Plan Review Details - Permit 23010193
Plan Review Stops For Permit 23010193
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By jwitmer Date 2023-03-20 Time 08:10 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:42 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-07 16:42:27TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 14:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By jwitmer Date 2023-03-20 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2023-03-20 Time 08:00 Sent To  
Notes
2023-03-20 08:08:39 
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:41 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-07 16:41:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23010193
 ADD: 1801 S FLAGLER DR # 1703
 CONT: ECO BUILDING SOLUTIONS
 TEL: 954-884-3431
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 07TH/ 2023
 ACTION: DENIED
  
 1) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 1C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-04-10 Cont ID  
Sent By mpeterso Date 2023-04-10 Time 11:20 Rev Time 0.00
Received By mpeterso Date 2023-04-10 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-27 Cont ID  
Sent By mpeterso Date 2023-03-27 Time 09:30 Rev Time 0.00
Received By mpeterso Date 2023-03-27 Time 09:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By mpeterso Date 2023-01-30 Time 11:44 Rev Time 0.00
Received By mpeterso Date 2023-01-30 Time 10:36 Sent To  
Notes
2023-01-30 11:46:26ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL
 NEW AND EXISTING ELECTRIC WORK. CLEARLY DISTINGUISH NEW
 WORK VERSUS WORK TO REMAIN. PLEASE INCLUDE ALL NEW
 APPLIANCES TO BE INSTALLED. FBC 107.2, CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL
  
 2) PLEASE PROVIDE KITCHEN COUNTER AND APPLIANCE LAYOUT
 AND DETAIL ALL ELECTRICAL RECEPTACLES AS REQUIRED PER
 NEC 210.52. A RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH WALL COUNTERTOP AND WORK SURFACE THAT IS 300 MM
 (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE
  
 3) PLEASE PROVIDE AN ELECTRIC PANEL SCHEDULE DETAILING
 ALL CIRCUITS REQUIRED, CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION FOR EACH CIRCUIT. PLEASE INDICATE WHETHER
 CIRCUIT IS NEW OR EXISTING. FBC 107.2 AND NEC 215.5
  
 4) PLEASE PROVIDE AN ACCURATE ELECTRIC RISER DETAILING
 ELECTRIC PANEL, CONDUIT, CONDUCTOR AND OVERCURRENT
 PROTECTION SIZES. PLEASE INDICATE EQUIPMENT AS NEW OR
 EXISTING. NEC 215.5
  
 5) PROVIDE AN ELECTRIC LOAD CALCULATION DETAILING ALL
 ELECTRIC LOADS, AND APPLIANCES SUCH AS WATER HEATERS,
 RANGES, AIR CONDITIONING EQUIPMENT, ETC. NEC 220.40,
 THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE
 LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS
 SUPPLIED
  
 6) PLEASE DETAIL RECEPTACLES THAT APPEAR TO BE MISSING
 IN ACCORDANCE WITH NEC 210.52, RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET AND ANY SPACE 600 MM
 (2 FT) OR MORE IN WIDTH
  
 7) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY
 WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC
 FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT
 RECEPTACLE REQUIREMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-17 Cont ID  
Sent By cwalker Date 2023-03-17 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-17 09:09:01FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE, INCLUDING PAINT, DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ANY CHANGES, OR MODIFICATIONS TO ANY EXISTING LIFE
 SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE ALARM) SHALL
 BE PERFORMED BY PROPERLY LICENSED CONTRACTORS UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By cwalker Date 2023-01-20 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-01-20 09:52:17FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE, INCLUDING PAINT, DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF
 FIRE WATCH.
  
 (4) ANY CHANGES, OR MODIFICATIONS TO ANY EXISTING LIFE
 SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM) SHALL
 BE PERFORMED BY PROPERLY LICENSED CONTRACTORS UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-10 Cont ID  
Sent By mpeterso Date 2023-04-10 Time 11:20 Rev Time 0.00
Received By mpeterso Date 2023-03-30 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-27 Cont ID  
Sent By mpeterso Date 2023-03-27 Time 09:30 Rev Time 0.00
Received By mpeterso Date 2023-03-16 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-02-07 Time   Rev Time 0.00
Received By amcgrego Date 2023-01-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:42 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-04-07 Cont ID  
Sent By medwards Date 2023-04-07 Time 14:35 Rev Time 0.00
Received By medwards Date 2023-04-07 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-17 Cont ID  
Sent By medwards Date 2023-03-17 Time 14:00 Rev Time 0.00
Received By medwards Date 2023-03-17 Time 14:00 Sent To  
Notes
2023-03-17 14:04:28PER THE NARRATIVE THAT STATES THERE IS TO BE NO NEW
 DUCT WORK, PLEASE REMOVE THE NOTE 13 THAT STATES -
 REMOVE HVAC REGISTERS AND PREPARE TO REROUTE DUCTWORK
 TO NEW REGISTER LOCATION ON SHEET D1.01
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-20 Cont ID  
Sent By medwards Date 2023-01-20 Time 16:04 Rev Time 0.00
Received By medwards Date 2023-01-20 Time 16:04 Sent To  
Notes
2023-01-20 16:05:09PROVIDE A MECHANICAL DRAWING SHOWING THE REVISED DUCT
 WORK CALLED FOR ON SHEET D1.01 NOTE 13.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 09:57 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 16:07 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 15:59 Sent To  
Notes
2023-03-17 16:10:442ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23010193
 3/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.01 WHICH INCLUDES THE PLUMBING NOTES AND
 DETAILS IS NOT DIGITALLY SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By ccole Date 2023-01-23 Time 13:37 Rev Time 0.00
Received By ccole Date 2023-01-23 Time 12:30 Sent To  
Notes
2023-01-23 13:38:351ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010193
 1/23/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS D1.01 & A1.01: PLEASE PROVIDE A CLEAR SCOPE
 OF WORK FOR PLUMBING ON THE PLAN WITH NOTES AND DETAILS
 AS APPLICABLE- SEC. 107.2.1 WPB. IT APPEARS THE BATH
 FIXTURES WILL REMAIN AND THE KITCHEN SINK, FAUCETS,
 DISHWASHER ARE TO BE REPLACED IN THE SAME LOCATION.
 PLEASE CONFIRM AND NOTE THAT RISER DRAWINGS ARE
 REQUIRED FOR RELOCATED FIXTURES- SEC. 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 10:05 Rev Time 0.00
Received By ccole Date 2023-04-05 Time 10:05 Sent To  
Notes
2023-04-05 10:06:35HURST ENGINEER SELF CERTIFIED NOTIFIED AND ADDED TO
 LIST.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 16:13 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 16:13 Sent To  
Notes
2023-03-17 16:17:022ND SIGNATURE REVIEW
 PERMIT- 23010193
 3/17/23
  
 CODES IN EFFECT:
  
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS T1.01, A1.01, A2.01, A5.00, E100, E101, E301,
 E401, E701 AND THE COVER SHEET ARE NOT DIGITALLY SIGNED
 AND SEALED BY THE ARCHITECT OF RECORD- FL STATUTE
 481.221 AND SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE
 CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 16:43 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***