| 2023-02-24 16:34:57 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | 1.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE |
| | SPECIFICATION SHEETS OF A FLUID APPLIED MEMBRANE. |
| | FBC R 703.4, FBC B 1405.4: |
| | A FLASHING DETAIL OR SPECIFICATION IS REQUIRED. THIS |
| | COMMENT CAN BE RESOLVED BY DOING ONE OF THE FOLLOWING: |
| | |
| | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED |
| | AND NOTE THE CODE REFERENCE ??? FBC R 703.4; FBC B |
| | 1405.4: |
| | EXAMPLE "FLASHING IN ACCORDANCE WITH FBC R 703.4/B |
| | 1405.4 WILL BE INSTALLED". |
| | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS |
| | MAY INCLUDE MORE THAN ONE OPTION |
| | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN |
| | ONE |
| | OPTION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| 2023-02-03 16:04:29 | SIGNATURE REVIEW FAILED |
| | |
| | PAPER PLANS SUBMITTED DETAIL AN ENGINEERS SEAL WITH A |
| | DIGITAL SIGNATURE. |
| | |
| | THERE ARE ONLY TWO WAYS IN WHICH PLANS PREPARED BY AN |
| | ENGINEER OR ARCHITECT ARE ACCEPTABLE AND WILL PASS A |
| | SIGNATURE REVIEW. SEE THE DESCRIPTION BELOW. |
| | |
| | 1) PAPER DOCUMENTS SUBMITTED MUST HAVE A SEAL WITH A |
| | WET SIGNATURE. |
| | |
| | 2) DIGITALLY SUBMITTED DOCUMENTS MUST HAVE A SEAL WITH |
| | A DIGITAL SIGNATURE. PLEASE NOTE IT IS EXTREMELY |
| | IMPORTANT THAT ALL DIGITAL SIGNATURES ARE VERIFIABLE |
| | THROUGH ADOBE OR BLUEBEAM SOFTWARE |
| | |
| | DIGITALLY SUBMITTED DOCUMENTS ARE PREFERRED |
| | |
| | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF |
| | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | DIGITALLY SEALED AND SIGNED. |
| | |
| | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS |
| | FOLLOWING PROJECTDOX INSTRUCTIONS |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |