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING
 THAT THE REFRIGERATION SYSTEMS I.E. WALK-IN COOLERS AND
 FREEZERS WILL REQUIRE A SEPARATE PERMIT, DOCUMENT
 SUBMITTAL AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED
 FROM THIS SUBMITTAL.
  
 7) SHOW HOW THE VAV???S WILL HAVE ACCESS FOR
 MAINTENANCE AND CHANGE OUT. FMC 306.1
  
 8) SHEET M2-00-C: SHOW THE DAMPERS FOR THE PENETRATIONS
 IN THE RATED WALLS AT THE LAUNDRY. FMC 607.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status N Date 2023-04-17 Cont ID  
Sent By ccole Date 2023-04-17 Time 13:09 Rev Time 0.00
Received By ccole Date 2023-04-17 Time 13:09 Sent To  
Notes
2023-04-17 13:10:35NO MED-GAS WORK SHOWN ON PLANS. SEPARATE PERMIT
 REQUIRED FOR ALTERATIONS.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By ccole Date 2023-02-06 Time 16:22 Rev Time 0.00
Received By ccole Date 2023-02-06 Time 15:38 Sent To  
Notes
2023-02-06 16:23:051ST REVIEW FBC-2020 MEDICAL GAS
 PERMIT- 23011089
 2/6/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS AD1.01, AD1.01A, AD1.01B, AD101C: THE PLANS
 SHOW INTERIOR DEMOLITION HOWEVER NO DETAILS OR NOTES
 HAVE BEEN PROVIDED CONCERNING THE EXISTING MEDICAL GAS
 SYSTEM. PLEASE PROVIDE MED-GAS DEMOLITION AND NEW
 INSTALLATION PLANS- SEC. 1202.1 FBC P AND NFPA 99.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-06-01 Cont ID  
Sent By ccole Date 2023-06-01 Time 15:09 Rev Time 0.00
Received By ccole Date 2023-06-01 Time 11:35 Sent To  
Notes
2023-06-01 15:11:153RD REVIEW FBC-2020 PLUMBING
 PERMIT- 23011089
 6/1/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ARCHITECTURAL AND PLUMBING FLOOR PLANS: 3RD REQUEST
 TO IDENTIFY THE BATHROOMS AS MALE, FEMALE OR UNISEX AND
 PROVIDE SIGNAGE AS REQUIRED BY SEC. 403.4 FBC P. THE
 ARCHITECT'S RESPONSE TO THE PREVIOUS COMMENT #1E CITES
 SEC. 403.1.2 WHICH IS A SUB-SECTION OF 403.1- MINIMUM
 NUMBER OF FIXTURES. SEC. 403.2 IS THE SECTION THAT
 REQUIRES SEPARATE FACILITIES AND THE FOUR EXCEPTIONS
 LISTED UNDER 403.2 ARE NOT APPLICABLE TO THE FACILITY.
 SEC. 403.2.1 ALLOWS THE USE OF UNISEX WHEN A BUILDING
 OR TENANT SPACE REQUIRES A SINGLE TOILET FOR EACH SEX,
 HOWEVER THE CALCULATIONS LISTED ON SHEET AC1.01
 INDICATE MULTIPLE TOILETS REQUIRED FOR PATIENTS, STAFF,
 AND VISITORS.
  
 2) SHEETS P2.00, P2.01, P2.02, & P7.00: BASED ON TABLES
 709.1 & 710.1 IT APPEARS THE ACCUMULATED DFU TOTALS AT
 A POINT IN AREA C WILL EXCEED THE CAPACITY OF A 4-INCH
 BUILDING DRAIN HOWEVER NO DFU TOTALS HAVE BEEN PROVIDED
 AND THE SIZE OF THE EXISTING BUILDING DRAIN IS NOT
 SHOWN.
  
 3) P2.01, P2.02, P7.00, & FS1.2: BASED ON PREVIOUS
 COMMENT #7 PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE
 THAT CORRELATES WITH THE FIXTURES SHOWN IN THE KITCHEN.
 THIS IS REQUIRED TO DETERMINE WHICH DRAINAGE SHOULD BE
 GOING TO SANITARY AND WHICH TO GREASE.
  
 NEW COMMENT.
  
 1) SHEET P2.01: BASED ON SEC. 803.1 FBC P IT APPEARS
 THAT A DILUTION OR NEUTRALIZING DEVICE MUST BE PROVIDED
 FOR THE DRAINAGE FROM LAB SINK S-5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-17 Cont ID  
Sent By ccole Date 2023-04-17 Time 13:05 Rev Time 0.00
Received By ccole Date 2023-04-14 Time 15:19 Sent To  
Notes
2023-04-17 13:09:092ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23011089
 4/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. AC1.01: THE FIXTURE CALCULATIONS ARE
 INCOMPLETE FOR THE FACILITY. REFER TO TABLE 403.1 FBC P
 AND PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. PLEASE NOTE DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR
 I-2 OCCUPANCIES. MIXED OCCUPANCY CALCULATIONS SHALL BE
 DONE IN ACCORDANCE WITH SEC. 403.1.1. A COMPLETE REVIEW
 OF THE PROJECT CANNOT BE COMPLETED WITHOUT THE
 CALCULATIONS.
 A) THE REVISED CALCULATIONS AND SCHEDULE LISTING THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES WAS NOT
 PROVIDED. BASED ON TABLE 403.1 OCCUPANTS LOADS FOR
 STAFF AND VISITORS NEED TO BE BROKEN OUT TO CALCULATE
 THE REQUIRED FIXTURES FOR EACH. THE PLANS APPEAR TO
 SHOW THAT ADEQUATE WATER CLOSETS AND LAVATORIES WILL BE
 PROVIDED FOR PATIENTS, STAFF, AND THE VISITORS HOWEVER
 THE REVIEW CANNOT BE COMPLETED AT THIS TIME.
  
 B) DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED
 FIXTURES AND NO CALCULATIONS AND CORRESPONDING
 LOCATIONS FOR THOSE FIXTURES HAVE BEEN PROVIDED- TABLE
 403.1 FBC P.
  
 C) THE ENGINEER'S RESPONSE TO NOT INSTALL THE DRINKING
 FOUNTAIN'S PER THE HOSPITAL ADMINISTRATION'S REQUEST IS
 NOT ACCEPTED BECAUSE THERE ARE NO EXCEPTIONS IN THE
 PLUMBING CODE FOR HOSPITALS. SECTION 449.3.9.1 FBC B
 REQUIRES PLUMBING SYSTEMS FOR HOSPITALS TO BE DESIGNED
 IN ACCORDANCE WITH THE FBC P. SECTION 410.4 FBC P
 ALLOWS ONLY RESTAURANTS TO SUBTITUTE WATER IN
 CONTAINERS FREE OF CHARGE TO OCCUPANTS. IF THERE IS AN
 EXCEPTION FROM ANOTHER REGULATING AGENCY SUCH AS AHCA
 PLEASE PROVIDE DOCUMENTATION TO VERIFY COMPLIANCE.
  
 D) THERE IS ONE MOP SINK (SB-1) IN THE KITCHEN. CLARIFY
 IF THIS SINK WILL SERVICE ALL THE ROOMS AND AREAS ON
 THE FLOOR.
  
 E) BASED ON SEC. 403.2 SEPARATE FACILITIES SHALL BE
 PROVIDED FOR EACH SEX HOWEVER THE PLANS DO NOT IDENTIFY
 THE RESTROOMS AS MALE OR FEMALE.
  
  
 6) FAILED. PLEASE SUBMIT SANITARY DRAINAGE/VENT AND
 WATER RISER DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE
 NOTE A COMPLETE REVIEW OF THE PROJECT CANNOT BE
 COMPLETED WITHOUT THE ISOMETRICS. A COMPLETE REVIEW
 CANNOT BE ACCOMPLISHED AT THIS TIME PER ITEMS A & B.
 A) IDENTIFY ALL FIXTURES BASED ON THE SCHEDULE ON SHEET
 P0.02. ONLY THE FIXTURES FROM PART C PLANS ARE
 IDENTIFIED ON THE SANITARY RISER. NO FIXTURES IDENTIFED
 ON THE WATER RISER.
  
 B) LABEL THE GREASE WASTE LINE
  
 7) FAILED. P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING
 FIXTURES IN THE KITCHEN THAT ARE DRAINING INTO THE
 GREASE WASTE LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P.
 PLEASE NOTE THAT DRAINAGE FROM HAND SINKS OR ICE BINS
 AND ICE MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR.
 SHEETS P2.01 & P.2.02 SHOW THE DRAINAGE FROM THE HAND
 SINKS DISCHARGING INTO THE GREASE WASTE LINE WHICH IS
 NOT ALLOWED- SEC. 1003.3.1 FBC P. HANDSINKS ARE NOT
 CONSIDERED TO BE SIGNIFICANT CONTRIBUTORS OF GREASE
 WASTE.
  
 8) FAILED. P0.02, P3.01: INDICATE THE WATER SUPPLY
 TEMPERATURE FOR THE EYE WASH STATION EW-2 WILL BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
 TEPID WATER AND ASSE 1071 COMPLIANCE NOT NOTED IN THE
 SCHEDULE ON SHEET P0.02.
  
 9) FAILED. P3.00, P3.01, & P3.02: IN ORDER TO MEET
 COMPLIANCE WITH TABLE C404.5.1 FBC ENERGY, THE HW
 RECIRCULATION LINES MUST BE LOCATED AT A POINT WITHIN 2
 FT. OF THE HW SUPPLY PIPES TO THE PUBLIC LAVATORIES.
 THIS INCLUDES ALL BATHROOMS FOR STAFF BUT NOT THE
 PATIENT BATHROOMS.
 REFER TO COMMENT RESPONSE TO 6 AND IDENTIFY THE
 LOCATIONS OF THE PUBLIC LAVATORIES ON THE WATER RISER.
  
  
 12) FAILED. P6.00: SHOW THE LOCATION OF THE THERMAL
 EXPANSION CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC
 P. NOT PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By ccole Date 2023-02-06 Time 15:34 Rev Time 0.00
Received By ccole Date 2023-02-06 Time 07:31 Sent To  
Notes
2023-02-06 15:36:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23011089
 2/6/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AC1.01: THE FIXTURE CALCULATIONS ARE INCOMPLETE FOR
 THE FACILITY. REFER TO TABLE 403.1 FBC P AND PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES. PLEASE NOTE DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR I-2 OCCUPANCIES. MIXED OCCUPANCY
 CALCULATIONS SHALL BE DONE IN ACCORDANCE WITH SEC.
 403.1.1. A COMPLETE REVIEW OF THE PROJECT CANNOT BE
 COMPLETED WITHOUT THE CALCULATIONS.
  
 2) C.400, P3.01, P6.00: THE CIVIL PLAN SHOWS A NEW
 2-INCH WATER SERVICE LINE BUT THE PLUMBING PLANS SHOW A
 3-INCH INSIDE THE BUILDING. PLEASE CLARIFY AND SHOW THE
 POINT OF CONNECTION AND MAIN SHUTOFF VALVE LOCATIONS-
 606.1 FBC P.
  
 3) C.400, P3.01: PLEASE INDICATE THE EXISTING WATER
 LINE ON THE CIVIL PLAN WILL REMAIN AND SHOW THE POINT
 OF CONNECTION INSIDE THE FACILITY. IN ACCORDANCE WITH
 SEC. 609.2 FBC P- TWO WATER SERVICE PIPES ARE REQUIRED.
  
 4) P3.01 & P6.00: PLEASE SHOW THE PHYSICAL LOCATION OF
 THE BOOSTER PUMP (BP-1) ON THE FLOOR PLAN AND INDICATE
 HOW ACCESS WILL BE PROVIDED IF IN A CONCEALED LOCATION-
 SEC. 602.3.5.1 FBC P.
  
 5) C.400 & P2.01: PLEASE NOTE SEPARATE PERMITS ARE
 REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER AND THE GREASE INTERCEPTOR (IF REPLACED) AND
 THE PERMIT APPLICATIONS FOR THOSE ITEMS SHALL BE
 SUBMITTED PRIOR TO PLUMBING PLAN APPROVAL FOR THIS
 PERMIT. YOU CAN SUBMIT APPLICATIONS TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE CONTRACTORS SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 6) PLEASE SUBMIT SANITARY DRAINAGE/VENT AND WATER RISER
 DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE NOTE A
 COMPLETE REVIEW OF THE PROJECT CANNOT BE COMPLETED
 WITHOUT THE ISOMETRICS.
  
 7) P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING FIXTURES
 IN THE KITCHEN THAT ARE DRAINING INTO THE GREASE WASTE
 LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P. PLEASE NOTE
 THAT DRAINAGE FROM HAND SINKS OR ICE BINS AND ICE
 MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR.
 A) TO HELP EXPEDITE THE REVIEW PLEASE LABEL THE
 FIXTURES USING THE NUMBERS OR LABELS PROVIDED IN THE FS
 (FOOD SERVICE PLANS) SEC. 107.2.1 WPB.
 B) PLEASE PROVIDE GREASE WASTE CALCULATIONS- SEC.
 1003.3.5 & 1003.3.7 FBC P.
 C) P5.00: PLEASE SHOW TWO-WAY CLEANOUTS WILL BE
 INSTALLED ON THE INLET AND OUTLET PIPES OF THE
 INTERCEPTOR- SEC. 1003.3.1. THE CLEANOUT ON THE OUTLET
 SIDE IS ALSO REQUIRED FOR GREASE SAMPLING BY THE WPB
 UTILITES DEPT.
  
 8) P0.02, P3.01: INDICATE THE WATER SUPPLY TEMPERATURE
 FOR THE EYE WASH STATION EW-2 WILL BE CONTROLLED BY A
 TEMPERATURE ACTUATED MIXING VALVE COMPLYING WITH ASSE
 1071- SEC. 411.3 FBC P.
  
 9) P3.00, P3.01, & P3.02: IN ORDER TO MEET COMPLIANCE
 WITH TABLE C404.5.1 FBC ENERGY, THE HW RECIRCULATION
 LINES MUST BE LOCATED AT A POINT WITHIN 2 FT. OF THE HW
 SUPPLY PIPES TO THE PUBLIC LAVATORIES. THIS INCLUDES
 ALL BATHROOMS FOR STAFF BUT NOT THE PATIENT BATHROOMS.
  
 10) P0.02 & P.6.00: PROVIDE EQUIPMENT SCHEDULES FOR THE
 THREE RPBP BACKFLOW PREVENTERS SHOWN IN DETAIL 1- SECS.
 608.1, 608.17.2, 608.17.3 FBC P.
  
 11) P0.02, M0.03, P6.00: PLEASE PROVIDE AN EQUIPMENT
 SCHEDULE FOR THE HWBT- SEC. 107.2.1 WPB.
  
 12) P6.00: SHOW THE LOCATION OF THE THERMAL EXPANSION
 CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC P.
  
 13) P6.00: PLEASE PROVIDE CONDENSATE DISPOSAL PLANS FOR
 THE BOILERS AND OTHER FUEL GAS BURNING EQUIPMENT IN THE
 MECHANICAL ROOM- SEC. 307.2 FBC FG. PLEASE NOTE A WATER
 SUPPLY SHALL BE PROVIDED FOR CLEANING, FLUSHING AND
 RESEALING CONDENSATE TRAPS- SEC. 609.7 FBC P.
  
 14) A2.01, A.201C, A2.10, A2.11 & A.500: THE PLAN
 LEGENDS SHOW SYMBOLS FOR ROOF DRAINS, AND RD-1 IS
 SPECIFIED IN THE FIXTURE SCHEDULE ON P0.02: PLEASE
 PROVIDE ROOF DRAINAGE PLANS IN ACCORDANCE WITH SEC.
 107.3.5.1.3 (7) WPB AND SECS. 1105.1 & 1106.1 FBC P.
  
 15) A5.41: PLEASE PROVIDE A SEAT DETAIL THAT SHOWS THE
 SIZE OF THE SEAT AND MOUNTING CLEARANCES IN THE SHOWER
 PER SEC. 610.3 FBC ACC.
  
 16) A5.4.1: PLEASE SHOW THE HEIGHTS OF THE SHOWER GRABS
 MEASURED FROM THE FINISHED SHOWER FLOORS TO THE TOPS OF
 THE GRIPPING SURFACES- SEC. 609.4 FBC ACC.
  
 17) A6.15, A6.25 & A6.30: THE DETAILS CALL OUT ADA
 COMPLIANCE FOR THE PATIENT TOILET ROOMS, AND SECLUSION
 ROOMS. PLEASE PROVIDE THE FOLLOWING DETAILS PER THE FBC
 ACCESSIBILITY CODE.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2
 SHOWERS:
 A) CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.2.
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.2 & 609.4.
 C) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SEC. 608.5.2.
 D) LOCATION OF ACCESSIBLE SHOWER SEAT AND MOUNTING
 PARAMETERS- SECS. 610.3.
  
 18) A6.15: SHOW THE CLEAR FLOOR SPACE DIAGRAM WITH
 DIMENSIONS FOR THE NURSE STATION SINK- SECS. 212.3 &
 606.2 FBC ACC.
  
 19) A6.32 DETAIL 11 NOURISH SINK: SHOW THE CLEAR FLOOR
 SPACE DIAGRAM WITH DIMENSIONS, AND THE HEIGHT OF THE
 SINK RIM OR COUNTER- SECS. 212.3 & 606.2 FBC ACC.
  
 20) A6.26: REFER TO COMMENT #14 ABOVE AND REVISE DETAIL
 1 TO SHOW COMPLIANCE. CONCERNING THE TRANSFER SHOWER
 PLEASE PROVIDE:
 A) SHOWER DIMENSIONS- SEC. 608.2.1.
 B) CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.1.
 C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 & 609.4.
 D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SEC. 608.5.1.
  
 21) A101B STAFF LOUNGE SINK: SHOW THE CLEAR FLOOR SPACE
 DIAGRAM WITH DIMENSIONS, AND THE HEIGHT OF THE SINK RIM
 OR COUNTER- SECS. 212.3 & 606.2 FBC ACC. PLEASE NOTE
 SHEET A6.01 WHICH MAY SHOW THE DETAILS PER THE DETAIL
 SYMBOL WAS NOT UPLOADED FOR REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-02 Cont ID  
Sent By rmcphers Date 2023-06-02 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2023-06-02 Time 08:27 Sent To  
Notes
2023-06-02 08:29:57SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE STRUCTURAL DRAWINGS, ELECTRICAL DRAWINGS (EXCEPT
 FOR THE ELECTRICAL DRAWINGS ADDED ON 5-24-23), FIRE
 PROTECTION DRAWINGS AND THE TELECOM DRAWINGS DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 PLUMBING AND GAS (P) SHEETS APPROVED.
2023-06-01 12:32:28PLUMBING/GAS PLAN SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 14:31 Rev Time 0.00
Received By rmcphers Date 2023-04-24 Time 14:28 Sent To  
Notes
2023-04-24 14:31:24SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE STRUCTURAL DRAWINGS, ELECTRICAL DRAWINGS, FIRE
 PROTECTION DRAWINGS AND THE TELECOM DRAWINGS DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2023-04-17 13:27:35PLUMBING AND GAS (P) SHEETS APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By rmcphers Date 2023-03-10 Time 14:19 Rev Time 0.00
Received By rmcphers Date 2023-03-10 Time 14:19 Sent To  
Notes
2023-02-23 11:04:00MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-02-06 17:04:02PLUMBING PLANS PASSED DIG-SIG.

Review Stop Z ZONING
Rev No 3 Status P Date 2023-06-05 Cont ID  
Sent By asangele Date 2023-06-05 Time 11:03 Rev Time 0.00
Received By asangele Date 2023-06-05 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-25 Cont ID  
Sent By asangele Date 2023-04-25 Time 11:43 Rev Time 0.00
Received By asangele Date 2023-04-25 Time 11:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-24 Cont ID  
Sent By ASangele Date 2023-03-24 Time 09:33 Rev Time 0.00
Received By asangele Date 2023-03-24 Time 09:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved