| Plan Review Stops For Permit 23011089 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-23 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-23 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2023-02-23 11:52:47 | APPLICANT PROVIDED SITE PLAN. ADDRESS APPROPRIATE FOR | | | PROJECT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-02-15 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-02-15 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2023-02-15 16:49:42 | PLEASE PROVIDE A SITE PLAN OR AERIAL MAP SHOWING THE | | | EXACT BUILDING TO BE WORKED ON. PLEASE EMAIL RESPONSE | | | TO [email protected] OR CALL 561-805-6659. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2023-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-01 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-01 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-24 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-24 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2023-04-24 14:33:12 | THE ASBESTOS SURVEY IS NOT REQUIRED - THE LETTER FROM | | | THE CONTRACTOR IS REQUIRED. | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-10 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-10 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2023-03-10 11:53:27 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-01 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-01 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2023-06-01 15:03:22 | HOSPITAL REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | | FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787) | | | - (FL4553) | | | | | | 2) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | I CHECK THE ELECTRONIC SIGNATURE FOR THE DRAWINGS | | | UPLOADED TO PROJECTDOX BY OPENING THEM IN ???ADOBE | | | READER???. THE ???ADOBE READER??? STATES WHETHER THEY | | | ARE AN ORIGINAL ELECTRONICALLY SIGNED DOCUMENT. WHEN | | | ELECTRONICALLY SIGNED DRAWINGS ARE PRINTED OUT, THEY | | | LOSE THEIR ELECTRONIC SIGNATURE. ELECTRONICALLY SIGNED | | | DRAWINGS NEED TO BE MOVED AROUND IN THE COMPUTER FROM | | | PLACE TO PLACE. FROM THE ARCHITECT???S OR ENGINEER???S | | | COMPUTER TO YOUR COMPUTER TO THE CITY???S ELECTRONIC | | | PLAN REVIEW (PROJECTDOX). MAYBE YOURS WERE PRINTED OUT | | | AT SOME TIME? | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-24 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-24 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2023-04-24 14:01:13 | HOSPITAL REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10 | | | SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD | | | MATCH. | | | | | | 2) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | | FRONT PAGES FOR PRODUCT APPROVALS (FL15850) - (FL8787) | | | - (FL4553) - ALL PRODUCT APPROVALS NEED TO BE REVIEWED | | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD | | | FBC WPB 107.3.4 | | | | | | 3) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS | | | ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT | | | SPECIALIZING IN TREATING CONDITIONS THAT AFFECT | | | MOBILITY. | | | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS | | | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER | | | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE | | | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE | | | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS | | | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A | | | 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS | | | THAT AFFECT MOBILITY. | | | IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT | | | AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING | | | ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH | | | 805. | | | | | | 4) PLEASE SHOW THE FIRE RATED CEILING ASSEMBLY DESIGN | | | NUMBER - FBC 703.3 | | | | | | 5) PLEASE SHOW THE FIRE RATED WALL ASSEMBLY DESIGN | | | NUMBER ON THE WALL SCHEDULE - FBC 703.3 | | | | | | 6) CANNOT FIND THE DOOR HARDWARE SET DESCRIPTIONS - FBC | | | WPB 107.2.1 | | | | | | 7) THE PLYWOOD ADDED TO THE EXTERIOR WALLS SHOULD BE | | | FIRE RETARDANT PER FBC 602.3 | | | | | | 8) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-10 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-09 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2023-03-10 11:30:20 | HOSPITAL REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING G0.00 - UNDER "PROJECT INFORMATION" SHOWS | | | RISK CATEGORY IV AND A WIND SPEED OF 178MPH - WIND | | | SPEED SHOULD BE 180MPH PER FBC WPB SECTION 120. | | | | | | 2) DRAWING G0.00 SHOWS RISK CATEGORY IV - DRAWING S1.10 | | | SHOWS RISK CATEGORY III - PLEASE CLARIFY - THEY SHOULD | | | MATCH. | | | | | | 3) DRAWING G0.00 - UNDER "PROJECT INFORMATION" THE FIRE | | | RATINGS SHOULD BE SHOWN PER FBC TABLE 601 FOR A | | | CONSTRUCTION TYPE III A. | | | | | | 4) DRAWINGS SHOW OCCUPANCY TYPE "I 2" PLEASE SHOW IF | | | CONDITION 1 OR CONDITION 2 - FBC 308.4 | | | | | | 5) PLEASE SHOW THE CORRIDOR WALLS TO BE SMOKE | | | PARTITIONS PER FBC 407.3 | | | 407.2 CORRIDORS CONTINUITY AND SEPARATION. | | | CORRIDORS IN OCCUPANCIES IN GROUP I-2 SHALL BE | | | CONTINUOUS TO THE EXITS AND SHALL BE SEPARATED FROM | | | OTHER AREAS IN ACCORDANCE WITH SECTION 407.3 EXCEPT | | | SPACES CONFORMING TO SECTIONS 407.2.1 THROUGH 407.2.6. | | | | | | 6) PLEASE SHOW SMOKE PARTITION DETAILS PER FBC 710.4 | | | CONTINUITY. | | | SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE | | | FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR | | | OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE | | | UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING | | | MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. | | | | | | 7) WALLS SURROUNDING THE LAUNDRY ROOM (1209) ARE SHOWN | | | TO BE FIRE RATED BUT THE DOOR IS NOT - PLEASE CLARIFY | | | FBC TABLE 716.5 | | | | | | 8) PLEASE SHOW THE PUBLIC RESTROOM WALL AND BASE BOARD | | | FINISHES TO COMPLY WITH FBC 1210.2.2 WALLS AND | | | PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT | | | CONSIDERED A HARD SURFACE) | | | | | | 9) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS FOR THE | | | INTERIOR FINISHES - FBC 803.11 INTERIOR FINISH | | | REQUIREMENTS BASED ON GROUP. | | | INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME | | | SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE | | | 803.11 FOR THE GROUP AND LOCATION DESIGNATED. | | | | | | 10) DRAWING A5.10 SHOWS A VAPER BARRIER AND FIRE | | | SEPARATION AT THE ROOF TRUSSES - PLEASE CLARIFY - WHAT | | | TYPE OF VAPER BARRIER AND THE HOURLY FIRE RATING - | | | PLEASE PROVIDE DETAILS - ROOF VENTILATION MAY BE NEEDED | | | PER FBC 1203.2 VENTILATION REQUIRED. ENCLOSED ATTICS | | | AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE | | | APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING | | | MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATION OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN AND SNOW. BLOCKING AND BRIDGING SHALL | | | BE ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF | | | AIR. AN AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL | | | BE PROVIDED BETWEEN THE INSULATION AND THE ROOF | | | SHEATHING. THE NET FREE VENTILATING AREA SHALL BE NOT | | | LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED. | | | | | | 11) DRAWING A5.10 SHOW A FIRE SEPARATION AT THE ROOF | | | TRUSSES - PLEASE CLARIFY - SHOW THE HOURLY FIRE RATING | | | ASSEMBLY - PLEASE PROVIDE DETAILS - FBC 708.4 | | | CONTINUITY. | | | FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE | | | FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE | | | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK | | | ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR | | | ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY | | | ATTACHED THERETO. | | | | | | 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND | | | DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC | | | WPB 107.3.4 | | | | | | 13) PLEASE SHOW THE WATER DRAINAGE FROM THE CANOPY ROOF | | | SYSTEM - FBC 1503.7 PROTECTION AGAINST DECAY AND | | | TERMITES. | | | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT | | | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR | | | SPLASH BLOCKS. | | | FBC 1808.7.4 "REQUIRED DRAINAGE TO THE POINT OF | | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | | ALL LOCATIONS ON THE SITE". | | | | | | 14) THE VERTICAL TOILET GRAB BAR IS NOT A REQUIREMENT | | | IN THE FBC - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE | | | THE GRAB BARS - FBC A 609.3 THE SPACE BETWEEN THE GRAB | | | BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES | | | (305 MM) MINIMUM. | | | | | | 15) ACCESSIBLE RESTROOM = WHEN REFERRING TO THE | | | DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR | | | PLEASE USE THE WORDS "REFLECTIVE SURFACE" - FBC A 603.3 | | | MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND | | | | | | 16) PLEASE NOTE WHICH ROOMS ARE TO BE ACCESSIBLE ROOMS | | | ON THE DRAWINGS - FBC A 223.2.1 FACILITIES NOT | | | SPECIALIZING IN TREATING CONDITIONS THAT AFFECT | | | MOBILITY. | | | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS | | | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER | | | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE | | | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE | | | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS | | | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. FBC A | | | 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS | | | THAT AFFECT MOBILITY. | | | IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT | | | AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING | | | ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH | | | 805. | | | | | | 17) PLEASE SHOW THE INCIDENTAL ROOMS (LAUNDRY, STORAGE, | | | PATIENT ROOMS EQUIPPED WITH PADDED SURFACES, PHYSICAL | | | PLANT MAINTENANCE SHOPS, WASTE AND LINEN COLLECTION, | | | ETC) TO BE FIRE RATED PER FBC SECTION 509 - TABLE 509 | | | --- 509.4.1SEPARATION. WHERE TABLE 509 SPECIFIES A | | | FIRE-RESISTANCE-RATED SEPARATION, THE INCIDENTAL USES | | | SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING | | | BY A FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 711, OR BOTH. | | | | | | 18) SEPARATE PERMITS ARE REQUIRED FOR - GENERATOR, | | | GENERATOR ENCLOSURE, OUTDOOR CANOPIES, PARKING LOT, | | | FENCES. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-06-21 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-06-21 |
Time |
11:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-04-19 |
Time |
19:44 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-04-18 |
Time |
20:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-02-27 |
Time |
20:17 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-02-13 |
Time |
20:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-02-13 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-05-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-05-31 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-04-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-04-17 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-17 13:37:11 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING | | | COMMENTS: | | | | | | THE COMMENTS BELOW ARE REPEATED COMMENTS FROM THE FIRST | | | REVIEW, NO RESPONSES WERE FOUND IN THE DOCUMENTS | | | SUBMITTED RESPONDING TO THE COMMENTS BELOW. | | | | | | 1) ON THE COVER SHEET YOU REFERENCE 2020 NATIONAL FIRE | | | CODE AND THE MOST CURRENT IS NFPA 2018. | | | | | | 2) IN REFERENCE TO NPFA 101 CHAPTER 18 TABLE 18.1.6.1, | | | WHAT CLASSIFICATION WOULD YOU SELECT TO APPLY TOWARD | | | YOUR CONSTRUCTION TYPE? | | | | | | 3) WHAT IS THE RATING OF THE FIRE SEPARATION INDICATED | | | ON 016 A5.00? | | | | | | 4) PLEASE CLARIFY THE PERCENTAGE OF REHABILITATION | | | BEING DONE IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.1.1.4.3 REHABILITATION. | | | 18.1.1.4.3.1 FOR PURPOSES OF THE PROVISIONS OF THIS | | | CHAPTER, THE FOLLOWING | | | SHALL APPLY: | | | (1) A MAJOR REHABILITATION SHALL INVOLVE THE | | | MODIFICATION OF MORE THAN | | | 50 PERCENT, OR MORE THAN 4500 FT2 (420 M2), OF THE AREA | | | OF THE SMOKE | | | COMPARTMENT. | | | (2) A MINOR REHABILITATION SHALL INVOLVE THE | | | MODIFICATION OF NOT MORE THAN 50 PERCENT, AND NOT MORE | | | THAN 4500 FT2 (420 M2), OF THE AREA OF THE SMOKE | | | COMPARTMENT. | | | | | | 5) PROVIDE THE HORIZONTAL EXIT CAPACITY AND TOTAL | | | EGRESS CAPACITY OF ANY OTHER EXITS FOR EACH COMPARTMENT | | | IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING | | | WITH 7.2.4 AND | | | THE MODIFICATIONS OF 18.2.2.5.1 THROUGH 18.2.2.5.7 | | | SHALL BE PERMITTED. | | | 18.2.2.5.1 ACCUMULATION SPACE SHALL BE PROVIDED IN | | | ACCORDANCE WITH | | | 18.2.2.5.1.1 AND 18.2.2.5.1.2. | | | 18.2.2.5.1.1 NOT LESS THAN 30 NET FT2 (2.8 NET M2) PER | | | PATIENT IN A HOSPITAL | | | OR NURSING HOME, OR NOT LESS THAN 15 NET FT2 (1.4 NET | | | M2) PER RESIDENT IN | | | A LIMITED CARE FACILITY, SHALL BE PROVIDED WITHIN THE | | | AGGREGATED AREA OF | | | CORRIDORS, PATIENT ROOMS, TREATMENT ROOMS, LOUNGE OR | | | DINING AREAS, AND | | | OTHER SIMILAR AREAS ON EACH SIDE OF THE HORIZONTAL | | | EXIT. | | | 18.2.2.5.1.2 ON STORIES NOT HOUSING BEDRIDDEN OR | | | LITTERBORNE PATIENTS, | | | NOT LESS THAN 6 NET FT2 (0.56 NET M2) PER OCCUPANT | | | SHALL BE PROVIDED ON | | | EACH SIDE OF THE HORIZONTAL EXIT FOR THE TOTAL NUMBER | | | OF OCCUPANTS IN | | | ADJOINING COMPARTMENTS. | | | 18.2.2.5.2 THE TOTAL EGRESS CAPACITY OF THE OTHER EXITS | | | (STAIRS, RAMPS, | | | DOORS LEADING OUTSIDE THE BUILDING) SHALL NOT BE | | | REDUCED BELOW ONE-THIRD | | | OF THAT REQUIRED FOR THE ENTIRE AREA OF THE BUILDING. | | | | | | 6) PLEASE PROVED THE MEASUREMENT OF THE WIDTH OF THE | | | CORRIDORS PER NFPA 101 CHAPTER 18, 18.2.3.4. | | | | | | 7) PLEASE PROVIDE THE MEASUREMENT OF THE DOOR WIDTH PER | | | NFPA 101 CHAPTER 18, | | | 18.2.3.6 THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS | | | OF EGRESS | | | FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, | | | SUCH AS X-RAY, | | | SURGERY, OR PHYSICAL THERAPY; AND NURSERY ROOMS SHALL | | | BE AS FOLLOWS: | | | (1) HOSPITALS AND NURSING HOMES ??? 411???2 IN. (1055 | | | MM) | | | (2) PSYCHIATRIC HOSPITALS AND LIMITED CARE | | | FACILITIES??? 32 IN. (810 MM) | | | | | | 8) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT | | | | | | | | | 9) NO COMMON PATH OF TRAVEL WAS INDICATED ON THE PLANS. | | | | | | | | | | | | 10) COMPARTMENT D HAS MULTIPLE EGRESS PATHS MARKED | | | GOING THROUGH INTERVENING ROOMS OR SPACES WHICH IS NOT | | | ALLOWED PER NFPA 101 CHAPTER 18, | | | | | | 18.2.5.4* INTERVENING ROOMS OR SPACES. EVERY CORRIDOR | | | SHALL PROVIDE | | | ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN | | | ACCORDANCE WITH SECTIONS | | | 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING | | | ROOMS OR | | | SPACES OTHER THAN CORRIDORS OR LOBBIES. | | | A.18.2.5.4 THE TERM INTERVENING ROOMS OR SPACES MEANS | | | ROOMS OR | | | SPACES SERVING AS A PART OF THE REQUIRED MEANS OF | | | EGRESS FROM ANOTHER ROOM. | | | | | | 11) PLEASE ENSURE THAT THE SLEEPING SUITE TRAVEL | | | DISTANCE IS IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.2.5.7.2.4 SLEEPING SUITE TRAVEL DISTANCE. | | | (A) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING | | | SUITE AND AN EXIT | | | ACCESS DOOR TO ANOTHER SUITE, AN EXIT ACCESS CORRIDOR | | | DOOR, OR A HORIZONTAL | | | EXIT DOOR FROM THAT SUITE SHALL NOT EXCEED 100 FT (30 | | | M). | | | (B) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING | | | SUITE AND AN EXIT | | | SHALL NOT EXCEED 200 FT (61 M). | | | | | | 12) ACCORDING TO THE FOLLOWING CODE NOT LESS THEN TWO | | | EXITS ARE REQUIRED. PLEASE INDICATE THE EXITS FROM EACH | | | AREA AND THE TRAVEL DISTANCE FOR BOTH. | | | 18.2.4 NUMBER OF MEANS OF EGRESS. | | | 18.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 7.4. | | | 18.2.4.2 NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON | | | EVERY STORY. | | | 18.2.4.3 NOT LESS THAN TWO SEPARATE EXITS SHALL BE | | | ACCESSIBLE FROM EVERY | | | PART OF EVERY STORY. | | | 18.2.4.4* EXITS FROM SMOKE COMPARTMENTS. | | | A.18.2.4.4 AN EXIT IS NOT NECESSARY FOR EACH INDIVIDUAL | | | SMOKE COMPARTMENT | | | IF THERE IS ACCESS TO AN EXIT THROUGH OTHER SMOKE | | | COMPARTMENTS | | | WITHOUT PASSING THROUGH THE SMOKE COMPARTMENT OF FIRE | | | ORIGIN. | | | 18.2.4.4.1 NOT LESS THAN TWO EXITS SHALL BE ACCESSIBLE | | | FROM EACH SMOKE | | | COMPARTMENT, AND EGRESS SHALL BE PERMITTED THROUGH AN | | | ADJACENT | | | COMPARTMENT(S), PROVIDED THAT THE TWO REQUIRED EGRESS | | | PATHS ARE ARRANGED | | | SO THAT BOTH DO NOT PASS THROUGH THE SAME ADJACENT | | | SMOKE | | | COMPARTMENT. | | | 18.2.4.4.2 A DOOR IN A SMOKE BARRIER SHALL NOT SERVE AS | | | THE ONLY EXIT | | | ACCESS FROM ANY SPACE IN A SMOKE COMPARTMENT. | | | | | | | | | | | | 13) THE MOUNTING OF EMERGENCY EXIT SIGNS MUST BE OVER | | | THE DOOR IN WHICH THE EGRESS PATHWAY GOES PER NFPA 101 | | | CHAPTER 7, 7.10.1.9 MOUNTING LOCATION | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 14) ROOM 1316 (HOUSE KEEPING STORAGE), 1035 | | | (MAINTENANCE SHOP) AND ALL SOILED ROOMS DO NOT SHOW | | | FIRE RESISTANCE RATING. IF THESE ROOMS MEET THE | | | REQUIREMENTS IN THE FOLLOWING CODE FROM NFPA 101 | | | CHAPTER 18 THEY MUST HAVE FIRE RESISTANCE RATING OR | | | SMOKE PARTITIONS. | | | 18.3.2.1.2THE FOLLOWING AREAS SHALL BE CONSIDERED | | | HAZARDOUS AREAS AND | | | SHALL BE PROTECTED BY FIRE BARRIERS HAVING A MINIMUM | | | 1-HOUR FIRE RESISTANCE | | | RATING IN ACCORDANCE WITH SECTION 8.3: | | | (1) BOILER AND FUEL-FIRED HEATER ROOMS | | | (2) CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2) | | | (3) PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND | | | MATERIALS IN QUANTITIES | | | LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE | | | HAZARD | | | (4) PHYSICAL PLANT MAINTENANCE SHOPS | | | (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL | | | (242 L) | | | (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 | | | GAL (242 L) | | | (7) STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND | | | STORING COMBUSTIBLE | | | MATERIAL | | | 18.3.2.1.3 THE FOLLOWING AREAS SHALL BE CONSIDERED | | | HAZARDOUS AREAS AND | | | SHALL BE PROTECTED BY SMOKE PARTITIONS IN ACCORDANCE | | | WITH SECTION 8.4: | | | (1) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE | | | MATERIALS IN | | | QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A | | | SEVERE | | | HAZARD | | | (2) STORAGE ROOMS LARGER THAN 50 FT2 (4.6 M2) BUT NOT | | | EXCEEDING 100 FT2 | | | (9.3 M2) AND STORING COMBUSTIBLE MATERIAL | | | (9.4 | | | | | | 15) IT IS INDICATED YOU ARE INSTALLING VINYL AND | | | CARPET FLOORING. ALL FLOORING MUST HAVE SPECS SUBMITTED | | | FOR REVIEW. | | | 10.2.7* INTERIOR FLOOR FINISH TESTING AND | | | CLASSIFICATION. | | | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR | | | FINISHES SHALL | | | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR | | | IGNITION | | | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING | | | MATERIALS. | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN | | | THE CLASSES SPECIFIED | | | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE | | | CRITICAL RADIANT FLUX | | | REQUIREMENTS. | | | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.45 W/CM2, AS DETERMINED | | | BY THE TEST DESCRIBED IN 10.2.7.3. | | | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.22 W/CM2, BUT LESS | | | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN | | | 10.2.7.3. | | | | | | PLEASE REVIEW AND PROVIDE SPEC SHEETS. | | | | | | | | | 16) ON SHEET 047 AC1.03 THERE ARE DIFFERENT LEVELS OF | | | SECURITY. PLEASE INDICATE THE TYPE OF DOOR CLOSING OR | | | LOCKING MECHANISMS ON EACH LEVEL OF SECURITY. HOW DO | | | PATIENTS EGRESS IN A FIRE EMERGENCY? | | | | | | | | | | | | | | | | | | 17) PLEASE ENSURE THAT THE SLEEPING SUITE SUPERVISION | | | MEETS THE REQUIREMENTS OF NFPA 101 CHAPTER 18, | | | 18.2.5.7.2.1 SLEEPING SUITE SUPERVISION. | | | (A) SLEEPING SUITES SHALL BE PROVIDED WITH CONSTANT | | | STAFF SUPERVISION | | | WITHIN THE SUITE. | | | (B)* SLEEPING SUITES SHALL BE ARRANGED IN ACCORDANCE | | | WITH ONE OF THE | | | FOLLOWING: | | | (1)* PATIENT SLEEPING ROOMS WITHIN SLEEPING SUITES | | | SHALL PROVIDE ONE OF | | | THE FOLLOWING: | | | (A) THE PATIENT SLEEPING ROOMS SHALL BE ARRANGED TO | | | ALLOW FOR | | | DIRECT SUPERVISION FROM A NORMALLY ATTENDED LOCATION | | | WITHIN | | | THE SUITE, SUCH AS IS PROVIDED BY GLASS WALLS, AND | | | CUBICLE CURTAINS | | | SHALL BE PERMITTED. | | | (B) ANY PATIENT SLEEPING ROOMS WITHOUT THE DIRECT | | | SUPERVISION | | | REQUIRED BY 18.2.5.7.2.1(B)(1)(A) SHALL BE PROVIDED | | | WITH | | | SMOKE DETECTION IN ACCORDANCE WITH SECTION 9.6 AND | | | 18.3.4. | | | (2) SLEEPING SUITES SHALL BE PROVIDED WITH A TOTAL | | | (COMPLETE) COVERAGE | | | AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH | | | 9.6.2.9 AND | | | 18.3.4 | | | | | | 18) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE | | | AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 19) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 20) IF ACCESS CONTROL IS BEING UPDATED OR ADDED THERE | | | MUST BE A PERMIT AND PLAN SUBMITTED SEPARATELY. | | | | | | 21) IF THE HOOD SYSTEM/ HOOD SUPPRESSION IS BEING | | | UPDATED OR ADDED THERE MUST BE A PERMIT AND PLAN | | | SUBMITTED SEPARATELY. | | | | | | ALL RESPONSES SHOULD BE IN A NARRATIVE FORM AND ANY AND | | | ALL CHANGES MUST B CLOUDED ON THE PLANS FOR RESUBMITTAL | | | VIA BUILDING DEPARTMENT. | | | | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4728 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-02-09 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-02-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-02-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-02-09 12:40:48 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING | | | COMMENTS: | | | | | | 1) ON THE COVER SHEET YOU REFERENCE 2020 NATIONAL FIRE | | | CODE AND THE MOST CURRENT IS NFPA 2018. | | | | | | 2) IN REFERENCE TO NPFA 101 CHAPTER 18 TABLE 18.1.6.1, | | | WHAT CLASSIFICATION WOULD YOU SELECT TO APPLY TOWARD | | | YOUR CONSTRUCTION TYPE? | | | | | | 3) WHAT IS THE RATING OF THE FIRE SEPARATION INDICATED | | | ON 016 A5.00? | | | | | | 4) PLEASE CLARIFY THE PERCENTAGE OF REHABILITATION | | | BEING DONE IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.1.1.4.3 REHABILITATION. | | | 18.1.1.4.3.1 FOR PURPOSES OF THE PROVISIONS OF THIS | | | CHAPTER, THE FOLLOWING | | | SHALL APPLY: | | | (1) A MAJOR REHABILITATION SHALL INVOLVE THE | | | MODIFICATION OF MORE THAN | | | 50 PERCENT, OR MORE THAN 4500 FT2 (420 M2), OF THE AREA | | | OF THE SMOKE | | | COMPARTMENT. | | | (2) A MINOR REHABILITATION SHALL INVOLVE THE | | | MODIFICATION OF NOT MORE THAN 50 PERCENT, AND NOT MORE | | | THAN 4500 FT2 (420 M2), OF THE AREA OF THE SMOKE | | | COMPARTMENT. | | | | | | 5) PROVIDE THE HORIZONTAL EXIT CAPACITY AND TOTAL | | | EGRESS CAPACITY OF ANY OTHER EXITS FOR EACH COMPARTMENT | | | IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING | | | WITH 7.2.4 AND | | | THE MODIFICATIONS OF 18.2.2.5.1 THROUGH 18.2.2.5.7 | | | SHALL BE PERMITTED. | | | 18.2.2.5.1 ACCUMULATION SPACE SHALL BE PROVIDED IN | | | ACCORDANCE WITH | | | 18.2.2.5.1.1 AND 18.2.2.5.1.2. | | | 18.2.2.5.1.1 NOT LESS THAN 30 NET FT2 (2.8 NET M2) PER | | | PATIENT IN A HOSPITAL | | | OR NURSING HOME, OR NOT LESS THAN 15 NET FT2 (1.4 NET | | | M2) PER RESIDENT IN | | | A LIMITED CARE FACILITY, SHALL BE PROVIDED WITHIN THE | | | AGGREGATED AREA OF | | | CORRIDORS, PATIENT ROOMS, TREATMENT ROOMS, LOUNGE OR | | | DINING AREAS, AND | | | OTHER SIMILAR AREAS ON EACH SIDE OF THE HORIZONTAL | | | EXIT. | | | 18.2.2.5.1.2 ON STORIES NOT HOUSING BEDRIDDEN OR | | | LITTERBORNE PATIENTS, | | | NOT LESS THAN 6 NET FT2 (0.56 NET M2) PER OCCUPANT | | | SHALL BE PROVIDED ON | | | EACH SIDE OF THE HORIZONTAL EXIT FOR THE TOTAL NUMBER | | | OF OCCUPANTS IN | | | ADJOINING COMPARTMENTS. | | | 18.2.2.5.2 THE TOTAL EGRESS CAPACITY OF THE OTHER EXITS | | | (STAIRS, RAMPS, | | | DOORS LEADING OUTSIDE THE BUILDING) SHALL NOT BE | | | REDUCED BELOW ONE-THIRD | | | OF THAT REQUIRED FOR THE ENTIRE AREA OF THE BUILDING. | | | | | | 6) PLEASE PROVED THE MEASUREMENT OF THE WIDTH OF THE | | | CORRIDORS PER NFPA 101 CHAPTER 18, 18.2.3.4. | | | | | | 7) PLEASE PROVIDE THE MEASUREMENT OF THE DOOR WIDTH PER | | | NFPA 101 CHAPTER 18, | | | 18.2.3.6 THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS | | | OF EGRESS | | | FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, | | | SUCH AS X-RAY, | | | SURGERY, OR PHYSICAL THERAPY; AND NURSERY ROOMS SHALL | | | BE AS FOLLOWS: | | | (1) HOSPITALS AND NURSING HOMES ??? 411???2 IN. (1055 | | | MM) | | | (2) PSYCHIATRIC HOSPITALS AND LIMITED CARE | | | FACILITIES??? 32 IN. (810 MM) | | | | | | 8) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT | | | | | | | | | 9) NO COMMON PATH OF TRAVEL WAS INDICATED ON THE PLANS. | | | | | | | | | | | | 10) COMPARTMENT D HAS MULTIPLE EGRESS PATHS MARKED | | | GOING THROUGH INTERVENING ROOMS OR SPACES WHICH IS NOT | | | ALLOWED PER NFPA 101 CHAPTER 18, | | | | | | 18.2.5.4* INTERVENING ROOMS OR SPACES. EVERY CORRIDOR | | | SHALL PROVIDE | | | ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN | | | ACCORDANCE WITH SECTIONS | | | 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING | | | ROOMS OR | | | SPACES OTHER THAN CORRIDORS OR LOBBIES. | | | A.18.2.5.4 THE TERM INTERVENING ROOMS OR SPACES MEANS | | | ROOMS OR | | | SPACES SERVING AS A PART OF THE REQUIRED MEANS OF | | | EGRESS FROM ANOTHER ROOM. | | | | | | 11) PLEASE ENSURE THAT THE SLEEPING SUITE TRAVEL | | | DISTANCE IS IN ACCORDANCE WITH NFPA 101 CHAPTER 18, | | | 18.2.5.7.2.4 SLEEPING SUITE TRAVEL DISTANCE. | | | (A) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING | | | SUITE AND AN EXIT | | | ACCESS DOOR TO ANOTHER SUITE, AN EXIT ACCESS CORRIDOR | | | DOOR, OR A HORIZONTAL | | | EXIT DOOR FROM THAT SUITE SHALL NOT EXCEED 100 FT (30 | | | M). | | | (B) TRAVEL DISTANCE BETWEEN ANY POINT IN A SLEEPING | | | SUITE AND AN EXIT | | | SHALL NOT EXCEED 200 FT (61 M). | | | | | | 12) ACCORDING TO THE FOLLOWING CODE NOT LESS THEN TWO | | | EXITS ARE REQUIRED. PLEASE INDICATE THE EXITS FROM EACH | | | AREA AND THE TRAVEL DISTANCE FOR BOTH. | | | 18.2.4 NUMBER OF MEANS OF EGRESS. | | | 18.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 7.4. | | | 18.2.4.2 NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON | | | EVERY STORY. | | | 18.2.4.3 NOT LESS THAN TWO SEPARATE EXITS SHALL BE | | | ACCESSIBLE FROM EVERY | | | PART OF EVERY STORY. | | | 18.2.4.4* EXITS FROM SMOKE COMPARTMENTS. | | | A.18.2.4.4 AN EXIT IS NOT NECESSARY FOR EACH INDIVIDUAL | | | SMOKE COMPARTMENT | | | IF THERE IS ACCESS TO AN EXIT THROUGH OTHER SMOKE | | | COMPARTMENTS | | | WITHOUT PASSING THROUGH THE SMOKE COMPARTMENT OF FIRE | | | ORIGIN. | | | 18.2.4.4.1 NOT LESS THAN TWO EXITS SHALL BE ACCESSIBLE | | | FROM EACH SMOKE | | | COMPARTMENT, AND EGRESS SHALL BE PERMITTED THROUGH AN | | | ADJACENT | | | COMPARTMENT(S), PROVIDED THAT THE TWO REQUIRED EGRESS | | | PATHS ARE ARRANGED | | | SO THAT BOTH DO NOT PASS THROUGH THE SAME ADJACENT | | | SMOKE | | | COMPARTMENT. | | | 18.2.4.4.2 A DOOR IN A SMOKE BARRIER SHALL NOT SERVE AS | | | THE ONLY EXIT | | | ACCESS FROM ANY SPACE IN A SMOKE COMPARTMENT. | | | | | | | | | | | | 13) THE MOUNTING OF EMERGENCY EXIT SIGNS MUST BE OVER | | | THE DOOR IN WHICH THE EGRESS PATHWAY GOES PER NFPA 101 | | | CHAPTER 7, 7.10.1.9 MOUNTING LOCATION | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 14) ROOM 1316 (HOUSE KEEPING STORAGE), 1035 | | | (MAINTENANCE SHOP) AND ALL SOILED ROOMS DO NOT SHOW | | | FIRE RESISTANCE RATING. IF THESE ROOMS MEET THE | | | REQUIREMENTS IN THE FOLLOWING CODE FROM NFPA 101 | | | CHAPTER 18 THEY MUST HAVE FIRE RESISTANCE RATING OR | | | SMOKE PARTITIONS. | | | 18.3.2.1.2THE FOLLOWING AREAS SHALL BE CONSIDERED | | | HAZARDOUS AREAS AND | | | SHALL BE PROTECTED BY FIRE BARRIERS HAVING A MINIMUM | | | 1-HOUR FIRE RESISTANCE | | | RATING IN ACCORDANCE WITH SECTION 8.3: | | | (1) BOILER AND FUEL-FIRED HEATER ROOMS | | | (2) CENTRAL/BULK LAUNDRIES LARGER THAN 100 FT2 (9.3 M2) | | | (3) PAINT SHOPS EMPLOYING HAZARDOUS SUBSTANCES AND | | | MATERIALS IN QUANTITIES | | | LESS THAN THOSE THAT WOULD BE CLASSIFIED AS A SEVERE | | | HAZARD | | | (4) PHYSICAL PLANT MAINTENANCE SHOPS | | | (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL | | | (242 L) | | | (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 | | | GAL (242 L) | | | (7) STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND | | | STORING COMBUSTIBLE | | | MATERIAL | | | 18.3.2.1.3 THE FOLLOWING AREAS SHALL BE CONSIDERED | | | HAZARDOUS AREAS AND | | | SHALL BE PROTECTED BY SMOKE PARTITIONS IN ACCORDANCE | | | WITH SECTION 8.4: | | | (1) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE | | | MATERIALS IN | | | QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A | | | SEVERE | | | HAZARD | | | (2) STORAGE ROOMS LARGER THAN 50 FT2 (4.6 M2) BUT NOT | | | EXCEEDING 100 FT2 | | | (9.3 M2) AND STORING COMBUSTIBLE MATERIAL | | | (9.4 | | | | | | 15) IT IS INDICATED YOU ARE INSTALLING VINYL AND | | | CARPET FLOORING. ALL FLOORING MUST HAVE SPECS SUBMITTED | | | FOR REVIEW. | | | 10.2.7* INTERIOR FLOOR FINISH TESTING AND | | | CLASSIFICATION. | | | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR | | | FINISHES SHALL | | | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR | | | IGNITION | | | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING | | | MATERIALS. | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN | | | THE CLASSES SPECIFIED | | | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE | | | CRITICAL RADIANT FLUX | | | REQUIREMENTS. | | | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.45 W/CM2, AS DETERMINED | | | BY THE TEST DESCRIBED IN 10.2.7.3. | | | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.22 W/CM2, BUT LESS | | | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN | | | 10.2.7.3. | | | | | | PLEASE REVIEW AND PROVIDE SPEC SHEETS. | | | | | | | | | 16) ON SHEET 047 AC1.03 THERE ARE DIFFERENT LEVELS OF | | | SECURITY. PLEASE INDICATE THE TYPE OF DOOR CLOSING OR | | | LOCKING MECHANISMS ON EACH LEVEL OF SECURITY. HOW DO | | | PATIENTS EGRESS IN A FIRE EMERGENCY? | | | | | | | | | | | | | | | | | | 17) PLEASE ENSURE THAT THE SLEEPING SUITE SUPERVISION | | | MEETS THE REQUIREMENTS OF NFPA 101 CHAPTER 18, | | | 18.2.5.7.2.1 SLEEPING SUITE SUPERVISION. | | | (A) SLEEPING SUITES SHALL BE PROVIDED WITH CONSTANT | | | STAFF SUPERVISION | | | WITHIN THE SUITE. | | | (B)* SLEEPING SUITES SHALL BE ARRANGED IN ACCORDANCE | | | WITH ONE OF THE | | | FOLLOWING: | | | (1)* PATIENT SLEEPING ROOMS WITHIN SLEEPING SUITES | | | SHALL PROVIDE ONE OF | | | THE FOLLOWING: | | | (A) THE PATIENT SLEEPING ROOMS SHALL BE ARRANGED TO | | | ALLOW FOR | | | DIRECT SUPERVISION FROM A NORMALLY ATTENDED LOCATION | | | WITHIN | | | THE SUITE, SUCH AS IS PROVIDED BY GLASS WALLS, AND | | | CUBICLE CURTAINS | | | SHALL BE PERMITTED. | | | (B) ANY PATIENT SLEEPING ROOMS WITHOUT THE DIRECT | | | SUPERVISION | | | REQUIRED BY 18.2.5.7.2.1(B)(1)(A) SHALL BE PROVIDED | | | WITH | | | SMOKE DETECTION IN ACCORDANCE WITH SECTION 9.6 AND | | | 18.3.4. | | | (2) SLEEPING SUITES SHALL BE PROVIDED WITH A TOTAL | | | (COMPLETE) COVERAGE | | | AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH | | | 9.6.2.9 AND | | | 18.3.4 | | | | | | 18) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE | | | AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 19) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 20) IF ACCESS CONTROL IS BEING UPDATED OR ADDED THERE | | | MUST BE A PERMIT AND PLAN SUBMITTED SEPARATELY. | | | | | | 21) IF THE HOOD SYSTEM/ HOOD SUPPRESSION IS BEING | | | UPDATED OR ADDED THERE MUST BE A PERMIT AND PLAN | | | SUBMITTED SEPARATELY. | | | | | | ALL RESPONSES SHOULD BE IN A NARRATIVE FORM AND ANY AND | | | ALL CHANGES MUST B CLOUDED ON THE PLANS FOR RESUBMITTAL | | | VIA BUILDING DEPARTMENT. | | | | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4728 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-01 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-01 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2023-06-01 16:51:09 | 3RD REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23011089 | | | 6/1/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | NFPA- 58- 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #4 PRINTED BELOW | | | FROM THE 1ST AND 2ND REVIEW STILL EXISTS. THE GAS | | | SYSTEM AND PIPING COMPLIANCE INFORMATION REQUESTED | | | SHALL BE ON THE RISER DRAWING ON SHEET P7.02. | | | | | | 4) SHEET P7.02 NEW GAS RISER: PROVIDE THE MISSING GAS | | | PIPING INFORMATION PREVIOUSLY REQUESTED UNDER 1ST | | | REVIEW COMMENT #2. | | | A) TYPES OF PIPING. | | | B) TOTAL DEVELOPED LENGTHS OF EACH SYSTEM FROM THE TANK | | | OR METER TO THE MOST REMOTE APPLIANCE OUTLET OR LOW | | | PRESSURE REGULATOR. | | | C) LOCATIONS OF REGULATORS AND SHUT OFF VALVES. | | | D) LOW PRESSURE BRANCH AND CUT PIPING LENGTHS FROM THE | | | REGULATORS TO THE BOILERS. | | | E) PIPE SIZING TABLES. | | | F) REGULATOR VENTING DETAILS | | | | | | NEW COMMENT BASED ON RESUBMITTED PLANS. | | | | | | 1) C-400, P0.01, P2.01, P3.01 & P7.02 APPEAR TO SHOW | | | THE LP AND NATURAL PIPING WILL BE RUN UNDERGROUND | | | OUTSIDE THE BUILDING HOWEVER THE NOTES ON P0.02 | | | INDICATE GAS PIPING MATERIAL TO BE SCHEDULE 40 BLACK | | | IRON PIPE. PLEASE INDICATE HOW THE PIPING WILL BE | | | PROTECTED FROM CORROSION IN ACCORDANCE WITH SEC. 404.11 | | | FBC FG. AS AN ALTERNATE TO BLACK IRON PE OR CSST PIPING | | | CAN BE INSTALLED UNDERGOUND ON THE EXTERIOR OF THE | | | BUILDING, HOWEVER PLEASE NOTE PE SHALL NOT BE INSTALLED | | | UNDERNEATH THE BUILDING- SEC. 404.17.1. IF CHOOSING TO | | | USE PE PLEASE REVISE THE RISER DRAWING, THE NOTES, AND | | | THE SIZING TABLE ACCORDINGLY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-17 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-14 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2023-04-17 15:36:41 | 2ND REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23011089 | | | 4/17/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | NFPA- 58- 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) 2ND REQUEST FOR A SEPARATE PERMIT APPLICATION AND | | | PLANS FOR THE LP TANK TO BE SUBMITTED- SEC. 105.1 & | | | 107.2.1 WPB. | | | | | | 2) REVISE THE CIVIL PLANS TO SHOW THE NEW LP TANK | | | LOCATION AND EXTERIOR PIPING RUN TO THE BUILDING- SEC. | | | 107.2.1 WPB. | | | | | | 3) THE ENGINEER???S RESPONSE TO 1ST REVIEW GAS PIPING | | | COMMENTS REFERENCES SHEET P0.01 WHICH PROVIDES | | | INCORRECT GAS PIPING COMPLIANCE INFORMATION. PLEASE | | | CORRECT PER ITEMS BELOW. | | | A) NATURAL GAS PIPING SIZING SHALL BE BASED ON THE FBC | | | -2020 FUEL GAS CODE. | | | B) LP GAS PIPING SHALL BE BASED ON FBC-2020 FUEL GAS | | | AND NFPA 58- 2017. | | | C) LP GAS PIPE SIZING IS NOT BASED ON TABLE 402.4(2) OF | | | THE IFGC. TABLE 402.4(2) IS A NATURAL GAS TABLE. | | | D) LP GAS PIPING DOES NOT RUN FROM THE TANK TO THE | | | METER (THERE IS NO LP METER SHOWN) AND IS NOT 300 FT. | | | LONG- REFER TO RISER DRAWING ON P7.02. | | | D) LP GAS PIPING DOES NOT RUN 100 FT ON HOUSE SIDE OF | | | THE METER (THERE IS NO LP METER SHOWN) AND THE 100 FT. | | | LENGTH IS NOT SHOWN ON THE RISER. | | | | | | 4) SHEETS P7.02 NEW GAS RISER: PROVIDE THE MISSING GAS | | | PIPING INFORMATION PREVIOUSLY REQUESTED UNDER 1ST | | | REVIEW COMMENT #2. | | | A) TYPES OF PIPING. | | | B) TOTAL DEVELOPED LENGTHS OF EACH SYSTEM FROM THE TANK | | | OR METER TO THE MOST REMOTE APPLIANCE OUTLET OR LOW | | | PRESSURE REGULATOR. | | | C) LOCATIONS OF REGULATORS AND SHUT OFF VALVES. | | | D) LOW PRESSURE BRANCH AND CUT PIPING LENGTHS FROM THE | | | REGULATORS TO THE BOILERS. | | | E) PIPE SIZING TABLES. | | | F) REGULATOR VENTING DETAILS | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-06 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-06 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2023-02-06 16:50:33 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23011089 | | | 2/6/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P.600: THE PLAN NOTES INDICATE BOTH NATURAL | | | GAS AND PROPANE (LP) GAS EQUIPMENT AND PIPING SYSTEM | | | WORK. PLEASE PROVIDE THE FOLLOWING MINIMUM PLAN REVIEW | | | ITEMS PER SEC. 107.3.5.1.5 WPB. | | | A) NATURAL GAS AND LP GAS RISER DRAWINGS. | | | B) GAS EQUIPMENT AND APPLIANCE LOCATION PLANS INCLUDING | | | PIPING RUNS THROUGH THE BUILDING. | | | C) LP TANK LOCATION AND ADDITIONAL INFORMATION TO | | | CLARIFY IF THE TANK IS NEW OR EXISTING. PLEASE NOTE A | | | SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF A NEW | | | LP TANK. | | | D) COMBUSTION AIR PLANS AND CALCULATIONS. | | | E) VENTING PLANS. | | | | | | 2) THE GAS RISER DRAWINGS SHALL INCLUDE THE FOLLOWING | | | INFORMATION PER CHAPTER 4 FBC FG. | | | A) DELIVERY PRESSURE AT THE METER OR TANK. | | | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | C) TYPES AND SIZES OF PIPING. | | | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND | | | REGULATOR VENT PIPING DETAILS (IF APPLICABLE). | | | G) OUTLET PRESSURES AT REGULATORS. | | | H) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | I) PIPE SIZING TABLES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-06-21 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-05-30 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-25 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-25 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-03-24 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-03-24 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-10 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-10 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-06-20 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-16 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2023-06-20 10:56:09 | PLAN DENIED | | | 1) PLEASE CLOUD THE CHANGES ON THE SCONED REVIEW | | | SO WE CAN SEE WHAT CHANGES WERE MADE.SECTION 107 FBC. | | | 2) REFER TO SECTION 607.5.4 CORRIDOR/ SMOKE BARRIERS. | | | IF YOU ARE USING SMOKE DAMPERS PLEASE SHOW DAMPERS ON | | | ALL DUCT PENETRATING SMOKE BARRIER PARTITIONS ON THE | | | PLAN. IF YOU ARE NOT | | | USING SMOKE DANPERS SHOW ON THE PLAN WHAT EXCEPTION | | | YOU ARE USING FROM 607.5.4 FBC (M) 2020 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6766 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-25 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-25 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2023-04-25 10:04:35 | 2ND REVIEW FMC | | | PERMIT: 23011089 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE | | | NOT SUBMITTED WITH THIS 2ND CYCLE REVIEW. PLEASE SUBMIT | | | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS REFERENCED | | | IN THE DESIGNERS 1ST REVIEW COMMENTS. FEC C403.2.1. | | | THERE ARE 199 SUPPORTING DOCUMENTS FILES, PLEASE | | | PROVIDE THE NAME OF THE FILE THAT CONTAINS THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS WHEN | | | RESUBMITTING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-23 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-22 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2023-02-23 11:03:13 | 1ST REVIEW FMC | | | PERMIT: 23011089 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DESIGN OF THIS PROJECT MUST MEET THE | | | REQUIREMENTS OF ASHRAE 170-2013. FMC 407.1 | | | | | | 2) ARE THE MECHANICAL SYSTEMS LIKE FOR LIKE CHANGE | | | OUTS? IF SO ADD A NOTE ON THE DRAWINGS STATING WHICH | | | ARE AND WHICH ARE NEW SYSTEMS. ALL NEW SYSTEMS MUST | | | INCLUDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | FEC C403.2.1 | | | | | | 3) SHEETS M2.02A; ZM2.02B, M2.02C; PROVIDE A DESIGN | | | THAT MINIMIZES THE SMOKE BARRIER PENETRATIONS | | | REQUIREMENTS OF ASHRAE 170-2013 6.7.3 AND 6.7.4 AND | | | SHOW THE REQUIRED SMOKE DAMPERS ON THE MECHANICAL | | | DRAWINGS WHERE THE DUCTWORK PENETRATES THE SMOKE | | | BARRIERS. | | | | | | 4) SHOW THE RADIATION DAMPERS FOR THE RETURNS AND THE | | | EXHAUST FANS IN THE PATIENT ROOMS AND BATHROOMS. FMC | | | 607.5.7 | | | | | | 5) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING | | | THAT THE KITCHEN HOODS AND GREASE DUCTS WILL REQUIRE A | | | SEPARATE PERMIT, DOCUMENT SUBMITTAL AND PLAN REVIEW AS | | | THEY WILL NOT BE REVIEWED FROM THIS SUBMITTAL. | | | | | | 6) PROVIDE A NOTE ON THE MECHANICAL DRAWING STATING | | | THAT THE REFRIGERATION SYSTEMS I.E. WALK-IN COOLERS AND | | | FREEZERS WILL REQUIRE A SEPARATE PERMIT, DOCUMENT | | | SUBMITTAL AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED | | | FROM THIS SUBMITTAL. | | | | | | 7) SHOW HOW THE VAV???S WILL HAVE ACCESS FOR | | | MAINTENANCE AND CHANGE OUT. FMC 306.1 | | | | | | 8) SHEET M2-00-C: SHOW THE DAMPERS FOR THE PENETRATIONS | | | IN THE RATED WALLS AT THE LAUNDRY. FMC 607. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
2 |
Status |
N |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-17 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-17 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2023-04-17 13:10:35 | NO MED-GAS WORK SHOWN ON PLANS. SEPARATE PERMIT | | | REQUIRED FOR ALTERATIONS. |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-06 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-06 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2023-02-06 16:23:05 | 1ST REVIEW FBC-2020 MEDICAL GAS | | | PERMIT- 23011089 | | | 2/6/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS AD1.01, AD1.01A, AD1.01B, AD101C: THE PLANS | | | SHOW INTERIOR DEMOLITION HOWEVER NO DETAILS OR NOTES | | | HAVE BEEN PROVIDED CONCERNING THE EXISTING MEDICAL GAS | | | SYSTEM. PLEASE PROVIDE MED-GAS DEMOLITION AND NEW | | | INSTALLATION PLANS- SEC. 1202.1 FBC P AND NFPA 99. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-01 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-01 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2023-06-01 15:11:15 | 3RD REVIEW FBC-2020 PLUMBING | | | PERMIT- 23011089 | | | 6/1/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ARCHITECTURAL AND PLUMBING FLOOR PLANS: 3RD REQUEST | | | TO IDENTIFY THE BATHROOMS AS MALE, FEMALE OR UNISEX AND | | | PROVIDE SIGNAGE AS REQUIRED BY SEC. 403.4 FBC P. THE | | | ARCHITECT'S RESPONSE TO THE PREVIOUS COMMENT #1E CITES | | | SEC. 403.1.2 WHICH IS A SUB-SECTION OF 403.1- MINIMUM | | | NUMBER OF FIXTURES. SEC. 403.2 IS THE SECTION THAT | | | REQUIRES SEPARATE FACILITIES AND THE FOUR EXCEPTIONS | | | LISTED UNDER 403.2 ARE NOT APPLICABLE TO THE FACILITY. | | | SEC. 403.2.1 ALLOWS THE USE OF UNISEX WHEN A BUILDING | | | OR TENANT SPACE REQUIRES A SINGLE TOILET FOR EACH SEX, | | | HOWEVER THE CALCULATIONS LISTED ON SHEET AC1.01 | | | INDICATE MULTIPLE TOILETS REQUIRED FOR PATIENTS, STAFF, | | | AND VISITORS. | | | | | | 2) SHEETS P2.00, P2.01, P2.02, & P7.00: BASED ON TABLES | | | 709.1 & 710.1 IT APPEARS THE ACCUMULATED DFU TOTALS AT | | | A POINT IN AREA C WILL EXCEED THE CAPACITY OF A 4-INCH | | | BUILDING DRAIN HOWEVER NO DFU TOTALS HAVE BEEN PROVIDED | | | AND THE SIZE OF THE EXISTING BUILDING DRAIN IS NOT | | | SHOWN. | | | | | | 3) P2.01, P2.02, P7.00, & FS1.2: BASED ON PREVIOUS | | | COMMENT #7 PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE | | | THAT CORRELATES WITH THE FIXTURES SHOWN IN THE KITCHEN. | | | THIS IS REQUIRED TO DETERMINE WHICH DRAINAGE SHOULD BE | | | GOING TO SANITARY AND WHICH TO GREASE. | | | | | | NEW COMMENT. | | | | | | 1) SHEET P2.01: BASED ON SEC. 803.1 FBC P IT APPEARS | | | THAT A DILUTION OR NEUTRALIZING DEVICE MUST BE PROVIDED | | | FOR THE DRAINAGE FROM LAB SINK S-5. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-17 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-14 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2023-04-17 13:09:09 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 23011089 | | | 4/17/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. | | | | | | 1) FAILED. AC1.01: THE FIXTURE CALCULATIONS ARE | | | INCOMPLETE FOR THE FACILITY. REFER TO TABLE 403.1 FBC P | | | AND PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED NUMBER OF FIXTURES. PLEASE NOTE DRINKING | | | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR | | | I-2 OCCUPANCIES. MIXED OCCUPANCY CALCULATIONS SHALL BE | | | DONE IN ACCORDANCE WITH SEC. 403.1.1. A COMPLETE REVIEW | | | OF THE PROJECT CANNOT BE COMPLETED WITHOUT THE | | | CALCULATIONS. | | | A) THE REVISED CALCULATIONS AND SCHEDULE LISTING THE | | | REQUIRED AND PROVIDED NUMBER OF FIXTURES WAS NOT | | | PROVIDED. BASED ON TABLE 403.1 OCCUPANTS LOADS FOR | | | STAFF AND VISITORS NEED TO BE BROKEN OUT TO CALCULATE | | | THE REQUIRED FIXTURES FOR EACH. THE PLANS APPEAR TO | | | SHOW THAT ADEQUATE WATER CLOSETS AND LAVATORIES WILL BE | | | PROVIDED FOR PATIENTS, STAFF, AND THE VISITORS HOWEVER | | | THE REVIEW CANNOT BE COMPLETED AT THIS TIME. | | | | | | B) DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED | | | FIXTURES AND NO CALCULATIONS AND CORRESPONDING | | | LOCATIONS FOR THOSE FIXTURES HAVE BEEN PROVIDED- TABLE | | | 403.1 FBC P. | | | | | | C) THE ENGINEER'S RESPONSE TO NOT INSTALL THE DRINKING | | | FOUNTAIN'S PER THE HOSPITAL ADMINISTRATION'S REQUEST IS | | | NOT ACCEPTED BECAUSE THERE ARE NO EXCEPTIONS IN THE | | | PLUMBING CODE FOR HOSPITALS. SECTION 449.3.9.1 FBC B | | | REQUIRES PLUMBING SYSTEMS FOR HOSPITALS TO BE DESIGNED | | | IN ACCORDANCE WITH THE FBC P. SECTION 410.4 FBC P | | | ALLOWS ONLY RESTAURANTS TO SUBTITUTE WATER IN | | | CONTAINERS FREE OF CHARGE TO OCCUPANTS. IF THERE IS AN | | | EXCEPTION FROM ANOTHER REGULATING AGENCY SUCH AS AHCA | | | PLEASE PROVIDE DOCUMENTATION TO VERIFY COMPLIANCE. | | | | | | D) THERE IS ONE MOP SINK (SB-1) IN THE KITCHEN. CLARIFY | | | IF THIS SINK WILL SERVICE ALL THE ROOMS AND AREAS ON | | | THE FLOOR. | | | | | | E) BASED ON SEC. 403.2 SEPARATE FACILITIES SHALL BE | | | PROVIDED FOR EACH SEX HOWEVER THE PLANS DO NOT IDENTIFY | | | THE RESTROOMS AS MALE OR FEMALE. | | | | | | | | | 6) FAILED. PLEASE SUBMIT SANITARY DRAINAGE/VENT AND | | | WATER RISER DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE | | | NOTE A COMPLETE REVIEW OF THE PROJECT CANNOT BE | | | COMPLETED WITHOUT THE ISOMETRICS. A COMPLETE REVIEW | | | CANNOT BE ACCOMPLISHED AT THIS TIME PER ITEMS A & B. | | | A) IDENTIFY ALL FIXTURES BASED ON THE SCHEDULE ON SHEET | | | P0.02. ONLY THE FIXTURES FROM PART C PLANS ARE | | | IDENTIFIED ON THE SANITARY RISER. NO FIXTURES IDENTIFED | | | ON THE WATER RISER. | | | | | | B) LABEL THE GREASE WASTE LINE | | | | | | 7) FAILED. P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING | | | FIXTURES IN THE KITCHEN THAT ARE DRAINING INTO THE | | | GREASE WASTE LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P. | | | PLEASE NOTE THAT DRAINAGE FROM HAND SINKS OR ICE BINS | | | AND ICE MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR. | | | SHEETS P2.01 & P.2.02 SHOW THE DRAINAGE FROM THE HAND | | | SINKS DISCHARGING INTO THE GREASE WASTE LINE WHICH IS | | | NOT ALLOWED- SEC. 1003.3.1 FBC P. HANDSINKS ARE NOT | | | CONSIDERED TO BE SIGNIFICANT CONTRIBUTORS OF GREASE | | | WASTE. | | | | | | 8) FAILED. P0.02, P3.01: INDICATE THE WATER SUPPLY | | | TEMPERATURE FOR THE EYE WASH STATION EW-2 WILL BE | | | CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE | | | COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. | | | TEPID WATER AND ASSE 1071 COMPLIANCE NOT NOTED IN THE | | | SCHEDULE ON SHEET P0.02. | | | | | | 9) FAILED. P3.00, P3.01, & P3.02: IN ORDER TO MEET | | | COMPLIANCE WITH TABLE C404.5.1 FBC ENERGY, THE HW | | | RECIRCULATION LINES MUST BE LOCATED AT A POINT WITHIN 2 | | | FT. OF THE HW SUPPLY PIPES TO THE PUBLIC LAVATORIES. | | | THIS INCLUDES ALL BATHROOMS FOR STAFF BUT NOT THE | | | PATIENT BATHROOMS. | | | REFER TO COMMENT RESPONSE TO 6 AND IDENTIFY THE | | | LOCATIONS OF THE PUBLIC LAVATORIES ON THE WATER RISER. | | | | | | | | | 12) FAILED. P6.00: SHOW THE LOCATION OF THE THERMAL | | | EXPANSION CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC | | | P. NOT PROVIDED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-06 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-06 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2023-02-06 15:36:33 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23011089 | | | 2/6/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AC1.01: THE FIXTURE CALCULATIONS ARE INCOMPLETE FOR | | | THE FACILITY. REFER TO TABLE 403.1 FBC P AND PROVIDE A | | | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | | NUMBER OF FIXTURES. PLEASE NOTE DRINKING FOUNTAINS ARE | | | REQUIRED FIXTURES FOR I-2 OCCUPANCIES. MIXED OCCUPANCY | | | CALCULATIONS SHALL BE DONE IN ACCORDANCE WITH SEC. | | | 403.1.1. A COMPLETE REVIEW OF THE PROJECT CANNOT BE | | | COMPLETED WITHOUT THE CALCULATIONS. | | | | | | 2) C.400, P3.01, P6.00: THE CIVIL PLAN SHOWS A NEW | | | 2-INCH WATER SERVICE LINE BUT THE PLUMBING PLANS SHOW A | | | 3-INCH INSIDE THE BUILDING. PLEASE CLARIFY AND SHOW THE | | | POINT OF CONNECTION AND MAIN SHUTOFF VALVE LOCATIONS- | | | 606.1 FBC P. | | | | | | 3) C.400, P3.01: PLEASE INDICATE THE EXISTING WATER | | | LINE ON THE CIVIL PLAN WILL REMAIN AND SHOW THE POINT | | | OF CONNECTION INSIDE THE FACILITY. IN ACCORDANCE WITH | | | SEC. 609.2 FBC P- TWO WATER SERVICE PIPES ARE REQUIRED. | | | | | | 4) P3.01 & P6.00: PLEASE SHOW THE PHYSICAL LOCATION OF | | | THE BOOSTER PUMP (BP-1) ON THE FLOOR PLAN AND INDICATE | | | HOW ACCESS WILL BE PROVIDED IF IN A CONCEALED LOCATION- | | | SEC. 602.3.5.1 FBC P. | | | | | | 5) C.400 & P2.01: PLEASE NOTE SEPARATE PERMITS ARE | | | REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW | | | PREVENTER AND THE GREASE INTERCEPTOR (IF REPLACED) AND | | | THE PERMIT APPLICATIONS FOR THOSE ITEMS SHALL BE | | | SUBMITTED PRIOR TO PLUMBING PLAN APPROVAL FOR THIS | | | PERMIT. YOU CAN SUBMIT APPLICATIONS TBD (TO BE | | | DETERMINED) IF YOU DO NOT HAVE CONTRACTORS SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected]. YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE | | | THE REVIEW STATUS TO PASS. | | | | | | 6) PLEASE SUBMIT SANITARY DRAINAGE/VENT AND WATER RISER | | | DRAWINGS- SEC. 107.3.5.1.3(13) WPB. PLEASE NOTE A | | | COMPLETE REVIEW OF THE PROJECT CANNOT BE COMPLETED | | | WITHOUT THE ISOMETRICS. | | | | | | 7) P2.01 & P2.02: PLEASE IDENTIFY THE PLUMBING FIXTURES | | | IN THE KITCHEN THAT ARE DRAINING INTO THE GREASE WASTE | | | LINE AND INTERCEPTOR- SEC. 1003.3.1 FBC P. PLEASE NOTE | | | THAT DRAINAGE FROM HAND SINKS OR ICE BINS AND ICE | | | MAKERS SHALL NOT DRAIN INTO THE INTERCEPTOR. | | | A) TO HELP EXPEDITE THE REVIEW PLEASE LABEL THE | | | FIXTURES USING THE NUMBERS OR LABELS PROVIDED IN THE FS | | | (FOOD SERVICE PLANS) SEC. 107.2.1 WPB. | | | B) PLEASE PROVIDE GREASE WASTE CALCULATIONS- SEC. | | | 1003.3.5 & 1003.3.7 FBC P. | | | C) P5.00: PLEASE SHOW TWO-WAY CLEANOUTS WILL BE | | | INSTALLED ON THE INLET AND OUTLET PIPES OF THE | | | INTERCEPTOR- SEC. 1003.3.1. THE CLEANOUT ON THE OUTLET | | | SIDE IS ALSO REQUIRED FOR GREASE SAMPLING BY THE WPB | | | UTILITES DEPT. | | | | | | 8) P0.02, P3.01: INDICATE THE WATER SUPPLY TEMPERATURE | | | FOR THE EYE WASH STATION EW-2 WILL BE CONTROLLED BY A | | | TEMPERATURE ACTUATED MIXING VALVE COMPLYING WITH ASSE | | | 1071- SEC. 411.3 FBC P. | | | | | | 9) P3.00, P3.01, & P3.02: IN ORDER TO MEET COMPLIANCE | | | WITH TABLE C404.5.1 FBC ENERGY, THE HW RECIRCULATION | | | LINES MUST BE LOCATED AT A POINT WITHIN 2 FT. OF THE HW | | | SUPPLY PIPES TO THE PUBLIC LAVATORIES. THIS INCLUDES | | | ALL BATHROOMS FOR STAFF BUT NOT THE PATIENT BATHROOMS. | | | | | | 10) P0.02 & P.6.00: PROVIDE EQUIPMENT SCHEDULES FOR THE | | | THREE RPBP BACKFLOW PREVENTERS SHOWN IN DETAIL 1- SECS. | | | 608.1, 608.17.2, 608.17.3 FBC P. | | | | | | 11) P0.02, M0.03, P6.00: PLEASE PROVIDE AN EQUIPMENT | | | SCHEDULE FOR THE HWBT- SEC. 107.2.1 WPB. | | | | | | 12) P6.00: SHOW THE LOCATION OF THE THERMAL EXPANSION | | | CONTROL DEVICE FOR THE ST-1- SEC. 607.3 FBC P. | | | | | | 13) P6.00: PLEASE PROVIDE CONDENSATE DISPOSAL PLANS FOR | | | THE BOILERS AND OTHER FUEL GAS BURNING EQUIPMENT IN THE | | | MECHANICAL ROOM- SEC. 307.2 FBC FG. PLEASE NOTE A WATER | | | SUPPLY SHALL BE PROVIDED FOR CLEANING, FLUSHING AND | | | RESEALING CONDENSATE TRAPS- SEC. 609.7 FBC P. | | | | | | 14) A2.01, A.201C, A2.10, A2.11 & A.500: THE PLAN | | | LEGENDS SHOW SYMBOLS FOR ROOF DRAINS, AND RD-1 IS | | | SPECIFIED IN THE FIXTURE SCHEDULE ON P0.02: PLEASE | | | PROVIDE ROOF DRAINAGE PLANS IN ACCORDANCE WITH SEC. | | | 107.3.5.1.3 (7) WPB AND SECS. 1105.1 & 1106.1 FBC P. | | | | | | 15) A5.41: PLEASE PROVIDE A SEAT DETAIL THAT SHOWS THE | | | SIZE OF THE SEAT AND MOUNTING CLEARANCES IN THE SHOWER | | | PER SEC. 610.3 FBC ACC. | | | | | | 16) A5.4.1: PLEASE SHOW THE HEIGHTS OF THE SHOWER GRABS | | | MEASURED FROM THE FINISHED SHOWER FLOORS TO THE TOPS OF | | | THE GRIPPING SURFACES- SEC. 609.4 FBC ACC. | | | | | | 17) A6.15, A6.25 & A6.30: THE DETAILS CALL OUT ADA | | | COMPLIANCE FOR THE PATIENT TOILET ROOMS, AND SECLUSION | | | ROOMS. PLEASE PROVIDE THE FOLLOWING DETAILS PER THE FBC | | | ACCESSIBILITY CODE. | | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | WATER CLOSETS- SEC. 604.3. | | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | LAVATORIES- SEC. 606.2. | | | C) TURNING SPACE DIAMETERS- SEC. 304.3. | | | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE | | | WALLS- SEC. 604.2. | | | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED | | | FLOORS- SEC. 604.4. | | | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE | | | FROM THE FINISHED FLOOR- SEC. 606.3. | | | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | | THE REFLECTIVE SURFACES- SEC. 603.3 | | | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. | | | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE | | | 604.7. | | | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. | | | 606.2 | | | SHOWERS: | | | A) CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS FOR THE | | | SHOWER- SEC. 608.2.2. | | | B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.2 & 609.4. | | | C) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE | | | SHOWER- SEC. 608.5.2. | | | D) LOCATION OF ACCESSIBLE SHOWER SEAT AND MOUNTING | | | PARAMETERS- SECS. 610.3. | | | | | | 18) A6.15: SHOW THE CLEAR FLOOR SPACE DIAGRAM WITH | | | DIMENSIONS FOR THE NURSE STATION SINK- SECS. 212.3 & | | | 606.2 FBC ACC. | | | | | | 19) A6.32 DETAIL 11 NOURISH SINK: SHOW THE CLEAR FLOOR | | | SPACE DIAGRAM WITH DIMENSIONS, AND THE HEIGHT OF THE | | | SINK RIM OR COUNTER- SECS. 212.3 & 606.2 FBC ACC. | | | | | | 20) A6.26: REFER TO COMMENT #14 ABOVE AND REVISE DETAIL | | | 1 TO SHOW COMPLIANCE. CONCERNING THE TRANSFER SHOWER | | | PLEASE PROVIDE: | | | A) SHOWER DIMENSIONS- SEC. 608.2.1. | | | B) CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS FOR THE | | | SHOWER- SEC. 608.2.1. | | | C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 & 609.4. | | | D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE | | | SHOWER- SEC. 608.5.1. | | | | | | 21) A101B STAFF LOUNGE SINK: SHOW THE CLEAR FLOOR SPACE | | | DIAGRAM WITH DIMENSIONS, AND THE HEIGHT OF THE SINK RIM | | | OR COUNTER- SECS. 212.3 & 606.2 FBC ACC. PLEASE NOTE | | | SHEET A6.01 WHICH MAY SHOW THE DETAILS PER THE DETAIL | | | SYMBOL WAS NOT UPLOADED FOR REVIEW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-06-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-02 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-02 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2023-06-02 08:29:57 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE STRUCTURAL DRAWINGS, ELECTRICAL DRAWINGS (EXCEPT | | | FOR THE ELECTRICAL DRAWINGS ADDED ON 5-24-23), FIRE | | | PROTECTION DRAWINGS AND THE TELECOM DRAWINGS DO NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | PLUMBING AND GAS (P) SHEETS APPROVED. | | 2023-06-01 12:32:28 | PLUMBING/GAS PLAN SIGNATURES PASSED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-24 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-24 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2023-04-24 14:31:24 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE STRUCTURAL DRAWINGS, ELECTRICAL DRAWINGS, FIRE | | | PROTECTION DRAWINGS AND THE TELECOM DRAWINGS DO NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | 2023-04-17 13:27:35 | PLUMBING AND GAS (P) SHEETS APPROVED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-10 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-10 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2023-02-23 11:04:00 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | 2023-02-06 17:04:02 | PLUMBING PLANS PASSED DIG-SIG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-05 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-05 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-25 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-25 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-03-24 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-03-24 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|