| Plan Review Stops For Permit 23011002 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-11 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-11 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-15 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-15 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2023-03-15 18:55:17 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23011002 | | | 130 BLOOMFIELD DR | | | | | | 1- GENERATOR CONCRETE PAD ENGINEERING IS DESIGNED BASED | | | ON 2017 FBC. ENGINEERING NEEDS TO BE REVISED USING ASCE | | | -16 AND 2020 FBC WHICH IS THE CURRENT CODE. ENGINEER TO | | | REVISE ENGINEERING DATA AS REQUIRED. | | | CHAPTER 553 F.S. | | | | | | 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL | | | SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. | | | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | 3- THE GENERATOR SHALL BE LOCATED A MINIMUM OF 10 FT. | | | FROM ANY OPENING INCLUDING WINDOWS, DOORS, ETC. SEC. | | | R303.5.1 FBC RES. PROVIDE NOTE ON SURVEY TO AVOID | | | CONFLICTS AT TIME OF INSPECTION. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-03-10 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-03-10 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-05 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-05 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-10 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-10 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2023-04-10 17:11:16 | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 23011002 | | | 4/10/23 | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS | | | BELOW AND NOTE- THE CONTRACTOR HAS THE OPTION OF | | | REQUESTING A SEPARATE PERMIT FOR THE GAS PIPING SYSTEM. | | | IF THIS OPTION IS SELECTED PLEASE EMAOIL ME AT | | | [email protected] AND I WILL REMOVE THE FAILED REVIEW AND | | | PROVIDE A "N" RESULT WHICH MEANS NO GAS REVIEW UNDER | | | THIOS PERMIT. | | | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | | THE NEW GAS PIPING TO THE GENERATOR AND EXISTING GAS | | | PIPING AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 | | | & G2412.4 FBC RES. WPB BUILDING DEPT. RECORDS INDICATE | | | PREVIOUS GAS PIPING PERMIT- 13100338. REFER TO FBC RES. | | | CHAPTER 24 FUEL GAS- THE NEW RISER SHALL INDICATE: | | | A) DELIVERY PRESSURE AT THE METER. | | | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | C) TYPES AND SIZES OF PIPING. | | | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | F) LOCATIONS OF REGULATORS, SHUTOFF VALVES. | | | G) OUTLET PRESSURES AT REGULATORS. | | | H) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | I) PIPE SIZING TABLES. | | | 2) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2023-03-16 15:07:13 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23011002 | | | 3/16/23 | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS | | | BELOW AND NOTE- THE CONTRACTOR HAS THE OPTION OF | | | REQUESTING A SEPARATE PERMIT FOR THE GAS PIPING SYSTEM. | | | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | | THE NEW GAS PIPING TO THE GENERATOR AND EXISTING GAS | | | PIPING AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 | | | & G2412.4 FBC RES. WPB BUILDING DEPT. RECORDS INDICATE | | | PREVIOUS GAS PIPING PERMIT- 13100338. REFER TO FBC RES. | | | CHAPTER 24 FUEL GAS- THE NEW RISER SHALL INDICATE: | | | A) DELIVERY PRESSURE AT THE METER. | | | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | C) TYPES AND SIZES OF PIPING. | | | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | F) LOCATIONS OF REGULATORS, SHUTOFF VALVES. | | | G) OUTLET PRESSURES AT REGULATORS. | | | H) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | I) PIPE SIZING TABLES. | | | 2) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-06-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-06-02 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-17 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-07 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-02-24 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-05 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-05 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-10 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-10 |
Time |
17:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-04-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-11 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-11 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-15 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-15 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2023-03-15 18:59:02 | | | | | | | SIGNATURE REVIEW: | | | | | | 1-- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF | | | THE ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL | | | SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. | | | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | 2023-03-10 08:40:43 | ELECTRICAL PAGE NOT SIGNED. JLEAHY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-17 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-17 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-03-07 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-03-07 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2023-03-07 08:57:00 | 3/7/23 FAILED FOR THE FOLLOWING REASONS: | | | | | | | | | 1. PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | REAR SETBACK FOR THE PRIMARY STRUCTURE IS REQUIRED TO | | | BE 15 FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS | | | | | | REAR SETBACK FOR BLOOMFILED IS 13 FEET, THEREFORE | | | GENERATOR MUST BE 9 FEET FROM THE REAR PROPERTY LINE | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | PLANNER | | | [email protected] | | | |
|
|