| 2023-02-23 15:47:55 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | 1. PROVIDE A FLOOR PLAN. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN; |
| | FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| | FBC R107.3.5.1 THRU 107.3.5.5 |
| | |
| | 2.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE |
| | SPECIFICATION SHEETS OF A FLUID APPLIED MEMBRANE. |
| | FBC R 703.4, FBC B 1405.4: |
| | A FLASHING DETAIL OR SPECIFICATION IS REQUIRED. THIS |
| | COMMENT CAN BE RESOLVED BY DOING ONE OF THE FOLLOWING: |
| | |
| | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED |
| | AND NOTE THE CODE REFERENCE ??? FBC R 703.4; FBC B |
| | 1405.4: |
| | EXAMPLE "FLASHING IN ACCORDANCE WITH FBC R 703.4/B |
| | 1405.4 WILL BE INSTALLED". |
| | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS |
| | MAY INCLUDE MORE THAN ONE OPTION |
| | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN |
| | ONE |
| | OPTION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |