| Plan Review Stops For Permit 23010262 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-11 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-11 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2023-01-11 14:52:11 | ADDRESS OF 6315 S FLAGLER DR WAS AGREED UPON FOR THIS | | | PROJECT, UPDATED PERMIT. SHOULD CHNAGES TO THE FRONT | | | DOOR OCCUR A DIFFERENT ADDRESS MAY BE APPROPRIATE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-06-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-13 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-13 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2023-06-13 12:57:42 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND | | | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD | | | FBC WPB 107.3.4 | | | | | | 2) DRAWING A1.0 IN THE "ZONING INFORMATION" CHART THE | | | FLOOR ELEVATION IS NOT THE SAME AS THE FLOOR ELEVATION | | | SHOWN ON THE PLAN. AND THE FLOOD ZONE INFORMATION SHOWS | | | 9.00 NAVD AND THE PLAN VIEW SHOWS 10.00 NAVD | | | | | | 3) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 | | | | | | 4) PLEASE PROVIDE THE FLOOD VENT CERTIFICATIONS (ICC | | | EVALUTATION - PRODUCT APPROVALS) FBC R322.2.2 | | | | | | 5) DRAWING A3.0 SHOWS 4 FLOOD VENTS FOR THE GARAGE AT | | | 200 SQ FOOT RATING EACH - NOT ENOUGH FLOOD VENTS FOR A | | | GARAGE WITH 898 SQ. FT. FBC R322.2.2 | | | | | | 6) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC 107.3.5.3 | | | | | | 7) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE | | | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC | | | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | | | | 8) PLEASE PROVIDE DOCUMENTATION (ICC EVALUATION REPORT) | | | FOR THE FOAM SPRAY INSULATION - FBC R316.3 | | | | | | 9) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF THE | | | BUILDING, FLOOD ZONES AND THE FLOOD ZONE DELINEATION | | | LINE BETWEEN THE FLOOD ZONES. | | | | | | 10) EXTERIOR WINDOW, DOOR AND ROOFING SYSTEM PRODUCT | | | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS | | | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC | | | WPB107.3.4.1 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-18 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2023-04-18 13:59:56 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS DO NOT APPEAR TO BE COMPLETE - DRAWINGS | | | HAVE A NOTE ON THEM THAT SAYS - "PROGRESS SET NOT FOR | | | CONSTRUCTION" - CANNOT HAVE THIS STATEMENT ON THE | | | DRAWINGS. | | | | | | 2) STRUCTURAL DRAWINGS ARE MISSING FROM PROJECTDOX. | | | | | | 3) DRAWING INDEX ON DRAWING A0.0 DOES NOT MATCH THE | | | DRAWINGS UPLOADED TO PROJECTDOX. | | | | | | 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND | | | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD | | | FBC WPB 107.3.4 | | | | | | 5) DOOR AND WINDOW SCHEDULES ARE INCOMPLETE - PLEASE | | | SHOW ALL WINDOW AND DOOR SIZES. | | | | | | 6) PLEASE SHOW THE EMERGENCY EGRESS WINDOW SIZES FROM | | | BEDROOM 6 AND 7 - FBC R310.1 | | | | | | 7) PLEASE SHOW THE WINDOW SILL HEIGHTS - R312.2.1 | | | WINDOW SILLS. | | | IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN | | | OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES | | | (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72 | | | INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER | | | SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE | | | OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING: | | | 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A | | | 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE | | | OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED | | | POSITION. | | | 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL | | | PREVENTION DEVICES THAT COMPLY WITH ASTM F2090. | | | 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW | | | OPENING CONTROL DEVICES THAT COMPLY WITH SECTION - FBC | | | R312.2.2. | | | | | | 8) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 | | | | | | 9) PLEASE SHOW GUARD RAIL DETAILS - HEIGHT, OPENING, | | | ATTACHMENTS ETC. - FBC R312.1 | | | | | | 10) PLEASE SHOW THE ROOF OVERFLOW DRAINAGE TYPE, AND | | | LOCATION - FBC R903.4.1 | | | | | | 11) PLEASE SHOW THE REQUIRED FLOOD VENTS - LOCATION AND | | | SIZES - FOR THE GARAGE BELOW THE DESIGN FLOOD ELEVATION | | | - FBC R322.2.2 | | | | | | 12) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC 107.3.5.3 | | | | | | 13) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE | | | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC | | | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | | | | 14) PLEASE PROVIDE DOCUMENTATION FOR THE FOAM SPRAY | | | INSULATION - FBC R316.3 | | | | | | 15) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF | | | THE BUILDING, FLOOD ZONES AND THE FLOOD ZONE | | | DELINEATION LINE BETWEEN THE FLOOD ZONES. | | | | | | 16) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | DESIGNER FBC WPB 107.1 - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-06 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-06 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2023-02-06 15:30:40 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS DO NOT APPEAR TO BE COMPLETE - DRAWINGS | | | HAVE A NOTE ON THEM THAT SAYS - "PROGRESS SET NOT FOR | | | CONSTRUCTION" - CANNOT HAVE THIS STATEMENT ON THE | | | DRAWINGS. | | | | | | 2) STRUCTURAL DRAWINGS ARE MISSING FROM PROJECTDOX. | | | | | | 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND | | | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD | | | FBC WPB 107.3.4 | | | | | | 4) DOOR AND WINDOW SCHEDULES ARE INCOMPLETE - PLEASE | | | SHOW ALL WINDOW AND DOOR SIZES. | | | | | | 5) PLEASE SHOW THE GARAGE FLOOR TO SLOPE - FBC R309.1 | | | | | | 6) PLEASE SHOW THE EMERGENCY EGRESS WINDOW SIZES FROM | | | BEDROOM 6 AND 7 - FBC R310.1 | | | | | | 7) PLEASE SHOW THE WINDOW SILL HEIGHTS - R312.2.1 | | | WINDOW SILLS. | | | IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN | | | OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES | | | (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72 | | | INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER | | | SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE | | | OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING: | | | 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A | | | 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE | | | OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED | | | POSITION. | | | 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL | | | PREVENTION DEVICES THAT COMPLY WITH ASTM F2090. | | | 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW | | | OPENING CONTROL DEVICES THAT COMPLY WITH SECTION - FBC | | | R312.2.2. | | | | | | 8) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 | | | | | | 9) PLEASE SHOW GUARD RAIL DETAILS - HEIGHT, OPENING, | | | ATTACHMENTS ETC. - FBC R312.1 | | | | | | 10) 2ND FLOOR MASTER BEDROOM SHOWS DOORS WITH NO | | | BALCONY - PLEASE CLARIFY. | | | | | | 11) PLEASE SHOW THE ROOF OVERFLOW DRAINAGE TYPE, AND | | | LOCATION - FBC R903.4.1 | | | | | | 12) PLEASE SHOW THE FINISHED FLOOR ELEVATION FOR THE | | | EXERCISE ROOM - FBC R322.1.5 | | | | | | 13) PLEASE SHOW THE REQUIRED FLOOD VENTS - LOCATION AND | | | SIZES - FOR THE ROOMS (AREAS) BELOW THE DESIGN FLOOD | | | ELEVATION - FBC R322.2.2 | | | | | | 14) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC 107.3.5.3 | | | | | | 15) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE | | | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC | | | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | | | | 16) PLEASE PROVIDE DOCUMENTATION FOR THE FOAM SPRAY | | | INSULATION - FBC R316.3 | | | | | | 17) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF | | | THE BUILDING, FLOOD ZONES AND THE FLOOD ZONE | | | DELINEATION LINE BETWEEN THE FLOOD ZONES. | | | | | | 18) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | DESIGNER FBC WPB 107.1 - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-06-14 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-06-14 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-06-14 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2023-06-14 16:19:55 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW | | | | | | 1. LOW VOLTAGE WIRING, ACCESS CONTROL, AND GENERATOR | | | SYSTEM NEED A SEPARATE PERMIT APPLICATION. | | | | | | END OF COMMENTS | | | | | | RUBEN P. PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-19 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-19 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2023-04-19 15:31:38 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION, SERVICE INFORMATION | | | (INCLUDE ELECTRICAL PANEL RATING, SERVICE CONDUCTORS | | | SIZES AND PROTECTION), AND PANEL SCHEDULE. | | | NEC 220, 230, 240, 408.4(A) | | | | | | 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES. | | | | | | 3. GENERATOR NEEDS A SEPARATE PERMIT. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-02-06 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-02-06 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2023-02-06 09:45:18 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION, SERVICE INFORMATION | | | (INCLUDE ELECTRICAL PANEL RATING, SERVICE CONDUCTORS | | | SIZES AND PROTECTION), AND PANEL SCHEDULE. | | | NEC 220, 230, 240, 408.4(A) | | | | | | 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES. | | | | | | 3. GENERATOR NEEDS A SEPARATE PERMIT. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-02-13 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-08 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-08 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2023-06-08 17:04:22 | 3RD REVIEW FBC-2020 RES. GAS | | | PERMIT- 23010262 | | | 6/8/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. | | | COMBUSTION AIR CALCULATIONS FOR THE NEW RANGES AND OVEN | | | NOT PROVIDED. | | | | | | 3) PLEASE NOTE THAT COMBUSTION AIR AND VENTING PLANS | | | ARE REQUIRED FOR INTERIOR APPLIANCES SUCH AS RANGES, | | | OVENS, COOKTOPS, DRYERS, FIREPLACES ETC.- SEC. | | | 107.3.5.3 WPB. | | | | | | NEW COMMENT BASED ON RESUBMITTED PLAN. | | | | | | 1) SHEET P-1: IT APPEARS THE LOCATIONS OF THE TANKLESS | | | WATER HEATERS ARE NOT IN COMPLIANCE WITH SEC. G2427.8 | | | FBC RES. THE VENTS FROM THE WATER HEATERS SHALL | | | TERMINATE NOT LESS THAN 4 FEET BELOW, 4 FEET | | | HORIZONTALLY FROM, OR 1 FOOT ABOVE ANY DOOR, OPERABLE | | | WINDOW OR GRAVITY AIR INLET INTO ANY BUILDING. THE | | | BOTTOM OF THE VENT TERMINAL SHALL BE LOCATED NOT LESS | | | THAN 12 INCHES ABOVE FINISHED GROUND LEVEL. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-14 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-13 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2023-04-14 08:02:39 | | | | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 23010262 | | | 4/14/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST | | | REVIEW PRINTED BELOW WERE NOT ADDRESSED. PLEASE NOTE | | | THAT GAS CAN BE UNDER SEPARATE PERMIT BY REQUEST. IF | | | THIS OPTION IS SELECTED, PLEASE EMAIL ME AT | | | [email protected] AND I WILL CHANGE THE F (FAILED) RESULT | | | TO N (NO REVIEW- SEPARATE PERMIT REQUIRED). | | | | | | 1) SHEET A3.0: THE PLAN SHOWS THREE EXTERIOR GAS-FIRED | | | TANKLESS WATER HEATERS. PLEASE PROVIDE A GAS RISER | | | DRAWING THAT INCLUDES THE SUPPLY PIPING TO THE WATER | | | HEATERS AND ALL OTHER GAS-FIRED APPLIANCES OR EQUIPMENT | | | TO BE INSTALLED- SEC. 107.3.5.3 WPB. REFER TO FBC RES. | | | CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | J) PIPE SIZING TABLES. | | | | | | 2) PLEASE PROVIDE GAS FLOOR PLAN OR SIRE PLAN SHALL BE | | | PROVIDED TO SHOW THE LOCATIONS OF ALL APPLIANCES AND | | | EQUIPMENT, METER LOCATION, AND GAS PIPING RUNS- SEC. | | | 107.3.5.3 WPB. | | | | | | 3) PLEASE NOTE THAT COMBUSTION AIR AND VENTING PLANS | | | ARE REQUIRED FOR INTERIOR APPLIANCES SUCH AS RANGES, | | | OVENS, COOKTOPS, DRYERS, FIREPLACES ETC.- SEC. | | | 107.3.5.3 WPB. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-30 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-30 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2023-01-30 16:10:35 | | | | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23010262 | | | 1/30/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A3.0: THE PLAN SHOWS THREE EXTERIOR GAS-FIRED | | | TANKLESS WATER HEATERS. PLEASE PROVIDE A GAS RISER | | | DRAWING THAT INCLUDES THE SUPPLY PIPING TO THE WATER | | | HEATERS AND ALL OTHER GAS-FIRED APPLIANCES OR EQUIPMENT | | | TO BE INSTALLED- SEC. 107.3.5.3 WPB. REFER TO FBC RES. | | | CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | J) PIPE SIZING TABLES. | | | | | | 2) PLEASE PROVIDE GAS FLOOR PLAN OR SIRE PLAN SHALL BE | | | PROVIDED TO SHOW THE LOCATIONS OF ALL APPLIANCES AND | | | EQUIPMENT, METER LOCATION, AND GAS PIPING RUNS- SEC. | | | 107.3.5.3 WPB. | | | | | | 3) PLEASE NOTE THAT COMBUSTION AIR AND VENTING PLANS | | | ARE REQUIRED FOR INTERIOR APPLIANCES SUCH AS RANGES, | | | OVENS, COOKTOPS, DRYERS, FIREPLACES ETC.- SEC. | | | 107.3.5.3 WPB. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-23 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-23 |
Time |
12:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-20 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-04-12 |
Time |
18:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-14 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-27 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-06 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-06 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2023-02-06 15:41:15 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-23 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-23 |
Time |
12:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-19 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-19 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2023-04-19 13:38:21 | 2ND ATTEMPT: | | | | | | 1ST REVIEW FMC | | | PERMIT: 23010262 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE COMPLETE MECHANICAL DESIGN FOR THIS | | | PROJECT INCLUDING: | | | | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | FEC R403.7.1- MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | MECHANICAL: | | | 1. ENERGY CALCULATIONS | | | 2. EXHAUST SYSTEMS: | | | CLOTHES DRYER EXHAUST | | | KITCHEN EQUIPMENT EXHAUST | | | SPECIALTY EXHAUST SYSTEMS | | | 3. EQUIPMENT | | | 4. EQUIPMENT LOCATION | | | 5. MAKE-UP AIR | | | 6. ROOF-MOUNTED EQUIPMENT | | | 7. DUCT SYSTEMS | | | 8. VENTILATION | | | 9. COMBUSTION AIR | | | 10. CHIMNEYS, FIREPLACES AND VENTS | | | 11. APPLIANCES | | | 12. BOILERS | | | 13. REFRIGERATION | | | 14. BATHROOM VENTILATION | | | 15. LABORATORY | | | 16. DESIGN FLOOD ELEVATION | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-30 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-30 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2023-01-30 15:18:33 | 1ST REVIEW FMC | | | PERMIT: 23010262 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE COMPLETE MECHANICAL DESIGN FOR THIS | | | PROJECT INCLUDING: | | | | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | FEC R403.7.1- MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | MECHANICAL: | | | 1. ENERGY CALCULATIONS | | | 2. EXHAUST SYSTEMS: | | | CLOTHES DRYER EXHAUST | | | KITCHEN EQUIPMENT EXHAUST | | | SPECIALTY EXHAUST SYSTEMS | | | 3. EQUIPMENT | | | 4. EQUIPMENT LOCATION | | | 5. MAKE-UP AIR | | | 6. ROOF-MOUNTED EQUIPMENT | | | 7. DUCT SYSTEMS | | | 8. VENTILATION | | | 9. COMBUSTION AIR | | | 10. CHIMNEYS, FIREPLACES AND VENTS | | | 11. APPLIANCES | | | 12. BOILERS | | | 13. REFRIGERATION | | | 14. BATHROOM VENTILATION | | | 15. LABORATORY | | | 16. DESIGN FLOOD ELEVATION | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-08 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-08 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-13 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-13 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2023-04-13 17:16:48 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23010262 | | | 4/13/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.0 PLUMBING RISER: THE HORIZONTAL WET VENTS | | | IN HIS BATH ANS BATH #5 ARE NOT DESIGNED IN ACCORDANCE | | | WITH SEC. P3108.2.1 FBC RES- NO MORE THAN ONE WET | | | VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION AT THE LAVATORIES. | | | | | | 2) 2ND REQUEST SHEET A6.0: PLEASE PROVIDE ADDITIONAL | | | ROOF DRAINAGE INFORMATION ON THE PLAN INCLUDING | | | LOCATIONS AND SIZES OF OVERFLOW DRAINS OR SCUPPERS- | | | SEC. R903.4.1 FBC RES. | | | | | | A) THE PLAN HAS A NOTE REFERRING TO SHOP DRAWINGS FOR | | | THE ROOF DRAINAGE SYSTEM. THE DRAWINGS REQUIRE THE | | | APPROVAL STAMP OF THE ARCHITECT OF RECORD AND CAN BE | | | SUBMITTED NOW FOR REVIEW OR BE A DEFERRED SUBMITTAL- | | | SEC. 107.3.4.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-30 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-30 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2023-01-30 15:43:29 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23010262 | | | 1/30/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SUBMIT PLUMBING RISER DRAWINGS- SEC. | | | 107.3.5.3 WPB MINIMUM PLAN REVIEW CRITERIA FOR | | | RESIDENTIAL BUILDINGS. | | | | | | 2) SHEET A6.0: PLEASE PROVIDE ADDITIONAL ROOF DRAINAGE | | | INFORMATION ON THE PLAN INCLUDING LOCATIONS AND SIZES | | | OF OVERFLOW DRAINS OR SCUPPERS- SEC. R903.4.1 FBC RES. | | | | | | A) THE PLAN HAS A NOTE REFERRING TO SHOP DRAWINGS FOR | | | THE ROOF DRAINAGE SYSTEM. THE DRAWINGS REQUIRE THE | | | APPROVAL STAMP OF THE ARCHITECT OF RECORD AND CAN BE | | | SUBMITTED NOW FOR REVIEW OR BE A DEFERRED SUBMITTAL- | | | SEC. 107.3.4.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-06-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-13 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-13 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2023-06-13 14:02:30 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-18 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2023-04-18 14:00:31 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-06 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-06 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2023-02-06 15:42:03 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-06-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-13 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-13 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2023-06-13 14:01:50 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS A4.0, A4.1, A4.2 DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | | | 2023-06-08 15:15:29 | PLUMBING AND GAS SIGNATURES PASSED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-18 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2023-04-18 14:01:04 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SIGNED AND SEALED DRAWINGS NEED TO SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-06 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-06 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2023-02-06 15:43:35 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SIGNED AND SEALED DRAWINGS NEED TO SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2023-06-15 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-15 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-15 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2023-06-15 11:42:53 | FAILED | | | 6/15/2023 | | | | | | REPEAT COMMENT | | | | | | | | | NEW CONSTRUCTIONS ARE REQUIRED TO HAVE A SEPARATE | | | LANDSCAPE PERMIT IN THE SYSTEM. | | | PLEASE REACH OUT TO SMITH AMISIAL (LANDSCAPE PLANNER) | | | 561-822-1562 | | | | | | | | | SEPARATE PERMIT REQUIRED AND NOT IN INCLUDE IN THIS | | | PERMIT: | | | DRIVEWAYS | | | LANDSCAPE | | | MECHANICAL/POOL EQUIPMENT/GENERATOR | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-14 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-14 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-14 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2023-04-14 16:11:02 | FAILED | | | 4/14/2023 | | | | | | REPEAT COMMENT | | | | | | | | | NEW CONSTRUCTIONS ARE REQUIRED TO HAVE A SEPARATE | | | LANDSCAPE PERMIT IN THE SYSTEM. | | | PLEASE REACH OUT TO SMITH AMISIAL (LANDSCAPE PLANNER) | | | 561-822-1562 | | | | | | | | | SEPARATE PERMIT REQUIRED AND NOT IN INCLUDE IN THIS | | | PERMIT: | | | DRIVEWAYS | | | LANDSCAPE | | | MECHANICAL/POOL EQUIPMENT/GENERATOR | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-02-07 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-07 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2023-02-07 14:07:25 | FAILED | | | 2/7/2023 | | | | | | PROPOSED SINGLE FAMILY HOME IS OVER THE MAXIMUM HEIGHT | | | ALLOWANCE FOR SINGLE FAMILY LOW DENSITY (SF7) ZONING | | | (HEIGHT IS MEASURED FROM GRADE) | | | ARTICLE III. SECTION 94-72 | | | | | | NEW CONSTRUCTIONS ARE REQUIRED TO HAVE A SEPARATE | | | LANDSCAPE PERMIT IN THE SYSTEM. | | | PLEASE REACH OUT TO SMITH AMISIAL (LANDSCAPE PLANNER) | | | 561-822-1562 | | | | | | WHERE THE OUTDOOR SHOWER IS LOCATED THERE IS TWO DOORS | | | FOR THE BATHROOM AND A MECHANICAL ROOM THOSE DOORS ARE | | | CURRENTLY SHOWING THAT THEY ARE 5FT ABOVE GRADE WITH NO | | | STEPS? | | | ARTICLE X SECTION 94-305 | | | STEPS AND PORCHES. STEPS, OPEN UNCOVERED PORCHES OR | | | STOOPS, AND OPEN TERRACES WHICH ARE THREE FEET OR LESS | | | ABOVE GRADE MAY ENCROACH INTO ANY REQUIRED SETBACK AREA | | | TO A POINT NOT CLOSER THAN TWO FEET TO THE PROPERTY | | | LINE. ANY GRADE DIFFERENTIAL BETWEEN THE ENCROACHING | | | STEP, PORCH, STOOP, OR TERRACE AND ADJACENT PROPERTY | | | SHALL BE STRUCTURALLY RETAINED AND POSITIVELY DRAINED | | | IN A MANNER THAT WILL PREVENT ANY DRAINAGE DISCHARGE TO | | | ANY PROPERTY CONTIGUOUS TO THE SIDE OR REAR PROPERTY | | | LINES. | | | | | | | | | SEPARATE PERMIT REQUIRED AND NOT IN INCLUDE IN THIS | | | PERMIT: | | | | | | DRIVEWAYS | | | THERE IS A 3FT MINIUM BUFFER FROM THE PROPERTY LINE TO | | | WHERE THE DRIVEWAY CAN BE LOCATED PLEASE LABEL THIS | | | SETBACK FOR THE DRIVEWAY LOCATED ON BLOOMFIELD DRIVE | | | THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE | | | FRONT YARD AREA SHALL BE LANDSCAPED WITH LIVING PLANT | | | MATERIAL (SUCH AS GRASS, GROUND COVER, SHRUBS, HEDGES, | | | VINES OR TREES). | | | ATRICLE XV. SECTION 94-482 | | | * FLAGLER DRIVE IS CONSIDERED YOUR FRONT | | | | | | VISIBILTY TRIANGLE IS REQUIRED PLEASE LABEL THE | | | DIMENTIONS OF THE TRIANGLE ON PLANS. | | | VISIBILITY AT INTERSECTIONS. AT ANY ROAD INTERSECTIONS, | | | VISIBILITY SHALL NOT BE OBSCURED BY THE CONSTRUCTION, | | | PLACEMENT, OR MAINTENANCE OF A STRUCTURE WALL, SIGN, | | | FENCE, BERM, PLANT MATERIAL, SHRUBS, OR ANY SIMILAR | | | ITEM BETWEEN 18 INCHES OR EIGHT FEET IN HEIGHT WITHIN A | | | TRIANGLE BEGINNING AT THE POINT WHERE PROPERTY LINES | | | MEET AT THE CORNER, THEN 20 FEET ALONG THE FRONT | | | PROPERTY LINE, THENCE DIAGONALLY TO A POINT ALONG THE | | | SIDE PROPERTY LINE 20 FEET FROM THE POINT OF BEGINNING, | | | AND THENCE TO THE POINT OF BEGINNING. IN THE EVENT THE | | | CORNER OF AN INTERSECTION IS ROUNDED, THE MEASUREMENT | | | SHALL BEGIN AT THE POINT THE PROPERTY LINES WOULD MEET | | | WITHOUT ROUNDING. | | | ATRICLE X. SECTION94-305 | | | | | | MECHANICAL/POOL EQUIPMENT/GENERATOR | | | EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A | | | SETBACK. | | | ARTICLE X SECTION 94-305 | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] | | | | | | | | | |
|
|