Plan Review Details - Permit 23010248
Plan Review Stops For Permit 23010248
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-06-23 Cont ID  
Sent By cpuell Date 2023-06-23 Time 10:21 Rev Time 0.00
Received By cpuell Date 2023-06-23 Time 10:21 Sent To  
Notes
2023-06-23 10:21:49THIS PERMIT IS FOR THE NORTH BUILDING ONLY WITH THE
 ADDRESS OF 2202 N TAMARIND AVE. RECEIVED PRELIMINARY
 LETTER FROM THE COUNTY 74434316100030090
 74434316100030101 AND 74434316100030110 WILL MERGE INTO
 74434316100030090. PRIMARY ADDRESS FOR THE PARCEL WILL
 BE 2160 N TAMARIND AVE, THE FOLLOWING ADDRESSES HAVE
 ALSO BEEN APPROVED 2190 N TAMARIND AVE 2160 N TAMARIND
 AVE 200 201 202 300 301 302 2202 N TAMARIND AVE 2212 N
 TAMARIND AVE 2224 N TAMARIND AVE 2236 N TAMARIND AVE
 2190 N TAMARIND AVE AND 2202 N TAMARIND AVE 200 201 202
 300 301 302. APPLICANT INFORMED PLANS AND APPLICATIONS
 FORMS NEED TO BE UPDATED WITH THE PRIMARY ADDRESS 2202
 N TAMARIND AVE.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By cpuell Date 2023-05-02 Time 12:54 Rev Time 0.00
Received By cpuell Date 2023-05-02 Time 12:54 Sent To  
Notes
2023-05-02 12:54:52NOBODY HAS CONTACTED ADDRESSING TO ADDRESS THE ADDRESS
 ISSUES. PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-14 Cont ID  
Sent By cpuell Date 2023-02-14 Time 13:46 Rev Time 0.00
Received By cpuell Date 2023-02-14 Time 13:46 Sent To  
Notes
2023-02-14 13:57:52PLEASE COORDINATE WITH [email protected] FOR THE
 HABITABLE SPACE TO BE GIVEN AN ADDRESS. ALL ACCESSORY
 RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER HABITABLE
 STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY ADDRESS
 NUMBER PER CITY'S ADDRESSING POLICY. PLEASE HAVE THE
 OWNER CONTACT [email protected] OR CALL
 561-805-6659 TO BEGIN WORKING ON THE ADDRESSING ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-05-16 Time   Rev Time 0.00
Received By swelter Date 2023-05-16 Time 13:41 Sent To  
Notes
2023-05-16 13:40:36AFFORDABLE HOUSING - EXEMPT PUBLIC ART

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By rmcphers Date 2023-07-24 Time 09:02 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 13:21 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 13:10 Sent To  
Notes
2023-06-21 13:21:16NEW RESIDENTIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING LS-1 - UNDER "SCOPE OF WORK" - WIND DESIGN -
 ASCE 7-10 IS SHOWN - SHOULD BE ASCE 7-16 - FBC CHAPTER
 35
  
 2) DRAWING A-10.2 - DETAIL 2 AND 3 - PLEASE SHOW THE
 CLEAR FLOOR SPACE FOR THE BATH TUB - FBC FHA
 REQUIREMENT 7
  
 3) DRAWING A-1.0A HAS BEEN UPLOADED ON TOP OF DRAWING
 A1.0B IN PROJECTDOX - PLEASE CORRECT.
  
 4) THE INDEX DRAWING DOES NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By rmcphers Date 2023-05-02 Time 08:30 Rev Time 0.00
Received By rmcphers Date 2023-05-02 Time 08:21 Sent To  
Notes
2023-05-02 08:30:15NEW RESIDENTIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEM - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 2) DRAWING LS-1 - UNDER "SCOPE OF WORK" - WIND DESIGN -
 ASCE 7-10 IS SHOWN - SHOULD BE ASCE 7-16 - FBC CHAPTER
 35
  
 3) DRAWING A-4.2 - DETAIL 1 - SHOWS HAND RAIL HEIGHT AT
 2'9" - FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 4) THE DRAWINGS (A-10.1) (A-10.00) (A-9.00) SHOWS THAT
 THE FBC ENERGY CONSERVATION NOTES USING THE 2014 CODE -
 SHOULD BE PER THE 2020 FBC ENERGY CONSERVATION.
  
 5) FOR THE UNITS ABOVE THE FIRST FLOOR - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 6) ITEMS SUCH AS EXTERIOR WINDOW, DOOR, ROOFING SYSTEM
 PRODUCT APPROVALS AND FLOORING ACOUSTICAL REPORTS MAY
 BE DEFERRED SUBMITTALS BY LISTING THE DEFERRED ITEMS ON
 THE CONSTRUCTION DRAWINGS - FBC WPB 107.3.4.1
  
 7) FYI - SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, TRELLIS, PLAYGROUND, PARKING LOT, SITE
 LIGHTING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By rmcphers Date 2023-03-09 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2023-03-09 Time 08:09 Sent To  
Notes
2023-03-09 11:00:02NEW RESIDENTIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXTERIOR FIRE RATED DOOR TO THE
 UNITS TO BE SELF CLOSING (THE DOOR SCHEDULE MAY SHOW
 THE WRONG HARDWARE TYPE) - FBC 716.5.9 DOOR CLOSING.
 FIRE DOORS SHALL BE LATCHING AND SELF- OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS SECTION.
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEM - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 3) PLEASE SHOW THE GRAB BAR WALL REINFORCEMENT TYPE,
 SIZE AND LOCATION DIMENSIONS ( FOR THE GROUND FLOOR 2
 BEDROOM UNITS) - FBC FHA REQUIREMENT 6
  
 4) DRAWING A-1.0B - UNDER "SCOPE OF WORK" - WIND DESIGN
 - ASCE 7-10 IS SHOWN - SHOULD BE ASCE 7-16 - FBC
 CHAPTER 35
  
 5) DRAWING A-6.1 - DETAIL 1 - SHOWS HAND RAIL HEIGHT AT
 2'9" - FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 6) FOR THE UNITS ABOVE THE FIRST FLOOR - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 7) PLEASE PROVIDE THE FIRE SPRINKLER AND ALARM PLANS -
 FBC WPB 107.3.5.1.1 (5)
  
 7) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, TRELLIS, PLAYGROUND, PARKING LOT, SITE
 LIGHTING

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-06-22 Cont ID  
Sent By jleahy Date 2023-06-22 Time 15:01 Rev Time 0.00
Received By jleahy Date 2023-06-22 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-15 Cont ID  
Sent By rperdomo Date 2023-05-15 Time 13:02 Rev Time 0.00
Received By rperdomo Date 2023-05-15 Time 12:53 Sent To  
Notes
2023-05-15 13:04:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW
  
 1. LOW VOLTAGE WIRING REQUIRES A SEPARATE PERMIT
 APPLICATION.
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-17 Cont ID  
Sent By rperdomo Date 2023-02-17 Time 09:29 Rev Time 0.00
Received By rperdomo Date 2023-02-17 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-06-22 Cont ID  
Sent By jleahy Date 2023-06-22 Time 15:09 Rev Time 0.00
Received By jleahy Date 2023-06-22 Time 15:08 Sent To  
Notes
2023-06-22 15:09:54VOICE/DATA AND TV AS PER PLANS JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-07-14 Cont ID  
Sent By cseifer Date 2023-07-14 Time 07:11 Rev Time 0.00
Received By cseifer Date 2023-07-14 Time 07:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-06-23 Cont ID  
Sent By cseifer Date 2023-06-23 Time 14:04 Rev Time 0.00
Received By cseifer Date 2023-06-23 Time 14:06 Sent To  
Notes
2023-06-23 14:04:54UNDER FORMAL ENGINEERING REVIEW SUBMITTAL.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-05-04 Cont ID  
Sent By lquinone Date 2023-05-04 Time 11:11 Rev Time 0.00
Received By lquinone Date 2023-05-04 Time 11:11 Sent To  
Notes
2023-05-04 11:11:34UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By rrossano Date 2023-02-13 Time   Rev Time  
Received By rrossano Date 2023-02-13 Time   Sent To  
Notes
2023-02-13 12:05:58AFTER SITE PLAN APPROVAL A FORMAL ENGINEERING SUBMITTAL
 IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By pleduc Date 2023-07-24 Time   Rev Time 0.00
Received By pleduc Date 2023-07-24 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By pleduc Date 2023-06-21 Time   Rev Time 0.00
Received By pleduc Date 2023-06-21 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By pleduc Date 2023-05-01 Time   Rev Time 0.00
Received By pleduc Date 2023-05-01 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-13 Cont ID  
Sent By cwalker Date 2023-02-13 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-02-13 10:49:08FIRE PROVISO COMMENT:
  
 DOOR LOCKING ARRANGEMENTS SHALL COMPLY WITH NFPA 101,
 LIFE SAFETY CODE, 30.2.2.2.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-24 Cont ID  
Sent By lmarchan Date 2023-07-24 Time 10:56 Rev Time 0.00
Received By lmarchan Date 2023-07-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-17 Cont ID  
Sent By aoliver Date 2023-07-17 Time 08:19 Rev Time 0.00
Received By aoliver Date 2023-06-16 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-17 Cont ID  
Sent By aoliver Date 2023-05-17 Time 07:07 Rev Time 0.00
Received By aoliver Date 2023-04-28 Time 17:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-03 Cont ID  
Sent By aoliver Date 2023-04-03 Time 08:20 Rev Time 0.00
Received By aoliver Date 2023-02-10 Time 11:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-13 Time 15:45 Sent To  
Notes
2023-07-13 15:45:287/13/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By rmcphers Date 2023-03-09 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2023-03-09 Time 11:00 Sent To  
Notes
2023-03-09 11:03:31PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-06-30 Cont ID  
Sent By cmontell Date 2023-06-30 Time 12:22 Rev Time 0.00
Received By cmontell Date 2023-06-30 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By medwards Date 2023-05-08 Time 08:40 Rev Time 0.00
Received By medwards Date 2023-05-08 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By medwards Date 2023-02-23 Time 14:20 Rev Time 0.00
Received By medwards Date 2023-02-23 Time 11:54 Sent To  
Notes
2023-02-23 14:20:401ST REVIEW FMC
 PERMIT: 23010248
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW HOW THE DRYER DUCT WILL NOT BE INSIDE OF THE
 RETURN AIR PLENUM. FMC 504.4
  
 2) THE KITCHEN HOOD EXHAUST DUCT THAT IS RUNNING INSIDE
 OF THE RETURN AIR PLENUM WILL NEED TO MEET THE DUCT
 CONSTRUCTION REQUIREMENTS OF FMC 603. SPECIFY THE DUCT
 THICKNESS WILL THE REQUIREMENTS OF FMC 603.4
  
 3) CHANGE THE PVC PIPING FOR THE CONDENSATE DRAIN AS
 THIS MATERIAL WILL NOT MEET THE SMOKE AND FLAME SPREAD
 REQUIREMENTS OF FMC 602.2.1.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-07-22 Cont ID  
Sent By ccole Date 2023-07-22 Time 10:13 Rev Time 0.00
Received By ccole Date 2023-07-22 Time 08:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-06-20 Cont ID  
Sent By ccole Date 2023-06-20 Time 13:50 Rev Time 0.00
Received By ccole Date 2023-06-20 Time 11:19 Sent To  
Notes
2023-06-20 14:08:533RD REVIEW FBC-2020 PLUMBING
 PERMIT- 23010248
 6/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED. 3RD REQUEST FOR THE
 BACKFLOW PERMIT APPLICATION TO BE SUBMITTED. PLEASE
 COMMENT #1 BELOW AND IF YOU DON???T UNDERSTAND WHAT IS
 REQUIRED PLEASE CONTACT ME ASAP.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NEW COMMENT BASED ON RESUBMITTED PLANS.
  
 1) SHEET A1.0A WHICH IS THE FLOOR PLANS FOR A BUILDING
 WITH ADA COMPLIANCE WAS RESUBMITTED IN PLACE OF A1.0B
 WHICH IS THE FLOOR PLANS WITH NON-ADA COMPLIANCE.
 PLEASE SUBMIT THE CORRECT PLANS.
  
 2) SHEETS A10.0, A10.1: THE REQUIRED 30X48-INCH CLEAR
 FLOOR SPACE DIAGRAM FOR THE BATHTUB SHOWING A
 PERPENDICULAR APPROACH IN THE TYPE A BATHROOM WAS
 REMOVED. THIS REQUIRED CLEAR FLOOR SPACE ALSO SERVES AS
 THE MANEUVERABLE CLEARANCE BEYOND THE ARC OF THE
 INSWINGING DOOR- REFER TO EXAMPLE A BATHROOM ON PAGE
 7.36 OF THE FHDA MANUAL.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By ccole Date 2023-05-02 Time 09:56 Rev Time 0.00
Received By ccole Date 2023-05-01 Time 12:25 Sent To  
Notes
2023-05-02 10:10:142ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23010248
 5/2/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS A10.1: PLEASE REMOVE THE ADA LABELS FROM
 DETAILS 2 & 3. THE BATHROOMS SHOWN ARE NOT COMPLETELY
 IN COMPLIANCE WITH THE FBC ACC AND NOT REQUIRED TO BE
 BASED ON THE SEC. 233.3.1 EXCEPTION FBC ACC. THE
 ARCHITECT HAS PROVIDED AN EMAIL WHICH IDENTIFIES THE
 LOCATIONS OF THE REQUIRED ADA UNITS AND BATHROOMS, AND
 BUILDING B, UNDER THIS PERMIT IS NOT INCLUDED. THE
 UNITS AND BATHROOMS IN BUILDING B SHALL COMPLY WITH THE
 FAIR HOUSING DESIGN ACT- SEC. 107.2.1 WPB.
  
 3) P-3 & P-4: THE PVC WATER HEATER DRAIN LINES IN THE
 AC CLOSET PLENUM ENCLOSURES ARE NOT PERMITTED PER SEC
 602.2.1 FBC M. PVC IS COMBUSTIBLE MATERIAL AND CAN BE
 USED OUTSIDE OF THE ENCLOSURES. PLEASE SELECT A DRAIN
 MATERIAL THAT MEETS COMPLIANCE SUCH AS COPPER.
  
 4) P-5: PLEASE CORRECT THE NOTE FROM THE FBC RES. CODE
 INDICATING NON-RECIRCULATED HOT WATER SHALL NOT EXCEED
 100 FT. REFER TO SEC. 607.2 FBC P- THE LONGEST
 ALLOWANBLE DISTANCE IS 50 FT.
  
 5) P-6: A NEW WATER HEATER NOTE INDICATES A TEMPERATURE
 LIMITING DEVICE SHALL BE PROVIDED HOWEVER NO DEVICE IS
 SHOWN. PLEASE SHOW THE LOCATION OF THE DEVICE AND
 PIPING CONNECTIONS- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By ccole Date 2023-02-17 Time 10:07 Rev Time 0.00
Received By ccole Date 2023-02-17 Time 07:34 Sent To  
Notes
2023-02-17 10:08:581ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010247
 2/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * FIRE LINE BACKFLOW PREVENTER.
 * IRRIGATION SYSTEM
 * IRRIGATION BACKFLOW PREVENTER
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEET A-1.0B: PLEASE REFER TO SEC. 233 FBC
 ACCESSIBILITY. BASED ON SECS. 233.3.1 & 233.3.1.1 A
 MINIMUM OF ONE OF THE EIGHT DWELLING UNITS SHALL BE
 DESIGNED WITH COMMUNICATION AND MOBILITY FEATURES IN
 COMPLIANCE WITH SECS. 809.2 & 809.4.
 PLEASE NOTE THE EXCEPTION UNDER 233.3.1 WHICH COULD BE
 APPLICABLE TO THE ENTIRE NEIGHBORHOOD RENAISSANCE
 PROJECT AS A WHOLE:
  
 EXCEPTION: WHERE FACILITIES CONTAIN 15 OR FEWER
 RESIDENTIAL DWELLING UNITS, THE REQUIREMENTS OF
 233.3.1.1 AND 233.3.1.2 SHALL APPLY TO THE TOTAL NUMBER
 OF RESIDENTIAL DWELLING UNITS THAT ARE CONSTRUCTED
 UNDER A SINGLE CONTRACT, OR ARE DEVELOPED AS A WHOLE,
 WHETHER OR NOT LOCATED ON A COMMON SITE.
  
 CONCERNING THE PLUMBING REVIEW, THE BATHROOM IN THE
 UNIT THAT MUST MEET COMPLIANCE SHALL BE DESIGNED IN
 ACCORDANCE WITH 809.4. SEC. 809.4 REFERS THE DESIGNER
 TO SECS. 603-610 FOR TOILET AND BATHING FIXTURE
 INSTALLATIONS. BECAUSE 809.2 REQUIRES THE SELECTED UNIT
 TO BE ON AN ACCESSIBLE ROUTE IT APPEARS THE UNIT
 MEETING COMPLIANCE SHALL BE ON THE GROUND FLOOR. PLEASE
 PROVIDE AN ENLARGED DRAWING OF THE SELECTED UNIT
 INDICATING COMPLIANCE WITH THE FOLLOWING LIST OF FBC
 ACC COMPLIANCES:
  
 A) SEC. 603.2.1: PROVIDE A TURNING SPACE IN THE
 BATHROOM COMPLYING WITH SEC. 304.
  
 B) SEC. 603.3 SHOW THE HEIGHT OF THE MIRROR AT THE
 LAVATORY TO BE INSTALLED WITH THE REFLECTIVE SURFACE 40
 INCHES MAXIMUM FOR THE FINISHED FLOOR.
  
 C) SEC. 604.3: CLEARANCE AROUND THE WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURE PERPENDICULAR
 FOR THE REAR WALL. PROVIDE A 60 IN. WIDE X 56 IN. CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE WATER
 CLOSETS. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED CLEARANCE, HOWEVER THERE IS
 AN EXCEPTION WHICH ALLOWS A LAVATORY ON THE REAR WALL
 18 INCHES MINIMUM FROM THE WATER CLOSET CENTERLINE
 WHERE THE CLEARANCE AT THE WATER CLOSET IS 66 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 D) SEC. 606.2: A 30 INCHES X 48 INCHES CLEAR FLOOR
 SPACE POSITIONED FOR A FORWARD APPROACH IS REQUIRED FOR
 THE LAVATORY. KNEE AND TOE CLEARANCES ARE REQUIRED
 HOWEVER PLEASE NOTE EXCEPTION 3 A, B, & C WHICH ALLOWS
 FOR REMOVABLE CABINETRY AT THE LAVATORY.
  
 E) SEC. 604.2: SHOW THE CENTERLINE OF THE WATER CLOSET
 TO BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDE WALL.
  
 F) SEC. 604.4 EXCEPTION 2: SHOW THE HEIGHT OF THE WATER
 CLOSET 15 INCHES MINIMUM AND INCHES MAXIMUM FROM THE
 FINISHED FLOOR.
  
 G) SEC. 604.5 EXCEPTION 2: SHOW LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SECS. 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2, OR
 PROVIDE REINFORCEMENT LOCATIONS FOR FUTURE
 INSTALLATIONS PER EXCEPTION 2.
  
 H) SEC. 604.7: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER TO BE LOCATED 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM FROM THE FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER.
  
 I) SEC. 606.3: SHOW THE HEIGHT OF THE LAVATORY SINK RIM
 OR COUNTER SURFACE TO BE MAXIMUM 34 INCHES FROM THE
 FINISHED FLOOR UNLESS MEETING EXCEPTION 2 WHICH ALLOWS
 THE HEIGHT TO BE 29-36 INCHES WHERE THE PLUMBING ROUGH
 IN LOCATIONS ALLOW FOR A SINK AT A HEIGHT OF 29 INCHES.
  
 J) SEC. 607.2: SHOW THE CLEAR FLOOR SPACE FOR THE
 BATHTUB TO EXTEND THE LENGTH OF THE BATHTUB AND 30
 INCHES WIDE MINIMUM. A LAVATORY COMPLYING WITH SEC. 606
 IS PERMITTED AT THE CONTROL END OF THE CLEARANCE.
  
 K) SEC. 607.3: SHOW EITHER A PERMANENT SEAT AT THE HEAD
 OF THE TUB OR A REMOVABLE SEAT SHALL BE PROVIDED.
 PLEASE SEE SECS. 607.4.1- 607.4.2.3.
  
 L) SEC. 607.4: SHOW GRAB LOCATIONS IN COMPLIANCE WITH
 SEC. 607.4.1- 607.4.1.2 UNLESS INSTALLING
 REINFORCEMENTS IN ACCORDANCE WITH EXCEPTION 2.
  
 M) SEC. 607.5: SHOW THE BATHTUB CONTROLS LOCATION.
  
 3) SHEET A-10.1: PLEASE SHOW THE CLEAR FLOOR DIAGRAMS
 FOR THE BATHTUBS AS SHOWN ON PAGE 7.53 FHHA MANUAL. IT
 APPEARS THE BATHROOMS ARE DESIGNED AS SPEC A TYPES
 BECAUSE SPEC B REQUIRES A 30X48-INCH CLEAR FLOOR SPACE
 PARALLEL TO THE TUB AND FLUSH WITH THE CONTROL WALL.
  
 4) A-10.1: REFER TO PAGES 6.3- 6.9 OF THE FHDA MANUAL
 AND SHOW THE MINIMUM HEIGHT OF THE WATER CLOSET AND
 BATHTUB REINFORCEMENTS WILL BE 38-INCHES MINIMUM FROM
 THE FINISHED FLOORS.
  
 5) P-1: BASED ON TABLE 403.1 PLUMBING FIXTURES WILL BE
 REQUIRED IN THE RETAIL-ADMINISTRATION SEPARATE TENANT
 SPACE SHOWN ON THE FLOOR PLANS. PLEASE REVISE THE
 DRAWINGS TO SHOW THE LOCATION OF THE UNDERGROUND
 BUILDING DRAIN IN THE SPACE, THE DRAIN RUN TO POINT OF
 CONNECTION TO THE SEWER, EXTERIOR AND INTERIOR CLEANOUT
 LOCATIONS, AND INTERIOR CAP FOR FUTURE ACCESS- SEC.
 107.2.1 WPB.
  
 6) P-6: THE PLANS DO NOT SHOW THE WATER HEATER DRAIN
 PAN LINE RUNS AND DISCHARGE LOCATIONS. PLEASE PROVIDE
 DETAILS IN COMPLIANCE WITH SECS. 504.7.1 & 504.7.2 FBC
 P.
  
 7) P-6: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATERS SHOWING THE MAKES AND MODELS, GALLON
 SIZES, AND EFFICIENCY RATINGS TO MATCH WITH THE DATA
 LISTED ON THE SUBMITTED ENERGY COMPLIANCE FORMS- TABLE
 C404.2 FBC EC. THE WATER HEATERS SPECIFICATIONS CAN BE
 DEFERRED SUBMITTALS IF PREFERRED- SEE SEC. 107.3.4.1
 WPB.
  
 8) P-2: PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE VERTICAL AND HORIZONTAL PIPING RUNS AND
 SIZES FROM THE ROOF DRAINS TO DISCHARGE LOCATIONS- SEC.
 107.3.5.1.3 (7) WPB, AND SECS. 1101.2, 1106.2 & 1106.3
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 13:22 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 13:22 Sent To  
Notes
2023-06-21 13:22:39ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By rmcphers Date 2023-05-02 Time 08:30 Rev Time 0.00
Received By rmcphers Date 2023-05-02 Time 08:30 Sent To  
Notes
2023-05-02 08:30:59SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By rmcphers Date 2023-03-09 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2023-03-09 Time 11:03 Sent To  
Notes
2023-03-09 11:04:05SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By rmcphers Date 2023-07-24 Time 09:02 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 09:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-21 Cont ID  
Sent By rmcphers Date 2023-06-21 Time 13:37 Rev Time 0.00
Received By rmcphers Date 2023-06-21 Time 13:37 Sent To  
Notes
2023-06-21 13:37:59SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE INDEX DRAWING DOES NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By rmcphers Date 2023-05-02 Time 08:44 Rev Time 0.00
Received By rmcphers Date 2023-05-02 Time 08:44 Sent To  
Notes
2023-05-02 08:45:45SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE CIVIL DRAWINGS FROM RICHARD REIKENIS P.E. DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-09 Cont ID  
Sent By rmcphers Date 2023-03-09 Time 11:30 Rev Time 0.00
Received By rmcphers Date 2023-03-09 Time 11:30 Sent To  
Notes
2023-02-23 14:23:04MECHANICAL DIGITAL SIGNATURES APPROVED ME
  
2023-02-17 10:49:52PLUMBING (P) PLANS SIGS APPROVED.

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-13 Cont ID  
Sent By vbroglia Date 2023-07-13 Time 15:28 Rev Time 0.00
Received By vbroglia Date 2023-07-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-11 Cont ID  
Sent By vbroglia Date 2023-05-11 Time 16:03 Rev Time 0.00
Received By vbroglia Date 2023-05-11 Time 16:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-31 Cont ID  
Sent By AVolcy Date 2023-03-31 Time 11:11 Rev Time 0.00
Received By avolcy Date 2023-03-31 Time 11:11 Sent To  
Notes
2023-03-31 11:13:5903.31.2023 - FAILED
  
 SEPARATE PERMIT REQUIRED FOR:
 FENCE/WALL, AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, OTHER
  
 THE VALUE OF THE CONSTRUCTION ($1,516,798.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($0.00) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE
 PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR
 ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO
 CONFORMITY.
  
 **** REVIEWD BY ****
 GAISHA (ANNE CLERISSE) VOLCY
 PLANNER
 [email protected]
  