Plan Review Details - Permit 23010779
Plan Review Stops For Permit 23010779
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-02-08 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:48 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-08 07:04:50 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-18 Cont ID  
Sent By jwitmer Date 2023-04-18 Time 12:45 Rev Time 0.00
Received By jwitmer Date 2023-04-18 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-08 Cont ID  
Sent By jwitmer Date 2023-02-08 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2023-02-07 Time 16:48 Sent To  
Notes
2023-02-08 07:03:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23010779
 ADD: 1815 PALM BEACH LAKES BLVD # 05
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 07TH/ 2023
 ACTION: DENIED
  
 1) SHEET G003 ACCESSIBILITY GUIDELINES, PLEASE NOTE THE
 STATE OF FLORIDA USES THE 2020 FBC-ACCESSIBILITY CODE:
 1A) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 1B) DETAIL 10 LAVATORIES IS MISSING: 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
 1C) DETAIL 16 ALL GRAB BAR LOCATIONS ARE MEASURED FROM
 FINISH FLOOR TO THE CENTER LINE OF THE GRAB BAR. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
 1D) TOILET PAPER HOLDER SHOWS A DIMENSION OF 12 INCHES
 FROM THE FRONT OF THE TOILET TO THE SIDE OF THE TOILET
 PAPER HOLDER. PLEASE REVIEW IN THE 2020
 FBC-ACCESSIBILITY CODE SECTION TOILET PAPER DISPENSERS.
 604.7. THE TOILET PAPER DISPENSER SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE
 OF THE DISPENSER.
 2) BUILDING PROVISO: A003 DRIVE THRU DETAILS NOT PART
 OF THIS PERMIT, SEPARATE PERMIT IS REQUIRED. THE PLAN
 ALSO STATES SITE SPECIFIC FOOTING ENGINEERING REQUIRED
 BY FLORIDA LICENSED ENGINEER. NOTE THERE IS NO WIND
 DESIGN GIVEN FOR THIS PLAN.
  
 3) SHEET A503 SOFFIT CONSTRUCTION AT BACK BAR, DETAIL
 1. THE SECTION SHOWS DO NOT ATTACH TACK TO ROOF DECK,
 BUT THERE ARE A SERIES OF FRT BLOCKING THAT THE WALL
 STRUCTURES ARE HUNG FROM. THE DETAIL DOES NOT INDICATE
 SIZE OF FRT BLOCKING OR HOW THE BLOCKING IS TO BE
 SECURED TO THE BAR JOIST. THE DETAIL IS ALSO SILENT AS
 HOW THE VERTICAL FRAMING MEMBERS ARE TO BE SECURED TO
 THE FRT BLOCKING. 2020 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES.
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By mpeterso Date 2023-01-30 Time 13:48 Rev Time 0.00
Received By mpeterso Date 2023-01-30 Time 13:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-30 Cont ID  
Sent By pleduc Date 2023-05-30 Time   Rev Time 0.00
Received By pleduc Date 2023-05-30 Time 13:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-18 Cont ID  
Sent By   Date 2023-04-18 Time   Rev Time 0.00
Received By jcclark Date 2023-04-18 Time 14:53 Sent To  
Notes
2023-04-18 14:54:12PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-21 Cont ID  
Sent By   Date 2023-01-21 Time   Rev Time 0.00
Received By jcclark Date 2023-01-21 Time 07:37 Sent To  
Notes
2023-01-21 07:39:31PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2023-05-26 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-18 Cont ID  
Sent By jleahy Date 2023-05-18 Time 13:36 Rev Time 0.00
Received By jleahy Date 2023-04-17 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-03 Cont ID  
Sent By jwitmer Date 2023-03-03 Time 11:10 Rev Time 0.00
Received By lmarchan Date 2023-01-19 Time 09:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:48 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By medwards Date 2023-01-20 Time 15:36 Rev Time 0.00
Received By medwards Date 2023-01-20 Time 15:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 06:20 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 06:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-18 Cont ID  
Sent By rwbrown Date 2023-04-18 Time 08:07 Rev Time 0.00
Received By rwbrown Date 2023-04-18 Time 08:07 Sent To  
Notes
2023-04-18 08:19:302ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE G-003, DETAIL #14 -- 2020 FPC 405.3.1 - YOU'VE
 NOTED 29" MIN CLEAR FOR THE URINAL. ALL FIXTURES
 REQUIRE 30 INCHES WIDTH AND 15 FROM CENTER CLEAR SPACE
 FOR THE FIXTURE TO ANY WALL OR PARTITION.
  
 2. DONE
  
 3. DONE
  
 4. P-501 - 2020 FPC 607.1.1 -- ALL HOT WATER MUST GO
 THROUGH A MIXING DEVICE. 1017 MIXING DEVICES ARE ABLE
 TO PRODUCE HOT WATER ABOVE 120 IF NECESSARY. IF YOU
 REQUIRE MORE THAN ONE TEMPERATURE OF HOT WATER OUTPUT,
 THEN MORE THAN ONE MIXING DEVICE CAN BE INSTALLED AND
 SET TO EACH DESIRED TEMPERATURE. BUT, UNDER NO
 CIRCUMSTANCE CAN ANY AMOUNT OF HOT WATER BE DELIVERED
 WITHOUT A MIXING DEVICE.
  
 5. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By jesmith Date 2023-01-25 Time 16:23 Rev Time 0.00
Received By jesmith Date 2023-01-25 Time 16:21 Sent To  
Notes
2023-01-30 11:05:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010779 1815 PALM BEACH LAKES BLVD # 05
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 PLAN SHEET G003-ACCESIBILITY GUIDELINES
 ***A) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***B) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 2. WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR. THIS INCLUDES BUT IS NOT LIMITED TO DRAINS
 FROM ICE BINS, HAND SINKS. PLEASE REVIEW YOUR DRAINAGE
 PLAN AND MAKE CORRECTIONS AS REQUIRED PER FBC PL
 1003.2, 1003.3.1; PROVIDE PLAN AND RISER DIAGRAM FOR
 SANITARY DRAIN PIPING RECEIVING THE DISCHARGE OF NEW
 ICE BINS, HAND SINKS AND ANY OTHER NEW EQUIPMENT THAT
 IS NOT ALLOWED TO DISCHARGE TO THE INTERCEPTOR. PROVIDE
 POINTS OF CONNECTION TO EXISTING SANITARY.
  
 3. PROVIDE REVISED CALCULATIONS AND STANDARD FOR SIZING
 OF THE GREASE INTERCEPTOR. FBC PL 1003.3.5
  
 4. P111/KEYED NOTE 1: REPLACE EXISTING WATER HEATER
 WITH NEW. REFERS TO WATER HEATER DETAIL ON P501. DETAIL
 DOES NOT EXIST. PLEASE PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , TEMPERATURE ACTUATED MIXING VALVE ASSE 1017
 FOR THE HOT WATER DISTRIBUTION, SIZED THERMAL EXPANSION
 CONTROL DEVICE IF DOWNSTREAM OF CHECK VALVE OR BACKFLOW
 PREVENTER, T&P DISCHARGE INCLUDING TERMINATION AND
 WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER
 WPB FPC 107.2.1, 107.3.5.1.3(5) ; COMPLY WITH FBC PL
 607.1.1, 607.3, 613.1, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 5. PROVIDE MATERIAL SPECIFICATIONS FOR WATER, DRAINAGE
 AND VENT PIPING. FBC PL CHAPTER 6,7,9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
2023-01-25 16:23:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010779 1815 PALM BEACH LAKES BLVD # 05
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 PLAN SHEET G003-ACCESIBILITY GUIDELINES
 ***A) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***B) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 2. WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR. THIS INCLUDES BUT IS NOT LIMITED TO DRAINS
 FROM ICE BINS, HAND SINKS. PLEASE REVIEW YOUR DRAINAGE
 PLAN AND MAKE CORRECTIONS AS REQUIRED PER FBC PL
 1003.2, 1003.3.1; PROVIDE PLAN AND RISER DIAGRAM FOR
 SANITARY DRAIN PIPING RECEIVING THE DISCHARGE OF NEW
 ICE BINS, HAND SINKS AND ANY OTHER NEW EQUIPMENT THAT
 IS NOT ALLOWED TO DISCHARGE TO THE INTERCEPTOR. PROVIDE
 POINTS OF CONNECTION TO EXISTING SANITARY.
  
 3. PROVIDE REVISED CALCULATIONS AND STANDARD FOR SIZING
 OF THE GREASE INTERCEPTOR. FBC PL 1003.3.5
  
 4. P111/KEYED NOTE 1: REPLACE EXISTING WATER HEATER
 WITH NEW. REFERS TO WATER HEATER DETAIL ON P501. DETAIL
 DOES NOT EXIST. PLEASE PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , TEMPERATURE ACTUATED MIXING VALVE ASSE 1017
 FOR THE HOT WATER DISTRIBUTION, SIZED THERMAL EXPANSION
 CONTROL DEVICE IF DOWNSTREAM OF CHECK VALVE OR BACKFLOW
 PREVENTER, T&P DISCHARGE INCLUDING TERMINATION AND
 WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER
 WPB FPC 107.2.1, 107.3.5.1.3(5) ; COMPLY WITH FBC PL
 607.1.1, 607.3, 613.1, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 5. PROVIDE MATERIAL SPECIFICATIONS FOR WATER, DRAINAGE
 AND VENT PIPING. FBC PL CHAPTER 6,7,9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-18 Cont ID  
Sent By jleahy Date 2023-05-18 Time 13:36 Rev Time 0.00
Received By jleahy Date 2023-05-18 Time 13:36 Sent To  
Notes
2023-04-18 12:38:40A & I SHEETS, DIGITAL SIGNATURES ARE OK. 4/18/23
 JWITMER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By mpeterso Date 2023-01-30 Time 13:48 Rev Time 0.00
Received By mpeterso Date 2023-01-30 Time 13:48 Sent To  
Notes
2023-01-30 13:49:00ALL PLANS PASSED SIGNATURE REVIEW. MP
2023-01-25 16:26:34ELECTRONIC SIGNATURES FOR PLUMBING ARE APPROVED. JS
2023-01-20 15:36:40MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By eschneid Date 2023-05-17 Time 11:06 Rev Time 0.25
Received By eschneid Date 2023-05-17 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By eschneid Date 2023-03-03 Time 10:05 Rev Time 0.50
Received By eschneid Date 2023-03-03 Time 08:57 Sent To  
Notes
2023-03-03 10:06:57FAILED
  
 1) THE OUTLETS MANAGEMENT STAMP IS REQUIRED ON THE
 PLANS. ALTERNATIVELY, YOU MAY PROVIDE A LIST OF THE
 APPROVED PLAN SHEETS THAT HAS BEEN STAMPED BY
 MANAGEMENT.
  
 2) THE MENU BOARD AND OTHER DRIVE THROUGH RELATED
 FEATURES REQUIRE SEPARATE PERMITTING WITH FULL PLANS.
 NOTE: THIS IS THE WORK SHOWN ON SHEETS A-002, A-003,
 E.004 AND E-004.1.
  
 3) THE MODIFICATIONS TO THE INTERIOR TO THE BUILDING
 COMPLY WITH ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446