Plan Review Details - Permit 23011083
Plan Review Stops For Permit 23011083
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-04-13 Cont ID  
Sent By cpuell Date 2023-04-13 Time 15:48 Rev Time 0.00
Received By cpuell Date 2023-04-13 Time 15:48 Sent To  
Notes
2023-04-13 15:49:27WORK IS BEING DONE ON THE NORTH BUILDING WITH THE
 ADDRESS OF 3205 BROADWAY ON APTS 7,8,9,10,11,12,14,15,
 UPDATED PERMIT TO REFLECT THE CORRECT BUILDING ADDRESS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-03-15 Cont ID  
Sent By cpuell Date 2023-03-15 Time 10:59 Rev Time 0.00
Received By cpuell Date 2023-03-15 Time 10:58 Sent To  
Notes
2023-03-15 10:59:57IS THIS FOR THE NORTH OR SOUTH BUILDING, PLEASE RESPOND
 TO [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 14:28 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-04 Cont ID  
Sent By pvalenti Date 2023-04-04 Time 08:45 Rev Time 0.00
Received By pvalenti Date 2023-04-04 Time 06:16 Sent To  
Notes
2023-04-04 08:50:12PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 & WPB AMENDMENTS TO FBC B 107.2.1, THE
 INFORMATION THAT HAS BEEN SUBMITTED IS NOT CLEAR.
 PLEASE ADDRESS THE FOLLOWING:
  
 1.) PROVIDE AN OVERALL FLOOR PLAN TO IDENTIFY WHERE
 EACH UNIT IS INRELATION TO EACH OTHER AND THAT SHOWS
 EXTERIOR WALLS AND INTERIOR TENANT SEPARATION WALLS.
 THE OVERALL FLOOR PLAN DOES NOT MATCH THE UNIT LAYOUTS.
 PLEASE BE CLEAR AS TO THE ORIENTATION OF UNITS BY
 INDICATING NORTH, SOUTH, EAST, & WEST. ALSO INDICATE
 THE 2ND FLOOR ON LAYOUT SHEET.
 2.) OK, MECHANICAL UNIT INFORMATION MUST BE APPROVED
 THROUGH MECHANICAL PERMIT #23031036.
 3.) OK, WINDOWS/DOORS WERE APPROVED UNDER PERMIT
 #21120857.
 4.) PROVIDE THE DETAILS FOR THE NEW SHOWER WORK
 INCLUDING LOCATION OF SHOWER WALLS IN RELATION TO
 EXTERIOR TENANT SEPARATION WALLS AND FLOOR/CEILING WORK
 FOR DUE TO SHOWERS. PROVIDE A WALL DETAIL SHOWING ALL
 MATERIAL TO BE USED INCLUDING FLOOR INSULATION,
 FRAMING, DRYWALL, & CEMENT BOARD. THIS MUST INCLUDE THE
 METHOD OF MAINTAINING THE FIRE RATING DETAILS SUCH AS
 USING THE DRYWALL WITH THE CEMENT BOARD ON SHOWER
 WALLS.
 5.) THE VALUATION DOES NOT APPEAR TO BE ACCURATE IN
 ACCORDANCE WITH THE ICC BUILDING VALUATION DATA
 CONSTRUCTION COST SCHEDULE AND THE MARSHALL / SWIFT
 VALUATIONS. PLEASE RE-EVALUATE THE COST OF THIS PROJECT
 AND PROVIDE A BREAKDOWN OF COSTS OF ALL WORK.
 6.) THE CONTRACTOR ON APPLICATION APPEARS TO BE A
 PLUMBING CONTRACTOR. FOR THIS PROJECT, PERMITS FOR
 MECHANICAL AND BUILDING PERMITS HAVE BEEN OBTAINED.
 THESE ADDITIONAL PERMITS (MECHANICAL 23031036 &
 BUILDING 23031034) MUST BE APPROVED.
 7.) EACH PLAN SHEET SUBMITTED NEEDS TO BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. SEVERAL OF THE
 SUBMITTED SHEETS HAVE NOT BEEN SIGNED BY CONTRACTOR.
 PLAN SHEET IDENTIFIED AS "001 PLAN" (ELECTRICAL RISER)
 IS A COPY OF AN ORIGINAL HAND SIGNED/SEALED PLAN SHEET
 BY AN ARCHITECT. THIS MUST BE 3RD PARTY VERIFIED
 DIGITALLY SIGNATURE/SEAL BY ARCHITECT. PLEASE SEE THE
 SIGNATURE PLAN REVIEW NOTES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By pvalenti Date 2023-03-14 Time 08:07 Rev Time 0.00
Received By pvalenti Date 2023-03-14 Time 07:37 Sent To  
Notes
2023-03-14 08:36:52PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 & WPB AMENDMENTS TO FBC B 107.2.1, THE
 INFORMATION THAT HAS BEEN SUBMITTED IS NOT CLEAR.
 PLEASE ADDRESS THE FOLLOWING:
  
 1.) PROVIDE AN OVERALL FLOOR PLAN TO IDENTIFY WHERE
 EACH UNIT IS INRELATION TO EACH OTHER AND THAT SHOWS
 EXTERIOR WALLS AND INTERIOR TENANT SEPARATION WALLS.
 2.) PROVIDE THE DETAILED INFORMATION FOR THE UNITS ONLY
 IDENTIFIED AS (EXAMPLE 12,000 BTUS). IF THESE A/C UNITS
 PLEASE IDENTIFY AS SUCH WITH ALL REQUIRED INFORMATION.
 IF THESE ARE SOMETHING ELSE, PLEASE CLARIFY.
 3.) PROVIDE THE DETAILED INFORMATION FOR WHAT APPEARS
 TO BE WINDOW AND/OR DOOR OPENINGS. EACH OPENING WILL
 NEED TO SHOW THE TYPE OF OPENING SUCH AS SINGLE HUNG
 WINDOW, HORIZONTAL ROLLING WINDOW, OR SLIDING GLASS
 DOOR. PRODUCT APPROVALS/N.O.A.S ARE REQUIRED FOR EACH
 WINDOW AND/OR DOOR TO BE INSTALLED.
 4.) PROVIDE THE DETAILS FOR THE NEW SHOWER WORK
 INCLUDING LOCATION OF SHOWER WALLS IN RELATION TO
 EXTERIOR AND INTERIOR SEPARATION WALLS. ALSO PROVIDE A
 WALL DETAIL SHOWING ALL MATERIAL TO BE USED INCLUDING
 INSULATION, FRAMING, DRYWALL, CEMENT BOARD, AND ANY
 FIRE RATING DETAILS.
 5.) THE VALUATION DOES NOT APPEAR TO BE ACCURATE IN
 ACCORDANCE WITH THE ICC BUILDING VALUATION DATA
 CONSTRUCTION COST SCHEDULE AND THE MARSHALL / SWIFT
 VALUATIONS. PLEASE RE-EVALUATE THE COST OF THIS PROJECT
 AND PROVIDE A BREAKDOWN OF COSTS.
 6.) THE CONTRACTOR ON APPLICATION APPEARS TO BE A
 PLUMBING CONTRACTOR. FOR THIS PROJECT, A MECHANICAL AND
 A GENERAL OR BUILDING CONTRACTOR WILL BE REQUIRED IN
 ADDITION TO PLUMBING CONTRACTOR. ADDITIONAL PERMITS
 AND/OR SUB-PERMITS WILL ALSO BE REQUIRED.
 7.) EACH PLAN SHEET SUBMITTED NEEDS TO BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 14:28 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-13 Cont ID  
Sent By cpuell Date 2023-04-13 Time 15:49 Rev Time 0.00
Received By cpuell Date 2023-03-23 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-15 Cont ID  
Sent By cpuell Date 2023-03-15 Time 11:00 Rev Time 0.00
Received By cpuell Date 2023-01-24 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-11 Cont ID  
Sent By medwards Date 2023-03-24 Time 13:49 Rev Time 0.00
Received By medwards Date 2023-03-24 Time 13:49 Sent To  
Notes
2023-03-24 13:54:22PROVIDE A COMPLETE MECAHNICAL DESIGN FOR EACH OF THESE
 UNITS. THIS WILL INCLUDE THE ENERGY CALCULATIONS, THE
 ECHANICAL EQUIPMENT SIZING CALCULATIONS AND MECHANICAL
 DRAWINGS SHOWING THE INDOOR UNIT LOCATIONS AND THE
 CINDENSING UNIT LOCATIONS INCLUDING THE TIE DOWN
 METHOD. FBC 107.3.5
  
 THE MECHANICAL DESIGN WAS APPROVED UNDER PERMIT #
 23031036. ME
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By medwards Date 2023-03-14 Time 07:17 Rev Time 0.00
Received By medwards Date 2023-03-14 Time 07:17 Sent To  
Notes
2023-03-14 07:17:571ST REVIEW FMC
 PERMIT: 23011083
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) OUR RECORDS DO NOT SHOW A MECHANICAL SYSTEM EVER
 BEEN PERMITTED FOR THIS ADDRESS. NOTE 1 ON THE DRAWINGS
 INDICATE 12,000 BTU. IS THIS A MECHANICAL SYSTEM? IF
 SO, PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS SYSTEM. IT WILL ALSO NEED TO
 PROVIDE HEAT. FMC 312.1; 309.1
  
 2) PROVIDE MECHANICAL DRAWINGS THAT SHOW THE INDOOR
 UNITS AND THE LOCATION OF THE CONDENSING UNITS. FBC
 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-05-16 Cont ID  
Sent By rwbrown Date 2023-05-16 Time 10:04 Rev Time 0.00
Received By rwbrown Date 2023-05-16 Time 10:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By rwbrown Date 2023-03-24 Time 08:52 Rev Time 0.00
Received By rwbrown Date 2023-03-24 Time 08:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-03-13 Cont ID  
Sent By rwbrown Date 2023-03-13 Time 12:51 Rev Time 0.00
Received By rwbrown Date 2023-03-13 Time 12:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 14:28 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By pvalenti Date 2023-04-04 Time 10:06 Rev Time 0.00
Received By pvalenti Date 2023-04-04 Time 10:06 Sent To  
Notes
2023-04-04 10:16:29SIGNATURE REVIEW APPROVED BY THE SUBMITTED ORIGINAL
 HAND SIGNED/SEALED, BY ARCHITECT, ELECTRICAL SERVICE
 RISER PLAN SHEET IDENTIFIED AS "001 PLAN".
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-14 Cont ID  
Sent By pvalenti Date 2023-03-14 Time 09:05 Rev Time 0.00
Received By pvalenti Date 2023-03-14 Time 07:37 Sent To  
Notes
***NONE***