Plan Review Details - Permit 23010192
Plan Review Stops For Permit 23010192
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 12:38 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-04-04 Cont ID  
Sent By aoliver Date 2023-04-04 Time 08:13 Rev Time 0.00
Received By aoliver Date 2023-04-04 Time 08:13 Sent To  
Notes
2023-04-04 08:13:42PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 11:31 Sent To  
Notes
2023-02-23 12:34:45PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-15 Cont ID  
Sent By rmcphers Date 2023-05-15 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2023-05-15 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 12:38 Sent To  
Notes
2023-04-26 13:10:16 
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE COVER SHEET "T-000.00 AND ALL OF THE "G" AND "A"
 DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 11:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By rperdomo Date 2023-04-03 Time 12:38 Rev Time 0.00
Received By rperdomo Date 2023-04-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By rperdomo Date 2023-02-07 Time 12:06 Rev Time 0.00
Received By rperdomo Date 2023-02-07 Time 12:06 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-02-13 Cont ID  
Sent By rrossano Date 2023-02-13 Time   Rev Time 0.00
Received By rrossano Date 2023-02-13 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-15 Cont ID  
Sent By pleduc Date 2023-05-15 Time   Rev Time 0.00
Received By pleduc Date 2023-05-15 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-25 Cont ID  
Sent By pleduc Date 2023-04-25 Time   Rev Time 0.00
Received By pleduc Date 2023-04-25 Time 14:51 Sent To  
Notes
2023-04-25 14:52:12FIRE PROVISO:
  
 THE PROPOSED WORK MAY REQUIRE MODIFICATIONS TO THE FIRE
 SPRINKLER HEAD AND FIRE ALARM COVERAGE.
  
 ANY DROP DOWN CEILINGS WOULD CONSTITUTE AN OBSRUCTION
 TO THE FIRE PROTECTION ABOVE.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By pleduc Date 2023-01-20 Time   Rev Time 0.00
Received By pleduc Date 2023-01-18 Time 15:00 Sent To  
Notes
2023-01-20 12:26:54FIRE PROVISO:
  
 THE PROPOSED WORK MAY REQUIRE MODIFICATIONS TO THE FIRE
 SPRINKLER HEAD AND FIRE ALARM COVERAGE.
  
 ANY DROP DOWN CEILINGS WOULD CONSTITUTE AN OBSRUCTION
 TO THE FIRE PROTECTION ABOVE.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-15 Cont ID  
Sent By lmarchan Date 2023-05-15 Time 13:24 Rev Time 0.00
Received By lmarchan Date 2023-05-12 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-05-09 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-24 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-04 Cont ID  
Sent By aoliver Date 2023-04-04 Time 14:34 Rev Time 0.00
Received By jgomez Date 2023-03-14 Time 16:53 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 11:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 14:19 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 16:38 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-05-09 Cont ID  
Sent By ccole Date 2023-05-09 Time 16:33 Rev Time 0.00
Received By ccole Date 2023-05-09 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 14:28 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By ccole Date 2023-01-27 Time 14:48 Rev Time 0.00
Received By ccole Date 2023-01-27 Time 13:26 Sent To  
Notes
2023-01-27 14:49:031ST REVIEW FBC-2020 PLUMBING
 PERMIT-23010192
 1/27/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-100.02 & P-200.01: THE PLANS SHOW HAND
 SINKS #6, #207A DRAINS, AND THE ICE BIN 207E DRAIN
 DISCHARGING INTO THE GREASE WASTE LINE WHICH IS
 PROHIBITED PER SEC. 1003.3.1 FBC P. GREASE INTERCEPTORS
 SHALL RECEIVE WASTE ONLY FROM FIXTURES THAT ALLOW FATS,
 OILS, OR GREASE TO BE DISCHARGED.
  
 2) P-200.01 DETAIL 2: THE DETAIL DOES NOT SHOW HOT
 WATER CONNECTIONS TO THE SINKS (207A & 207B) & THE
 PITCHER RINSER (207F). HOT WATER IS REQUIRED PER SEC.
 607.1 FBC P.
  
 3) P-200.01: PLEASE DETAIL THE MEANS OR METHOD USED TO
 LIMIT THE HOT WATER TEMPERATURE DELIVERY FROM THE
 SINKS- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-15 Cont ID  
Sent By rmcphers Date 2023-05-15 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2023-05-15 Time 09:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 13:11 Sent To  
Notes
2023-04-26 13:11:49SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE COVER SHEET "T-000.00 AND ALL OF THE "G" AND "A"
 DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-04 Cont ID  
Sent By jgomez Date 2023-04-04 Time 14:21 Rev Time 0.00
Received By jgomez Date 2023-04-04 Time 13:45 Sent To  
Notes
2023-04-04 14:21:35SIGNATURE REVIEW
  
 1- ALL ARCHITECTURAL DRAWINGS IN THE SIGNATURE FOLDER
 SHOW AN INVALID DIGITAL SIGNATURE BECAUSE THE DRAWINGS
 WERE ALTERED AFTER THE DIGITAL SIGNATURE WAS ISSUED.
 ALL DRAWINGS/DOCUMENTS NEED TO HAVE VERIFIABLE ORIGINAL
 DIGITAL SEAL/SIGNATURE AS REQUIRED BY CHAPTER 481 F..S.
 WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- ALL PLUMBING AND MECHANICAL PLANS IN THE SIGNATURE
 FOLDER ARE SIGNED AFTER THE DIGITAL SIGNATURE EXPIRED.
 THE DIGITAL SIGNATURE IS VALID FROM 4/27/200 TO
 9/12/2022. PLANS WERE SIGNED ON 2022/12/01. NEED TO
 SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE CURRENT
 DIGITAL SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By ccole Date 2023-01-27 Time 15:21 Rev Time 0.00
Received By ccole Date 2023-01-27 Time 13:26 Sent To  
Notes
2023-01-27 15:21:551ST DIGITAL SIGNATURE REVIEW
 PERMIT- 23010192
 1/27/23
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ELECTRICAL PLAN SHEETS IN THE SIGNATURE FILE DO
 NOT HAVE VERIFIABLE DIGTAL SIGNATURES AND SEALS BY THE
 ENGINEER OF RECORD AS REQUIRED BY FL. STATUTE 471.025,
 AND SECTION 61G15-23.005 FAC
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  