Plan Review Details - Permit 23010407
Plan Review Stops For Permit 23010407
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By rperdomo Date 2023-02-01 Time 12:55 Rev Time 0.00
Received By rperdomo Date 2023-02-01 Time 11:38 Sent To  
Notes
2023-02-01 13:08:32FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE THE CONNECTED LOAD AND THE PANEL SCHEDULE
 FOR EXISTING PANEL 'C" 60A MCB. NEC NEC 215.2, 220,
 408.4(A).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-01-20 Cont ID  
Sent By cwalker Date 2023-01-20 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-01-20 10:23:22FIRE REVIEW COMMENTS:
  
 (1) DEFINE THE TYPE AND CLASSIFICATION OF THE LIQUIDS
 TO BE STORED IN EACH TANK TO ALLOW FIRE REVIEW TO APPLY
 APPLICABLE CODE REQUIREMENTS. NFPA 30, 4.3
  
 (2) ONCE THE CLASSIFICATION IS PROVIDED, THE APPLICABLE
 CODE SECTIONS ON DISTANCE TO BUILDINGS, VENTING,
 PIPING, DISPENSERS, SIGNAGE, ETC. WILL BE REQUIRED FOR
 THOROUGH CODE REVIEW. NFPA 1, 1.14
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-02 Cont ID  
Sent By aoliver Date 2023-02-02 Time 08:14 Rev Time 0.00
Received By aoliver Date 2023-01-19 Time 12:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 15:24 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 15:24 Sent To  
Notes
2023-01-10 15:38:151) PROVIDE A COMPLETE DESIGN FOR THIS FUESLING STATION
 INCLUDING THE PUMPS AND HOW THEY ARE SECURED TO THE
 TANK. SHOW ANY PIPING THAT WILL BE USED IN TIS DESIGN.
 INCLUDE THE SHUTOFF VALVES THAT APPLY. FMC 1307
  
 2) HOW IS THE FUEL INTRODUCED TO THE VEHICLE? IF A
 FLEXIBLE HOSE, SHOW THAT IT IS LISTED AND LABELED IN
 ACCORDANCE WITH UL 536
  
 3) WHAT TYPE OF FUEL IS TO BE STORED?
  
 4) PROVIDE DETAILS FOR THE PUMPS. SHOW THAT THE PUMPS
 ARE LISTED AND LABELED IN ACCORDANCE WITH UL 343.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 15:40 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 15:40 Sent To  
Notes
***NONE***