| Plan Review Stops For Permit 23011083 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-04-13 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-04-13 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2023-04-13 15:49:27 | WORK IS BEING DONE ON THE NORTH BUILDING WITH THE | | | ADDRESS OF 3205 BROADWAY ON APTS 7,8,9,10,11,12,14,15, | | | UPDATED PERMIT TO REFLECT THE CORRECT BUILDING ADDRESS |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-03-15 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-03-15 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2023-03-15 10:59:57 | IS THIS FOR THE NORTH OR SOUTH BUILDING, PLEASE RESPOND | | | TO [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-05-22 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-05-22 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-04-04 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-04-04 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2023-04-04 08:50:12 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1 & WPB AMENDMENTS TO FBC B 107.2.1, THE | | | INFORMATION THAT HAS BEEN SUBMITTED IS NOT CLEAR. | | | PLEASE ADDRESS THE FOLLOWING: | | | | | | 1.) PROVIDE AN OVERALL FLOOR PLAN TO IDENTIFY WHERE | | | EACH UNIT IS INRELATION TO EACH OTHER AND THAT SHOWS | | | EXTERIOR WALLS AND INTERIOR TENANT SEPARATION WALLS. | | | THE OVERALL FLOOR PLAN DOES NOT MATCH THE UNIT LAYOUTS. | | | PLEASE BE CLEAR AS TO THE ORIENTATION OF UNITS BY | | | INDICATING NORTH, SOUTH, EAST, & WEST. ALSO INDICATE | | | THE 2ND FLOOR ON LAYOUT SHEET. | | | 2.) OK, MECHANICAL UNIT INFORMATION MUST BE APPROVED | | | THROUGH MECHANICAL PERMIT #23031036. | | | 3.) OK, WINDOWS/DOORS WERE APPROVED UNDER PERMIT | | | #21120857. | | | 4.) PROVIDE THE DETAILS FOR THE NEW SHOWER WORK | | | INCLUDING LOCATION OF SHOWER WALLS IN RELATION TO | | | EXTERIOR TENANT SEPARATION WALLS AND FLOOR/CEILING WORK | | | FOR DUE TO SHOWERS. PROVIDE A WALL DETAIL SHOWING ALL | | | MATERIAL TO BE USED INCLUDING FLOOR INSULATION, | | | FRAMING, DRYWALL, & CEMENT BOARD. THIS MUST INCLUDE THE | | | METHOD OF MAINTAINING THE FIRE RATING DETAILS SUCH AS | | | USING THE DRYWALL WITH THE CEMENT BOARD ON SHOWER | | | WALLS. | | | 5.) THE VALUATION DOES NOT APPEAR TO BE ACCURATE IN | | | ACCORDANCE WITH THE ICC BUILDING VALUATION DATA | | | CONSTRUCTION COST SCHEDULE AND THE MARSHALL / SWIFT | | | VALUATIONS. PLEASE RE-EVALUATE THE COST OF THIS PROJECT | | | AND PROVIDE A BREAKDOWN OF COSTS OF ALL WORK. | | | 6.) THE CONTRACTOR ON APPLICATION APPEARS TO BE A | | | PLUMBING CONTRACTOR. FOR THIS PROJECT, PERMITS FOR | | | MECHANICAL AND BUILDING PERMITS HAVE BEEN OBTAINED. | | | THESE ADDITIONAL PERMITS (MECHANICAL 23031036 & | | | BUILDING 23031034) MUST BE APPROVED. | | | 7.) EACH PLAN SHEET SUBMITTED NEEDS TO BE SIGNED BY THE | | | PERSON RESPONSIBLE FOR THE DESIGN. SEVERAL OF THE | | | SUBMITTED SHEETS HAVE NOT BEEN SIGNED BY CONTRACTOR. | | | PLAN SHEET IDENTIFIED AS "001 PLAN" (ELECTRICAL RISER) | | | IS A COPY OF AN ORIGINAL HAND SIGNED/SEALED PLAN SHEET | | | BY AN ARCHITECT. THIS MUST BE 3RD PARTY VERIFIED | | | DIGITALLY SIGNATURE/SEAL BY ARCHITECT. PLEASE SEE THE | | | SIGNATURE PLAN REVIEW NOTES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-14 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-14 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2023-03-14 08:36:52 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1 & WPB AMENDMENTS TO FBC B 107.2.1, THE | | | INFORMATION THAT HAS BEEN SUBMITTED IS NOT CLEAR. | | | PLEASE ADDRESS THE FOLLOWING: | | | | | | 1.) PROVIDE AN OVERALL FLOOR PLAN TO IDENTIFY WHERE | | | EACH UNIT IS INRELATION TO EACH OTHER AND THAT SHOWS | | | EXTERIOR WALLS AND INTERIOR TENANT SEPARATION WALLS. | | | 2.) PROVIDE THE DETAILED INFORMATION FOR THE UNITS ONLY | | | IDENTIFIED AS (EXAMPLE 12,000 BTUS). IF THESE A/C UNITS | | | PLEASE IDENTIFY AS SUCH WITH ALL REQUIRED INFORMATION. | | | IF THESE ARE SOMETHING ELSE, PLEASE CLARIFY. | | | 3.) PROVIDE THE DETAILED INFORMATION FOR WHAT APPEARS | | | TO BE WINDOW AND/OR DOOR OPENINGS. EACH OPENING WILL | | | NEED TO SHOW THE TYPE OF OPENING SUCH AS SINGLE HUNG | | | WINDOW, HORIZONTAL ROLLING WINDOW, OR SLIDING GLASS | | | DOOR. PRODUCT APPROVALS/N.O.A.S ARE REQUIRED FOR EACH | | | WINDOW AND/OR DOOR TO BE INSTALLED. | | | 4.) PROVIDE THE DETAILS FOR THE NEW SHOWER WORK | | | INCLUDING LOCATION OF SHOWER WALLS IN RELATION TO | | | EXTERIOR AND INTERIOR SEPARATION WALLS. ALSO PROVIDE A | | | WALL DETAIL SHOWING ALL MATERIAL TO BE USED INCLUDING | | | INSULATION, FRAMING, DRYWALL, CEMENT BOARD, AND ANY | | | FIRE RATING DETAILS. | | | 5.) THE VALUATION DOES NOT APPEAR TO BE ACCURATE IN | | | ACCORDANCE WITH THE ICC BUILDING VALUATION DATA | | | CONSTRUCTION COST SCHEDULE AND THE MARSHALL / SWIFT | | | VALUATIONS. PLEASE RE-EVALUATE THE COST OF THIS PROJECT | | | AND PROVIDE A BREAKDOWN OF COSTS. | | | 6.) THE CONTRACTOR ON APPLICATION APPEARS TO BE A | | | PLUMBING CONTRACTOR. FOR THIS PROJECT, A MECHANICAL AND | | | A GENERAL OR BUILDING CONTRACTOR WILL BE REQUIRED IN | | | ADDITION TO PLUMBING CONTRACTOR. ADDITIONAL PERMITS | | | AND/OR SUB-PERMITS WILL ALSO BE REQUIRED. | | | 7.) EACH PLAN SHEET SUBMITTED NEEDS TO BE SIGNED BY THE | | | PERSON RESPONSIBLE FOR THE DESIGN. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-05-22 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-05-15 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-04-13 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-03-23 |
Time |
16:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-03-15 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-24 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-24 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-24 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2023-03-24 13:54:22 | PROVIDE A COMPLETE MECAHNICAL DESIGN FOR EACH OF THESE | | | UNITS. THIS WILL INCLUDE THE ENERGY CALCULATIONS, THE | | | ECHANICAL EQUIPMENT SIZING CALCULATIONS AND MECHANICAL | | | DRAWINGS SHOWING THE INDOOR UNIT LOCATIONS AND THE | | | CINDENSING UNIT LOCATIONS INCLUDING THE TIE DOWN | | | METHOD. FBC 107.3.5 | | | | | | THE MECHANICAL DESIGN WAS APPROVED UNDER PERMIT # | | | 23031036. ME | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-14 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-14 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2023-03-14 07:17:57 | 1ST REVIEW FMC | | | PERMIT: 23011083 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) OUR RECORDS DO NOT SHOW A MECHANICAL SYSTEM EVER | | | BEEN PERMITTED FOR THIS ADDRESS. NOTE 1 ON THE DRAWINGS | | | INDICATE 12,000 BTU. IS THIS A MECHANICAL SYSTEM? IF | | | SO, PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS SYSTEM. IT WILL ALSO NEED TO | | | PROVIDE HEAT. FMC 312.1; 309.1 | | | | | | 2) PROVIDE MECHANICAL DRAWINGS THAT SHOW THE INDOOR | | | UNITS AND THE LOCATION OF THE CONDENSING UNITS. FBC | | | 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-05-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-16 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-16 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-24 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-24 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-13 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-13 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-05-22 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-05-22 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-04-04 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-04-04 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2023-04-04 10:16:29 | SIGNATURE REVIEW APPROVED BY THE SUBMITTED ORIGINAL | | | HAND SIGNED/SEALED, BY ARCHITECT, ELECTRICAL SERVICE | | | RISER PLAN SHEET IDENTIFIED AS "001 PLAN". | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-14 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-14 |
Time |
07:37 |
Sent To |
|
|
| Notes |
|
|