Plan Review Details - Permit 23010407
| Plan Review Stops For Permit 23010407 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-02-01 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-02-01 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2023-02-01 13:08:32 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE THE CONNECTED LOAD AND THE PANEL SCHEDULE | | | FOR EXISTING PANEL 'C" 60A MCB. NEC NEC 215.2, 220, | | | 408.4(A). | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-01-20 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-01-20 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-20 10:23:22 | FIRE REVIEW COMMENTS: | | | | | | (1) DEFINE THE TYPE AND CLASSIFICATION OF THE LIQUIDS | | | TO BE STORED IN EACH TANK TO ALLOW FIRE REVIEW TO APPLY | | | APPLICABLE CODE REQUIREMENTS. NFPA 30, 4.3 | | | | | | (2) ONCE THE CLASSIFICATION IS PROVIDED, THE APPLICABLE | | | CODE SECTIONS ON DISTANCE TO BUILDINGS, VENTING, | | | PIPING, DISPENSERS, SIGNAGE, ETC. WILL BE REQUIRED FOR | | | THOROUGH CODE REVIEW. NFPA 1, 1.14 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-02 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-19 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-10 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-10 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2023-01-10 15:38:15 | 1) PROVIDE A COMPLETE DESIGN FOR THIS FUESLING STATION | | | INCLUDING THE PUMPS AND HOW THEY ARE SECURED TO THE | | | TANK. SHOW ANY PIPING THAT WILL BE USED IN TIS DESIGN. | | | INCLUDE THE SHUTOFF VALVES THAT APPLY. FMC 1307 | | | | | | 2) HOW IS THE FUEL INTRODUCED TO THE VEHICLE? IF A | | | FLEXIBLE HOSE, SHOW THAT IT IS LISTED AND LABELED IN | | | ACCORDANCE WITH UL 536 | | | | | | 3) WHAT TYPE OF FUEL IS TO BE STORED? | | | | | | 4) PROVIDE DETAILS FOR THE PUMPS. SHOW THAT THE PUMPS | | | ARE LISTED AND LABELED IN ACCORDANCE WITH UL 343. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-10 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-10 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
|