Plan Review Details - Permit 23010432
Plan Review Stops For Permit 23010432
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-04-11 Cont ID  
Sent By cpuell Date 2023-04-11 Time 09:11 Rev Time 0.00
Received By cpuell Date 2023-04-11 Time 09:11 Sent To  
Notes
2023-04-11 09:31:04ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By cpuell Date 2023-01-31 Time 08:37 Rev Time 0.00
Received By cpuell Date 2023-01-31 Time 08:37 Sent To  
Notes
2023-01-31 08:37:40PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS ADDRESSING THE BUILDING

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2023-03-07 Cont ID  
Sent By swelter Date 2023-03-07 Time 10:14 Rev Time 0.00
Received By swelter Date 2023-03-07 Time 10:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-07-17 Cont ID  
Sent By rmcphers Date 2023-07-17 Time 12:48 Rev Time 0.00
Received By rmcphers Date 2023-07-17 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-29 Cont ID  
Sent By rmcphers Date 2023-06-29 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2023-06-29 Time 10:30 Sent To  
Notes
2023-06-29 10:34:11COMMUNITY CENTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PAGE 6 OF THE THRESHOLD INSPECTOR FORM WHICH IS
 SIGNED AND SEALED BY THE THRESHOLD INSPECTOR - DOES NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 I CHECK THE ELECTRONIC SIGNATURE BY OPENING THEM IN
 ???ADOBE READER???. THE ???ADOBE READER??? STATES
 WHETHER THEY ARE AN ORIGINAL ELECTRONICALLY SIGNED
 DOCUMENT. WHEN ELECTRONICALLY SIGNED DRAWINGS ARE
 PRINTED OUT, THEY LOSE THEIR ELECTRONIC SIGNATURE.
 ELECTRONICALLY SIGNED DRAWINGS NEED TO BE MOVED AROUND
 IN THE COMPUTER FROM PLACE TO PLACE. FROM THE
 ARCHITECT???S OR ENGINEER???S COMPUTER TO YOUR COMPUTER
 TO THE CITY???S ELECTRONIC PLAN REVIEW (PROJECTDOX).
 MAYBE YOURS WERE PRINTED OUT AT SOME TIME?
  
 2) PAGE 8 OF THE THRESHOLD INSPECTOR FORMS "GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS AND RESIDENT INSPECTORS" WHICH IS FOR THE
 CONTRACTORS SIGNATURE WILL BE REQUIRED WHEN THE
 CONTRACTOR IS CHOSEN.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-26 Cont ID  
Sent By rmcphers Date 2023-06-26 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2023-06-26 Time 15:41 Sent To  
Notes
2023-06-26 15:45:12COMMUNITY CENTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING LS1.10 AND PAGE 6 OF THE THRESHOLD INSPECTOR
 FORM WHICH IS SIGNED AND SEALED BY THE THRESHOLD
 INSPECTOR - DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 2) PLEASE FILL OUT PAGE 8 OF THE THRESHOLD INSPECTOR
 FORMS "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS"
 WHICH IS FOR THE CONTRACTORS SIGNATURE AND THE PROPERTY
 OWNERS SIGNATURE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By rmcphers Date 2023-04-05 Time 16:42 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 16:31 Sent To  
Notes
2023-04-05 16:26:46COMMUNITY CENTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE AREA INCREASE CALCULATIONS - FBC
 506.2.1 - DRAWING LS1.1.0 - BUILDING CODE ANALYSIS -
 FOR A NON SEPARATED OCCUPANCY THE ALLOWABLE AREA FOR AN
 OCCUPANCY A3 OR 4 IS (24000) - FBC 508.3.2 ALLOWABLE
 BUILDING AREA AND HEIGHT. THE ALLOWABLE BUILDING AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION
 503.1.
  
 2) DRAWING LS1.1.0 - BUILDING CODE ANALYSIS - THE
 DRAWINGS SHOW A GYMNASIUM WITH SPECTATOR SEATING -
 SHOULD BE AN OCCUPANCY CLASSIFICATION A4
  
 3) IF CHANGING THE BUILDING CONSTRUCTION TYPE - THE
 BUILDING SET BACKS FROM THE EXISTING BUILDING SHOWN ON
 DRAWING SP-1 WILL NEED TO BE EVALUATED FOR FIRE RATINGS
 - FBC CHAPTER 6
  
 4) "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS"
 THE FORM ON PAGE 6 FOR THE THRESHOLD INSPECTOR NEEDS TO
 BE FILLED OUT - THE FORM ON PAGE 8 NEEDS TO BE FILLED
 OUT FOR THE CONTRACTOR.
  
 5) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-01 Cont ID  
Sent By rmcphers Date 2023-03-01 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2023-03-01 Time 08:57 Sent To  
Notes
2023-03-01 12:36:08COMMUNITY CENTER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SEPARATE PERMIT REQUIRED FOR - EXISTING BUILDING
 DEMOLITION, FENCES, SITE WALLS, TENNIS COURTS, SHADE
 STRUCTURES, SITE LIGHTING AND PARKING LOTS.
  
 2) PLEASE PROVIDE THE FOLLOWING STATEMENT ON THE
 ARCHITECTURAL DRAWINGS - THRESHOLD BLDG. REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 FLORIDA STATUTES.
  
 3) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER
 THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 4) PLEASE PROVIDE A THRESHOLD INSPECTION PLAN FBC WPB
 110.8.1
  
 5) THE PROVIDED PRODUCT APPROVAL (FL17682-R6) - ON THE
 FRONT PAGE OF THE PRODUCT APPROVAL UNDER "STATUS" IT
 SAYS "PENDING FBC APPROVAL" STATUS NEEDS TO SAY
 "APPROVED".
  
 6) DRAWINGS COV-1, GN-1, DM-1, DM-2, DM-3, PGD-1,
 PGD-2, PGD-3, UT-1, UT-2, UT-3, DET-1, DET-2, DET-3,
 HD-1, HD-2, HD-3, HD-4, LT-1, LT-2, LT-3 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By mpeterso Date 2023-04-19 Time 10:18 Rev Time 0.00
Received By mpeterso Date 2023-04-19 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-21 Cont ID  
Sent By mpeterso Date 2023-02-21 Time 13:47 Rev Time 0.00
Received By mpeterso Date 2023-02-21 Time 13:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-04-12 Cont ID  
Sent By lquinone Date 2023-04-12 Time 13:56 Rev Time 0.00
Received By lquinone Date 2023-04-12 Time 13:56 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By rrossano Date 2023-01-30 Time   Rev Time  
Received By rrossano Date 2023-01-30 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-06-30 Cont ID  
Sent By clfranci Date 2023-06-30 Time   Rev Time 0.00
Received By clfranci Date 2023-06-30 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-06-09 Cont ID  
Sent By pleduc Date 2023-06-09 Time   Rev Time 0.00
Received By pleduc Date 2023-06-09 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-04 Cont ID  
Sent By cwalker Date 2023-04-04 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-04-04 09:12:42FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY EXISTING LIFE SAFETY SYSTEM
 (FIRE SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4
 CONTINUOUS HOURS IN DURATION WILL REQUIRE THE
 IMPLEMENTATION OF A FIRE WATCH.
  
 (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) DURING DEMOLITION AND
 CONSTRUCTION MUST BE CONDUCTED UNDER SEPARATE PERMITS
 BY PROPERLY QUALIFIED CONTRACTORS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-27 Cont ID  
Sent By cwalker Date 2023-01-27 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-01-27 13:21:55FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY EXISTING LIFE SAFETY SYSTEM
 (FIRE SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4
 CONTINUOUS HOURS IN DURATION WILL REQUIRE THE
 IMPLANTATION OF A FIRE WATCH.
  
 (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) DURING DEMOLITION AND
 CONSTRUCTION MUST BE CONDUCTED UNDER SEPARATE PERMITS
 BY PROPERLY QUALIFIED CONTRACTORS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By rwbrown Date 2023-04-05 Time 08:43 Rev Time 0.00
Received By rwbrown Date 2023-04-05 Time 08:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By jesmith Date 2023-01-30 Time 16:11 Rev Time 0.00
Received By jesmith Date 2023-01-30 Time 13:48 Sent To  
Notes
2023-01-30 16:10:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010432 1501 N AUSTRALIAN AVE
  
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
  
 A. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
  
 1. INDICATE ON THE PLANS THE TYPE OF GAS; NATURAL OR
 LP.
  
 2. INCLUDE ON THE RISER DIAGRAM THE FOLLOWING:
 ***A) LOCATIONS OF VALVES (INCLUDING EMERGENCY SHUTOFF
 VALVE) AND REGULATORS; FBC FG 401.1
 ***B) SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN
 REGULATORS; FBC FG 402.1
 ***C) INCLUDE PIPE LENGTHS, APPLIANCE ID, BTU LOADS,
 MATERIALS AND DISTANCES TO THE APPLIANCES THAT WERE
 USED TO CALCULATE MINIMUM PIPE SIZES USING THE SIZING
 TABLES FROM FBC FG 402.4; INCLUDE REFERENCES TO THE
 SPECIFIC TABLE(S). FBC FG 402.4.1, 402.4.2, 402.4.3
  
 3. PROVIDE AN EQUIPMENT SCHEDULE; LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
  
 4. PROVIDE ON FLOOR PLAN THE ID AND LOCATION OF
 APPLIANCE AND CORRESPONDING BTU LOAD.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 COOKING LINE AND SHOW HOW IT IS PROVIDED. FBC FG 304.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 PLEASE CONTACT RYAN BROWN WITH ANY QUESTIONS
 [email protected]
 561-805-6692
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-17 Cont ID  
Sent By rmcphers Date 2023-07-17 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2023-07-12 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-03 Cont ID  
Sent By aoliver Date 2023-07-03 Time 07:35 Rev Time 0.00
Received By aoliver Date 2023-06-28 Time 17:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-26 Cont ID  
Sent By rmcphers Date 2023-06-26 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2023-06-08 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-24 Cont ID  
Sent By medwards Date 2023-04-24 Time 15:50 Rev Time 0.00
Received By medwards Date 2023-04-03 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-08 Cont ID  
Sent By aoliver Date 2023-03-08 Time 09:10 Rev Time 0.00
Received By aoliver Date 2023-01-25 Time 10:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-07-28 Cont ID  
Sent By aoliver Date 2023-07-28 Time 08:57 Rev Time 0.00
Received By aoliver Date 2023-07-17 Time 13:41 Sent To  
Notes
2023-07-28 08:57:31NO IMPACT FEES DUE, SEE EMAIL UPLOADED
2023-07-17 13:41:357/17/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-01 Cont ID  
Sent By rmcphers Date 2023-03-01 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2023-03-01 Time 13:12 Sent To  
Notes
2023-03-01 13:14:03PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-04-24 Cont ID  
Sent By medwards Date 2023-04-24 Time 15:47 Rev Time 0.00
Received By medwards Date 2023-04-24 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-22 Cont ID  
Sent By medwards Date 2023-02-22 Time 06:48 Rev Time 0.00
Received By medwards Date 2023-02-17 Time 16:09 Sent To  
Notes
2023-02-22 06:48:301ST REVIEW FMC
 PERMIT: 23010432
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 4) ADD A NOTE ON THE DRAWING THAT THIS BUILDING WILL
 NEED TO MEET THE COMMERCIAL BUILDING COMMISSIONING
 REQUIREMENTS OF FEC C408. FEC C401.2.1
  
 5) SHEET M1.0.1: PLEASE UPDATE THE MULTIPURPOSE
 ASSEMBLY OCCUPANCY OUTDOOR AIR CFM???S FOR RTU-1. DOING
 THE CALCULATION USING THE OCCUPANCY DENSITY FROM TABLE
 403.3.1.1 FOR THE 1580 SQ. FT. I GET 190 OCCUPANTS.
 THIS INCREASES THE OUTDOOR AIR FOR THIS AREA TO 1045
 CFM???S.
  
 6) SHEET M1.0.1: RTU-5; THE MULTIPURPOSE ASSEMBLY AREA
 WOULD HAVE 216 OCCUPANTS WITH A TOTAL OF 1188 CFM???S
 OF OUTDOOR AIR REQUIRED FOR THIS SPACE.
  
 7) SHEET M1.0.1: RTU-5; THE KITCHEN COOKING AREA IS
 MISSING THE PEOPLE BREATHING ZONE PART OF THE EQUATION.
 MINIMUM OF 12 PEOPLE FOR THIS AREA AND A TOTAL OF
 OUTDOOR AIR IS 157 CFM???S REQUIRED.
  
 8) SHEET M1.2.1: THE RETURN IN THE KITCHEN WILL NEED TO
 MEET THE 10 FEET FROM THE HOOD REQUIREMENT IN FMC 601.5
 2ND EXCEPTION NUMBER 1.
  
 9) SHEET M1.2.1: PLAN NOTE 4 INDICATES AN EXHAUST FAN
 EF 1-5, THIS EF 1-5 IS NOT ON THE EXHAUST FAN SCHEDULES
 ON SHEET 1.0.1.
  
 10) SHEET M1.2.1: PLAN NOTE 3 INDICATES AN EXHAUST FAN
 EF 1-6, THIS EF 1-6 IS NOT ON THE EXHAUST FAN SCHEDULES
 ON SHEET 1.0.1
  
 11) ALL MECHANICAL EQUIPMENT ON THE ROOF WILL NEED TO
 MEET THE 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARD
 PROTECTION ACCORDING TO FMC 304.11
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-09 Cont ID  
Sent By rwbrown Date 2023-06-09 Time 10:59 Rev Time 0.00
Received By rwbrown Date 2023-06-09 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By rwbrown Date 2023-04-05 Time 08:43 Rev Time 0.00
Received By rwbrown Date 2023-04-05 Time 08:43 Sent To  
Notes
2023-04-05 08:50:101ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. 2020 FPC 1003.3.1 - THE HAND SINK IN THE KITCHEN IS
 NOT DESIGNED TO RECEIVE GREASE WASTE AND MUST GO TO THE
 SANITARY, NOT THE GREASE WASTE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By jesmith Date 2023-02-01 Time 14:54 Rev Time 0.00
Received By jesmith Date 2023-01-30 Time 11:43 Sent To  
Notes
2023-02-01 14:49:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010432 1501 N AUSTRALIAN AVE
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR INTERCEPTOR(S) AND BACKFLOW
 PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
  
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 SAMANTHA HILL, CHIEF PLANS EXAMINER AT [email protected]
 AND RYAN BROWN, CHIEF PLUMBING INSPECTOR AT
 [email protected] VIA EMAIL WITH THE PERMIT NUMBER(S).
  
 PLUMBING COMMENTS:
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 ***A) PLEASE SHOW THAT THE DRINKING FOUNTAINS COMPLY
 WITH FBC ACC 307.2 PROTRUDING OBJECTS. IF NECESSARY
 PROVIDE A CANE APRON FOR THE HIGHER LEVEL DRINKING
 FOUNTAIN TO COMPLY; NOTE IT ON THE PLUMBING FIXTURE
 SCHEDULE.
 ***B) ROOM 142/STAFF LOUNGE: SINK SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. PROVIDE CLEAR FLOOR SPACE AND CABINET DETAIL;
 INCLUDE KNEE AND TOE CLEARANCE IF APPLICABLE. FBC ACC
 212.3, 606.2, 606.3, 306.2, 306.3
  
 2. P1.0.0: PER WPB FBC 107.2.1, FBC PL CHAPTERS 6, 7,
 9, 11, FBC EC FBC EC C404.4 (A-E) AND TABLE C403.2.10,
 PLEASE PROVIDE A NOTE STATING "SEE MEP SPECIFICATIONS
 22 00 01 THROUGH 22 30 00 FOR PLUMBING SYSTEMS
 SPECIFICATIONS WHICH INCLUDES BUT IS NOT LIMITED TO
 DOMESTIC WATER, SANITARY, STORM, GAS AND PIPING
 INSULATION"
  
 3. P1.4.0/WATER HEATER DETAIL GWH-1:
 ***A) ADD NOTE "MIXING VALVE SHALL COMPLY WITH ASSE
 1017". FBC PL 613.1
 ***B) PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
  
  
 4. P1.4.0/WATER HEATER DETAIL EWH-1:
 ***A) PROVIDE A VACUUM RELIEF VALVE IN COLD WATER
 SUPPLY TO BOTTOM FED WATER HEATER. FBC PL 504.2
 ***B) ADD NOTE "MIXING VALVE SHALL COMPLY WITH ASSE
 1017". FBC PL 613.1
 ***C) PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
  
  
 5. REGARDING THE HOT WATER DISTRIBUTION PIPING: PLEASE
 REFER TO FBC EC C405.1 FOR THE MAXIMUM ALLOWABLE
 DEVELOPED PIPE LENGTH OF HOT WATER DISTRIBUTION FROM
 SOURCE TO FIXTURE. SOURCE AS DEFINED BY FBC PL 607.2
 INCLUDES HOT WATER RECIRCULATING SYSTEM PIPING AND HEAT
 TRACED PIPING. P1.4.0/WATER HEATER DETAIL EWH-1 NOTES A
 RECIRCULATING SYSTEM; P1.4.0/WATER HEATER DETAIL GWH-1
 DOES NOT. PLAN SHEETS P1.2.1, 1.3.2, 1.3.3 PLAN VIEW
 AND WATER RISERS DO NOT PROVIDE RECIRCULATING SYSTEMS.
 PLEASE PROVIDE SYSTEMS TO COMPLY.
 C404.5.1MAXIMUM ALLOWABLE PIPE LENGTH METHOD.
 THE MAXIMUM ALLOWABLE PIPING LENGTH FROM THE NEAREST
 SOURCE OF HEATED WATER TO THE TERMINATION OF THE
 FIXTURE SUPPLY PIPE SHALL BE IN ACCORDANCE WITH THE
 FOLLOWING. WHERE THE PIPING CONTAINS MORE THAN ONE SIZE
 OF PIPE, THE LARGEST SIZE OF PIPE WITHIN THE PIPING
 SHALL BE USED FOR DETERMINING THE MAXIMUM ALLOWABLE
 LENGTH OF THE PIPING IN TABLE C404.5.1.
 1. 1.FOR A PUBLIC LAVATORY FAUCET, USE THE "PUBLIC
 LAVATORY FAUCETS" COLUMN IN TABLE C404.5.1.
 2. 2.FOR ALL OTHER PLUMBING FIXTURES AND PLUMBING
 APPLIANCES, USE THE "OTHER FIXTURES AND APPLIANCES"
 COLUMN IN TABLE C404.5.1.
  
  
  
 6. PROVIDE SCHEDULE AND SPECIFICATION FOR HOT WATER
 RECIRCULATING PUMP NOTED ON P1.4.0/WATER HEATER DETAIL
 EWH-1.
  
  
 7. PLEASE PROVIDE WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 FOR LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. FBC PL 419.5, 607.1.2
  
 8. PLEASE NOTE TRAP PRIMER LINE CONNECTION FOR ALL
 FLOOR DRAINS AND OTHER TRAPS IN NEED OF TRAP SEAL
 PROTECTION AS APPLICABLE. PROVIDE A NOTE REFERENCING
 MEP SPECIFICATION SECTION 22 30 00, PART 2.1, SUB PART
 5(1); PROVIDE DETAIL OF TRAP PRIMER INSTALLATION. FBC
 PL 1002.4.1, 1002.4.1.1 THROUGH 1002.4.1.4
  
 9. KITCHEN/GREASE SYSTEM: PER WPB FBC
 107.3.5.1.3(11)(13), PROVIDE THE FOLLOWING:
 ***A) PROVIDE RISER DIAGRAM OF GREASY WASTE. WPB FBC
 107.3.5.1.3(6)(11)(13)
 ***B) PROVIDE CALCULATIONS FOR SIZING OF GREASE
 INTERCEPTOR. FBC PL 1003.3.5 THROUGH 1003.3.7
 ***C) P1.2.0-PROVIDE DESCRIPTIONS FOR NOTED EQUIPMENT
 ITEMS 202, 204, 400, 402, 505
 ***D) PROVIDE DETAILS FOR DISCHARGE OF NOTED EQUIPMENT
 ITEMS 202, 204, 400, 402, 505 TO GREASY WASTE SYSTEM.
 FBC PL SECTION 802
 ***D) HAND SINKS AND ICE BINS SHALL NOT DISCHARGE TO
 THE GREASE INTERCEPTOR. FBC PL 1003.2
  
 10. SANITARY RISER DIAGRAMS SHALL IN ADDITION TO THE
 TWO PUBLIC GANG BATHS, REFLECT SANITARY DRAINAGE AND
 VENT FOR TOILET ROOMS 125 AND 127, STAFF TOILET ROOMS
 139 AND 140, STAFF LOUNGE 142, LOBBY ROOM 100 (DRINKING
 FOUNTAIN TYPICAL), ROOMS 109 AND 117 FLOOR DRAINS AS
 WELL AS ANY KITCHEN ITEMS THAT SHOULD DISCHARGE TO
 SANITARY. IDENTIFY ALL SANITARY RISER DIAGRAMS WITH
 ROOM NUMBERS THAT CORRESPOND WITH THE FLOOR PLAN. WPB
 FBC 107.2.1, 107.3.5.1.3(4)(6)(13)
  
 11. WATER RISER DIAGRAM PROVIDES MIXING VALVE AT GWH
 FOR 110 DEGREE HOT WATER DISTRIBUTION TO PLUMBING
 FIXTURES. 140 DEGREE WATER IS SUPPLIED DIRECTLY TO THE
 KITCHEN EQUIPMENT. FBC PL 607.1.1 STIPULATES A
 THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES AND FBC PL 613.1 STATES
 TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE INSTALLED
 TO REDUCE WATER TEMPERATURES TO DEFINED LIMITS, SHALL
 COMPLY WITH ASSE 1017. SUCH VALVES SHALL BE INSTALLED
 AT THE HOT WATER SOURCE.
 THIS DOES NOT ELIMINATE THE REQUIREMENT FOR
 WATER-TEMPERATURE LIMITING DEVICES THAT CONFORM TO ASSE
 1070 OR CSA B125.3 FOR LAVATORIES AND GROUP WASH
 FIXTURES LOCATED IN PUBLIC TOILET FACILITIES AS
 REQUIRED BY FBC PL 419.5, 607.1.2.
  
 12. PLEASE RECONCILE WATER HEATER DETAILS ON P4.1.0 AND
 RISER DIAGRAMS. WPB FBC 107.2.1, 107.3.5.1.3(3)(5)(13)
  
 13. IDENTIFY ALL WATER RISER DIAGRAMS WITH ROOM NUMBERS
 THAT CORRESPOND WITH THE FLOOR PLAN. WPB FBC 107.2.1,
 107.3.5.1.3(3)(13)
  
 14. IDENTIFY KITCHEN EQUIPMENT ITEMS 202, 204, 400,
 400.1, 401, 402, 500, 505, 506 ON WATER RISER DIAGRAM
 (WPB FBC 107.2.1, 107.3.5.1.3).
 IF WATER IS CONNECTED TO ANY EQUIPMENT THAT PRESENTS A
 BACKFLOW/CROSS CONNECTION HAZARD TO THE POTABLE WATER
 SUPPLY, SPECIFY AND PROVIDE A BACKFLOW PREVENTER. FBC
 PL 608.3
  
 15. P1.2.1: PROVIDE DESCRIPTIONS FOR NOTED EQUIPMENT
 ITEMS 202, 204, 400, 400.1, 401, 402, 500, 505, 506.
 IF WATER IS CONNECTED TO ANY EQUIPMENT THAT PRESENTS A
 BACKFLOW/CROSS CONNECTION HAZARD TO THE POTABLE WATER
 SUPPLY, SPECIFY AND PROVIDE A BACKFLOW PREVENTER. FBC
 PL 608.3
  
 16. PROVIDE CALCULATIONS FOR SIZING OF WATER
 DISTRIBUTION. FBC PL 604.1
  
 17. PROVIDE CALCULATIONS FOR SIZING OF STORM WATER
 PIPING SYSTEM. CALCULATIONS SHALL INCLUDE IN ADDITION
 TO NOTED GPM, 100-YEAR HOURLY RAINFALL RATE, SLOPE,
 SQUARE FOOTAGE INCLUDING 1/2 OF VERTICAL SQUARE FOOTAGE
 AND RUNOFF FROM UPPER ROOF/INTERNAL GUTTER AND
 DOWNSPOUT SYSTEM. FBC PL 1106.1, 1106.2, 1106.3,
 1106.4, 1106.5, 1106.6
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 PLEASE CONTACT RYAN BROWN WITH ANY QUESTIONS
 [email protected]
 561-805-6692
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2023-06-26 Cont ID  
Sent By rmcphers Date 2023-06-26 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2023-06-26 Time 15:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2023-03-01 Cont ID  
Sent By rmcphers Date 2023-03-01 Time 13:17 Rev Time 0.00
Received By rmcphers Date 2023-03-01 Time 13:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-07-17 Cont ID  
Sent By rmcphers Date 2023-07-17 Time 12:48 Rev Time 0.00
Received By rmcphers Date 2023-07-17 Time 12:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-29 Cont ID  
Sent By rmcphers Date 2023-06-29 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2023-06-29 Time 10:34 Sent To  
Notes
2023-06-29 10:35:21SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PAGE 6 OF THE THRESHOLD INSPECTOR FORM WHICH IS
 SIGNED AND SEALED BY THE THRESHOLD INSPECTOR - DOES NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 I CHECK THE ELECTRONIC SIGNATURE BY OPENING THEM IN
 ???ADOBE READER???. THE ???ADOBE READER??? STATES
 WHETHER THEY ARE AN ORIGINAL ELECTRONICALLY SIGNED
 DOCUMENT. WHEN ELECTRONICALLY SIGNED DRAWINGS ARE
 PRINTED OUT, THEY LOSE THEIR ELECTRONIC SIGNATURE.
 ELECTRONICALLY SIGNED DRAWINGS NEED TO BE MOVED AROUND
 IN THE COMPUTER FROM PLACE TO PLACE. FROM THE
 ARCHITECT???S OR ENGINEER???S COMPUTER TO YOUR COMPUTER
 TO THE CITY???S ELECTRONIC PLAN REVIEW (PROJECTDOX).
 MAYBE YOURS WERE PRINTED OUT AT SOME TIME?

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-26 Cont ID  
Sent By rmcphers Date 2023-06-26 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2023-06-26 Time 15:45 Sent To  
Notes
2023-06-26 15:46:03SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING LS1.10 AND PAGE 6 OF THE THRESHOLD INSPECTOR
 FORM WHICH IS SIGNED AND SEALED BY THE THRESHOLD
 INSPECTOR - DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-06 Cont ID  
Sent By rmcphers Date 2023-04-06 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2023-04-06 Time 08:55 Sent To  
Notes
2023-04-06 08:56:10SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-01 Cont ID  
Sent By rmcphers Date 2023-03-01 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2023-03-01 Time 13:50 Sent To  
Notes
2023-03-01 13:51:45SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS COV-1, GN-1, DM-1, DM-2, DM-3, PGD-1,
 PGD-2, PGD-3, UT-1, UT-2, UT-3, DET-1, DET-2, DET-3,
 HD-1, HD-2, HD-3, HD-4, LT-1, LT-2, LT-3 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
2023-02-17 16:11:19MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-01-30 16:12:18ELECTRONIC SIGNATURES FOR PLUMBING AND GAS PLANS ARE
 APPROVED. JS

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2023-07-17 Cont ID  
Sent By rmcphers Date 2023-07-17 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2023-07-17 Time 12:49 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2023-06-29 Cont ID  
Sent By rmcphers Date 2023-06-29 Time 10:35 Rev Time 0.00
Received By rmcphers Date 2023-06-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2023-06-26 Cont ID  
Sent By rmcphers Date 2023-06-26 Time 15:57 Rev Time 0.00
Received By rmcphers Date 2023-06-26 Time 15:57 Sent To  
Notes
2023-06-26 15:58:10SEE BUILDING PLAN REVIEW

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2023-04-05 Cont ID  
Sent By rmcphers Date 2023-04-05 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 16:44 Sent To  
Notes
2023-04-05 16:44:37SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By kdefranc Date 2023-06-21 Time 15:53 Rev Time 0.00
Received By kdefranc Date 2023-06-21 Time 15:52 Sent To  
Notes
2023-06-21 15:53:026/21/23 ??? PASSED
  
 PREVIOUS REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A CURRENT SURVEY OF THE SUBJECT
 PROPERTY. [SATISFIED]
 2. PLEASE PROVIDE THE CONDITIONAL APPROVAL LETTER FOR
 FORMAL SITE PLAN REVIEW (FSPR) 22-09 (Z22060027).
 [SATISFIED]
 3. PLEASE PROVIDE THE APPROVED SITE PLANS AND DETAILS
 SHEETS ASSOCIATED WITH FSPR 22-09 (Z22060027).
 [SATISFIED]
  
 ADDITIONAL REVIEW COMMENT TO BE ADDRESSED:
 4. IN ACCORDANCE WITH CONDITIONAL APPROVAL LETTER FOR
 FSPR 22-09 (Z22060027), PLEASE SUBMIT A PERMIT
 APPLICATION FOR THE DUMPSTER ENCLOSURE. [WITHDRAWN]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER ??? PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-04-07 Cont ID  
Sent By kdefranc Date 2023-04-07 Time 09:59 Rev Time 0.00
Received By kdefranc Date 2023-04-07 Time 09:59 Sent To  
Notes
2023-04-07 09:59:334/7/23 ??? FAILED
  
 PREVIOUS REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A CURRENT SURVEY OF THE SUBJECT
 PROPERTY. [SATISFIED]
 2. PLEASE PROVIDE THE CONDITIONAL APPROVAL LETTER FOR
 FORMAL SITE PLAN REVIEW (FSPR) 22-09 (Z22060027).
 [SATISFIED]
 3. PLEASE PROVIDE THE APPROVED SITE PLANS AND DETAILS
 SHEETS ASSOCIATED WITH FSPR 22-09 (Z22060027).
 [SATISFIED]
  
 ADDITIONAL REVIEW COMMENT TO BE ADDRESSED:
 4. IN ACCORDANCE WITH CONDITIONAL APPROVAL LETTER FOR
 FSPR 22-09 (Z22060027), PLEASE SUBMIT A PERMIT
 APPLICATION FOR THE DUMPSTER ENCLOSURE.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER ??? PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By KDefranc Date 2023-02-06 Time 11:44 Rev Time 0.00
Received By kdefranc Date 2023-02-06 Time 11:43 Sent To  
Notes
2023-02-06 11:43:402/6/23 ??? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A CURRENT SURVEY OF THE SUBJECT
 PROPERTY.
 2. PLEASE PROVIDE THE CONDITIONAL APPROVAL LETTER FOR
 FORMAL SITE PLAN REVIEW (FSPR) 22-09 (Z22060027).
 3. PLEASE PROVIDE THE APPROVED SITE PLANS AND DETAILS
 SHEETS ASSOCIATED WITH FSPR 22-09 (Z22060027).
  
  
 KEVIE DEFRANC
 SENIOR PLANNER ??? PLANNING DIVISION
 [email protected]
 561-822-1449
  